AUKS DC Inverter 1 Drive1 50HZ R410A General description Contents Part 1 General description....................3 Part 2 Indoor unit ........................6 Part 3 Universal outdoor unit ....................78 Part 4 Trouble shooting ....................110 Part 5 Controller........................138 Part 6 Sensor resistance table ..................154...
AUKS DC Inverter 1 Drive 1 50HZ R410A Indoor unit Part 2 Indoor unit Four-way cassette ........................8 Ceiling & floor type ......................34 Ducted Type Indoor Unit ....................56...
Page 7
AUKS DC Inverter 1 Drive1 50HZ R410A General description...
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette 1. Feature DC Inverter type Four-way cassette unit (heat pump), is installed under the ceiling, compared with Floor &Standing type A/C, it has following advantages: saving room space; Ceiling installation combining with the decoration, makes the room more elegant;...
Page 10
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette Function introduction ALCA-H*4*DR1 ALCA-H*5*DR1 Function Name 18/4 24/4 36/4 48/5 60/5 ○ ○ high pressure protection - - - ○ ○ - - - low pressure protection ○ ○ ○ ○...
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette 3. Capacity Amendment 3.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling 16~49℃ Ambient temperature Heating -15~24℃ 3.2 Amendment coefficient of cooling capacity under different indoor/outdoor DB/WB temperature Indoor air inlet temperature℃...
Page 16
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette 3.4 Amendment coefficients of heating and cooling capacity under different height drop K3 Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit - Height of Indoor Unit...
Page 17
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette Bend and Oil Loop Conversion tablet Type Bend Oil Loop Pipe Dia.(mm) 6.35 0.10 9.52 0.18 12.70 0.20 15.88 0.25 19.05 0.35 22.02 0.40 Equivalent Pipe length L=Actual Pipe length L+ Bend Qty× Equivalent pipe bend length+ Oil Loop Qty ×...
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette 6. Installation 6.1 Preparation before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe Acetylene cylinders, oxygen cylinders (when longer pipe...
Page 23
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette 6.3 Installation precaution ◇ Hanging location should be able to support the unit’s weight, there should be no increase in noise and vibration. If the hanging location needs reinforcement, it should be reinforced before installation;...
Page 24
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette 6.5 Indoor unit suspension ◇ Select the suspension foundation: The suspension foundation is a structure of either wooden frame or reinforced concrete. It must be firm and reliable to bear at least 4 times weight of itself and capable of bearing vibration for long periods.
Page 25
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette 6.6 Drainage pipe installation The drain pipe should be properly insulated to prevent the generation of condensation. Heat insulation material: the thickness of rubber insulation pipe should be more than 8mm ◇...
Page 26
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette pipeline fluently, and carefully observe the junction to ensure that there is no water leakage. If the unit is installed in the newly built house, strongly recommend that this test taken before the ceiling installation.
Page 27
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette Notes: 1.Only under special usage that it is allowed to connect to duct pipe and the length of the duct pipe should be less than 5 meters. 2. Using the duct that can prevent frost and noise.
Page 30
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette ALCA-H24/4DR1, ALCA-H36/4DR1, ALCA-H48/5DR1, ALCA-H60/5DR1 ALCA-H24/4DR1 BOM Code Chinese name Part Name Quantity Remark 钣金套件 Sheet metal suite 16421010000034 围板 A Coaning A 16421010000035 围板 B Coaning B 16421010000036 围板 C Coaning C...
Page 32
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette BOM Code Chinese name Part Name Quantity Remark 钣金套件 Sheet metal suite 16421010000034 围板 A Coaning A 16421010000035 围板 B Coaning B 围板 C 16421010000036 Coaning C 16321005000019 Chassis assembly 底盘组件...
Page 33
AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette ALCA-H48/5DR1, ALCA-H60/5DR1 BOM Code Chinese name Part Name Quantity Remark Sheet metal suite 钣金套件 16421010000031 围板 A Coaning A 围板 B 16421010000032 Coaning B 16421010000033 围板 C Coaning C 16321005000019 底盘组件...
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type Ceiling & floor type 1.Feature ..........................29 2.Specification ........................31 3.Capacity amendment.......................33 4.Dimension.........................43 5.Electrical wiring ......................36 6.Installation ........................38 7.Explode view ........................40...
Page 35
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 1. Feature Ceiling& Foor type A/C (Heat pump) can be installed under the ceiling and also on the floor. Compared with normal Floor &Standing type A/C, it can be hoisted under the ceiling,saving room space, it is also the updating Product for Floor &...
Page 36
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type Function introduction ALCF-H*4*DR1 ALCF-H*5*DR1 Function Name 18A4 24A4 36A4 48A5 60A5 - - - ○ ○ high pressure protection ○ ○ - - - low pressure protection ○ ○...
Page 37
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 2. Specfication Indoor ALCF-H18/4DR1 ALCF-H24/4DR1 ALCF-H36/4DR1 Model Outdoor AL-H18/4DR1(U) AL-H24/4DR1(U) AL-H36/4DR1(U) V~,Hz, Power Supply 220~240,50,1 220~240,50,1 220~240,50,1 Btu/h 20000-18000-5500 26500-24000-7200 40000-36000-10800 Cooling 5610-5100-1530 7920-7200-2160 11000-10000-3000 Capacity Btu/h 20140-19000-4750 29700-27000-6750...
Page 38
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type Drainage R3/4in(DN20) R3/4in(DN20) R3/4in(DN20) Max. Refrigerant Pipe Length Max. Difference In Level ℃ Operation Temperature Range 16~32 16~32 16~32 Ambient Temperature ℃ 16~49/-15~24 16~49/-15~24 16~49/-15~24 Range(Cooling/Heating) Power Wiring( Indoor) 3×1mm...
Page 39
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type a.Number Of Row b.Tube Pitch(a)x Row Pitch(b) 20.5×12.7 22×19.05 c.Fin Spacing Hydrophilic aluminum Hydrophilic aluminum d.Fin Material Indoor Coil e.Tube Outside Dia.and φ7, Inner grooved φ7.94, Inner grooved Material f.Coil Length x Height x Width...
Page 40
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 3. Capacity amendment 3.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling 16~49℃ Ambient temperature Heating -15~24℃...
Page 41
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 3.4 Amendment coefficients of heating and cooling capacity under different height drop K3 Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit - Height of Indoor Unit...
Page 42
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type Bend and Oil Loop Conversion tablet Type Bend Oil Loop Pipe Dia.(mm) 6.35 0.10 9.52 0.18 12.70 0.20 15.88 0.25 19.05 0.35 22.02 0.40 Equivalent Pipe length L=Actual Pipe length L+ Bend Qty× Equivalent pipe bend length+ Oil Loop Qty ×...
Page 43
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 4. Dimension ALCF-H18/4DR1 ALCF-H24/4DR1, ALCF-H36/4DR1 ALCF-H48/5DR1, ALCF-H60/5DR1...
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 5. Electrical wiring diagram between indoor and outdoor unit ALCF-H18/4DR1, ALCF-H24/4DR1, ALCF-H36/4DR1, ALCF-H48/5DR1, ALCF-H60/5DR1...
Page 45
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type ALCF-H18/4DR1, ALCF-H24/4DR1, ALCF-H36/4DR1 ALCF-H48/5DR1, ALCF-H60/5DR1...
Page 46
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type Introduction of control board socket...
Page 47
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 6. Installation 6.1 Preparation and equipments before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe...
Page 48
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 6.3 Installation precaution ◇ Hanging location should be able to support the unit’s weight, there should be no increase in noise and vibration. If the hanging location needs reinforcement, it should be reinforced before installation;...
Page 49
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type ◇ Adjust the relative position of the suspension hook on the suspension bolt so that the unit can be in level position in all directions. Check with a level gauge after the installation is complete in order to ensure that the indoor unit is horizontal, otherwise it will cause water leakage, air leakage etc.
Page 50
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 7. Explode view ALCF-H18/4DR1 BOM Code Chinese Name Part Name Quantity 16420012000002 滤网 Air-inlet filter 16420010000002 Air-inlet grill(white) 格栅 16420015000002 左装饰板 Left side adornment plank 16421038000207 The electricity controls a box 电控盒...
Page 51
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 16420005000005 Sway a breeze leaf 导风门 16420014000016 The crest covers plank 顶盖板 16428001000023 Topmost foam 顶泡沫 16320006000007 Air guide louver assembly 导风架 16430001000022 步进电机 35BYJ46-QC50 Step motor 16430001000018 (ROHS)步进电机 35BYJ46-QC120...
Page 52
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type BOM Code Chinese name Part Name Quantity 16420012000002 Air-inlet filter 滤网 16420010000002 格栅 Air-inlet grill(white) 16420012000003 In the center filter net 中滤网 16420010000003 Air-inlet grill(white) 中格栅 16420015000002 左装饰板 Left side adornment plank...
Page 53
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 16444007000003 Motor lengthen axes 加长轴 16421002000011 轴承固定座 Bearing base 16421002000219 Bearing top cover 橡胶轴承压板 16421002000219 橡胶轴承 Rubber bearings 11222023000333 R 显示灯板 SX-DISP(ZDJ)-02-SYE1 Display board 16420017000002 显示盒 Display board cover...
Page 54
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type 16427001000010 端子板 5 位(600V 4mm2)AB Terminal board 16422005000033 (ROHS)变压器 Transformer TDB-14-B4B(PTC) 11330010000095 (ROHS)电容 5μF/450V A.C Capacitor 11222009002538 R 控制板 PCB board QRD-SN3F(18-60)K(485)-SYE1(S 16444002000014 Top plastics 上蜗壳 16444002000015 下蜗壳 Low plastics...
Page 55
AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type...
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit Ducted Type Indoor Unit 1. Feature ........................57 2. Specfication ......................5 9 3. Capacity amendment....................62 4. Dimension ......................65 5. Electrical wiring and connection ................. 66 6. Fan Performance....................69 7.
Page 57
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 1. Feature Duct type air conditioner (Heat pump), named for the Duct can be installed to Connect with air outlet and inlet. Medium ESP Duct type (50~80Pa). Application occasions: Small super market, hotel, restaurant, office, meeting room and so on.
Page 58
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit Function introduction ALMD-H*4*DR1 ALMD-H*5*DR1 Function Name 18A4 24A4 36A4 48A5 60A5 ○ ○ - - - high pressure protection ○ ○ - - - low pressure protection ○ ○...
Page 59
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 2. Specfication Indoor ALMD-H18/4DR1 ALMD-H24/4DR1 ALMD-H36/4DR1 Model Outdoor AL-H18/4DR1(U) AL-H24/4DR1(U) AL-H36/4DR1(U) V~,Hz, Power Supply 220-240/50/1 220-240/50/1 220-240/50/1 Btu/h 20000-18000-5500 26500-24000-7200 40000-36000-10800 Cooling 5610-5100-1530 7920-7200-2160 11000-10000-3000 Capacity Btu/h 20140-19000-4750 29700-27000-6750...
Page 60
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit Application Area 21-35 28-47 42-70 Qty’per 20’& 40’&40HQ(Only For 42/90/111 42/90/108 36/72/87 Reference) Note: 1. Working condition of the cooling capacity measured: Inside the room DB temperature 27 ℃ ,WB temperature19℃;Outside of the room DB temperature 35℃,WB temperature 24℃;Working condition...
Page 61
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit Drainage R3/4in(DN20) R3/4in(DN20) Max. Refrigerant Pipe Length Max. Difference In Level ℃ Operation Temperature Range 16~32 16~32 ℃ Ambient Temperature Range(Cooling/Heating) 16~49/-15~24 16~49/-15~24 Power Wiring( Indoor) 3×1mm 3×1mm Connection Wiring Power Wiring( Outdoor) 5×1.5mm...
Page 62
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 3. Capacity amendment 3.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling 16~49℃ Ambient temperature Heating -15~24℃...
Page 63
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit - Height of Indoor Unit Different Heating Capacity modified coefficients at different height:...
Page 64
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit Equivalent Pipe length L=Actual Pipe length L+ Bend Qty× Equivalent pipe bend length+ Oil Loop Qty × Equivalent Oil Loop length Sample: ALCA-H48/5 Actual Pipe length is 25 meters, Gas pipe diameter is 19.05mm. If there’s 5 bends and 2 oil loops during the installation, then the equivalent pipe length should be: L=25+0.35×5+2.4×2=31.5(m)
Page 65
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 4. Dimension ALMD-H18/4DR1, ALMD-H24/4DR1, ALMD-H36/4DR1 4-12×30 ALMD-H48/5DR1, ALMD-H60/5DR1 1250 4-12×30 1300...
Page 66
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 5. Electrical wiring and connection ALMD-H18/4DR1, ALMD-H24/4DR1, ALMD-H36/4DR1, ALMD-H48/5DR1, ALMD-H60/5DR1...
Page 67
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit ALMD-H18/4DR1, ALMD-H24/4DR1, ALMD-H36/4DR1 ALMD-H48/5DR1, ALMD-H60/5DR1...
Page 68
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit Introduction of control board socket...
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 7. Installation 7.1 Preparation and equipments before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe...
Page 72
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit ◇There is no obstacles getting in the way of air circulation, cold air can evenly spread to all corners of the room; ◇In order to facilitate maintenance and repair, there should be certain distance between indoor unit and obstacles;...
Page 73
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 7.6 Duct pipeline installation ◇Using canvas to connect between indoor unit and duct pipeline, in order to save unnecessary vibration, as to the detail connection method please refer to the following picture.
Page 74
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit ◇Mounting hole set up: please use certain instrument to dig a square hole with 88*88mm on the ceiling ◇Remote controller receiver installation. Hold the two sides (with clip sides) of the receiver, set the spring clip in the vertical way then put it into the mounting hole, if the two sides of the receiver is in the same level with the ceiling the installation is finished.
Page 75
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 8. Explode view ALMD-H18/4DR1, ALMD-H24/4DR1, ALMD-H36/4DR1 Chinese Name Part Name Quantity Remark Evaporator part 蒸发器总成 Evaporator assembly 蒸发器组件 Evaporator liquid input pipe assembly 蒸发器出气管组件 Evaporator gas output pipe assembly 蒸发器进液管组件...
Page 76
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 14.4 Up&down france 上下过滤器法兰 Boarding 围板 Electric assembly 电控盒总成 QRD-SN3F(1 16.1 PCB board 8-60)K(485)- 控制板 SYE1(SY) 16.2 TDB-14-B4B( Transformer 变压器 PTC) 16.3 Sensor 15K3950 1 回风温度传感器 16.4 Sensor 20K3950 2 盘管温度传感器...
Page 77
AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit Chinese Name Part Name Quantity Remark Evaporator part 蒸发器总成 蒸发器组件 Evaporator assembly Evaporator liquid input pipe 蒸发器集气管组件 assembly Evaporator gas output pipe 蒸发器进液管组件 assembly Valve board 阀板 Cover for electric components 电控盒盖...
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Part 3 Universal outdoor unit 1. Feature ........................79 2. Specification ......................80 3. Capacity Amendment .................... 83 4. Dimension ......................86 5. Electrical wiring and connection ................. 88 6. System Diagram..................... 93 7.
Page 79
AC inverter compressor, achieves high efficiency as well as low noise. ◇AUKS DC Inverter Air Conditioner adopts the advanced 180 sine wave DC Inverter driving technology. ◇ AUKS DC Inverter Air Conditioner adopts PD frequency control technology to well control the room temperature.
Page 80
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 2. Specification Model AL-H18/4DR1(U) AL-H24/4DR1(U) AL-H36/4DR1(U) V~,Hz, Power Supply 220~240,50,1 220~240,50,1 220~240,50,1 Max. Input Consumption 2400 3470 4360 Max. Current 12.1 17.5 19.8 40000-36000-1080 Btu/h 20000-18000-5500 26500-24000-7200 Cooling 5610-5100-1530 7920-7200-2160...
Page 81
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Max. Height ℃ Operation Temperature Range 16~32 16~32 16~32 Ambient Temperature ℃ 16~49/-15~24 16~49/-15~24 16~49/-15~24 Range(Cooling/Heating) 3×1mm 3×1mm 3×1mm Power Wiring(Indoor) Connection Power Wiring(Outdoor) 3×2.5mm 3×2.5mm 3×2.5mm Wiring Signal Wiring 2×1mm...
Page 82
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit c.Fin Pitch Hydrophilic aluminum Hydrophilic aluminum d.Fin Material e.Tube Outside Dia.And φ7.94, Inner grooved φ7.94, Inner grooved Material f.Coil Length x Height x Width 954×1320×38.1 954×1320×38.1 g.Heat Exchanging Area 54.84 54.84...
Page 83
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 3. Capacity Amendment 3.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling 16~49℃ Ambient temperature Heating -15~24℃ 3.2 Amendment coefficient of cooling capacity under different indoor/outdoor DB/WB temperature Indoor air inlet temperature℃...
Page 84
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit - Height of Indoor Unit Different Heating Capacity modified coefficients at different height:...
Page 85
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Equivalent Oil Loop length Sample: ALCA-H48/5 Actual Pipe length is 25 meters, Gas pipe diameter is 19.05mm. If there’s 5 bends and 2 oil loops during the installation, then the equivalent pipe length should be: L=25+0.35×5+2.4×2=31.5(m)
Page 86
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 4. Dimension AL–H18/4DR1(U) 4-10*19 AL–H24/4DR1(U) 4-10*19...
Page 87
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit AL–H36/4DR1(U) AL–H48/5DR1(U), AL–H60/5DR1(U) 4-10*19...
Page 88
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 5. Electrical wiring and connection AL–H18/4DR1(U), AL–H24/4DR1(U), AL–H36/4DR1(U)
Page 89
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit AL–H48/5DR1(U),AL–H60/5DR1(U)
Page 90
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Introduction of control board socket (Single phase) AL–H18/4DR1(U), AL–H24/4DR1(U), AL–H36/4DR1(U) Main control board Driver modular...
Page 91
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Introduction of control board socket (3 phase) AL–H48/5DR1(U), AL–H60/5DR1(U) Main control board Driver modular...
Page 92
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Filter board...
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 6. System Diagram AL-H18/4DR1(U) , AL-H24/4DR1(U), AL-H36/4DR1(U) Evaporator Stop valve(gas) Condenser T-outdoor ambient Four-way valve T-Condenser T-suction middle T-discharge inverter compressor T-indoor ambient T-indoor coil T-defrost Stop valve(liquid) Filter Filter...
Page 94
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 7. Explore View AL-H18/4DR1(U) , AL-H24/4DR1(U) AL-H18/4DR1(U) BOM Code Chinese Name Part Name Quan Remark tity 11321009000009 Top cover board 顶盖板 16324004000358 冷凝器总成 condenser assembly 11321017000030 Left-hand board 左侧板 11320009000040 420*148.8...
Page 97
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 11327002000035 R72W/BPS-4 压缩机 Compressor outside 11.1 mute cotton 机外围消音绵 A 11327002000003 DA250 压 缩 机 顶 盖 Compressor top mute 11.2 cotton 消音棉 11327002000004 DA250 压 缩 机 机 围...
Page 98
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit AL-H48/5DR1(U), AL-H60/5DR1(U) BOM Code Chinese Name Part Name Quant Remark 11321008000003 Cover electric 电器盖板 components 16427010000001 Insulation Gasket 绝缘垫片 16434099000396 cotton 电器盖板防水海绵 16421001000537 Right-hand board 右侧板 silencing cotton 聚氨酯消音绵板 1...
Page 99
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit insulation cotton 保温绵板 1 16421005000028 Top cover board 顶盖板 16330004000016 Electric assembly 控制器总成 11.1 16430007000201 Temperature sensor 温度传感器 XH10 1.3m(组件) 11.2 16422008000045 Communication wire (XH4Y-J) 通讯线 2 芯 0.22m 11.3...
Page 100
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 8. Installation 8.1 Preparation and equipments before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe...
Page 101
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 8.2 Connection piping installation Piping installation precaution Please choose the phosphorus deoxidation seamless copper pipe as the piping. ◇If use the lengthen piping needs welding: Please welding before fasten the nut, when welding using nitrogen gas to replace the air in the pipe in order to prevent oxidation.
Page 102
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Elbow and Oil loop conversion tablet Type Bend Oil Loop Pipe Dia.(mm) 6.35 0.10 9.52 0.18 12.70 0.20 15.88 0.25 19.05 0.35 22.02 0.40 Equivalent pipe length L=Actual Pipe length L+ Bend Qty× Equivalent pipe bend length+ Oil Loop Qty ×...
Page 103
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Heat insulation package of piping ◇ Use heat insulation material with good insulation performanCF to wrap the pipe. Notes Drainage pipe and connection piping should be wrapped by heat insulation material respectively or there...
Page 104
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Additional refrigerant charge When pipe length exceeds 5m, please add refrigerant according to the table below: Piping size) Additional refrigerant charge Connection piping Gas pipe Liquid pipe amount (kg/m) φ9.52×0.75mm φ6.35×0.75mm...
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Note: This chart is for explanation purposes. An actual installation will differ from this according to the site conditions. When making an oil trap the radius of the bend should be between 1.5 and 2 times the pipe diameter.
Page 106
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Power supply:220V~,50Hz Capacity Indoor power Outdoor Power supply Signal wire Model (BTU) cable power ALCA-H18/4DR1 18000 ALCF-H18/4DR1 3×1mm2 3×2.5mm2 2×1mm2 Outdoor unit ALMD-H18/4DR1 380-415V ALCA-H24/4DR1 3N~50Hz 24000 ALCF-H24/4DR1 3×1mm2 3×2.5mm2 2×1mm2...
Page 107
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit Notice: ◇ Compressor of AL-H36/5DR1(U) , AL-H48/5DR1(U), AL-H60/5DR1(U) are 3 phase power supply with phase sequence protection in its outdoor control board. Please be careful with wire connection. ◇ Be sure do’t make the drainage pipe flat while bundled.
Page 108
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 8.5 Daily maintenance Clean inhaler ◇ Before cleaning the filter, ensure the unit is switched off and the power is off; ◇ Forbidden to use water clean the filter , it will hurt PCB or get an electric shock;...
Page 109
AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit...
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Part 4 Trouble shooting 1. Main components of air conditioner................111 2. Electrical system main components................113 3. Poor efficiency explanation ..................114 4. Failure phenomenon....................114 5. Electric components malfunction inspection ............115 6.
Page 111
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 1. Main components of air conditioner Appellation Figuration and inner configuration Instruction function compressor: after refrigerant evaporate evaporator, compress the low temp and low pressure refrigerant gas, make the gas become...
Page 112
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Function of EXV: Utilize aperture and length change bring (Electronic pressure gap, control refrigerant flow expansion quantity and pressure. valve) EXV is controlled by PCB, more precisely. Function of 4 way valve:...
Page 113
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 2. Electrical system main components Appellation Figuration and inner configuration Instruction Function: Via program to control the relay, make every components on/off according to temperature and pressure variety, so to realize automatic...
Page 114
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 3. Poor efficiency explanation During the process of using air conditioner, some phenomenon seems to be malfunction but actually not. Thus when cooling effect does not to your expectation, the following factors have to be...
Page 115
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 5. Electric components malfunction inspection Component name Inspection methods Using multi-meter ohm phase, there is correct resistance value among windings (single Compressor phase compressor refers to specification, three phase compressor resistance approximately equal), resistance of winding should be infinite.
Page 116
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 6. Failure code display When AC has failure,outdoor control board、indoor digital tube and wire controller will display error codes. Indoor unit error code: Error Recovery Error code definition Problem possible reasons...
Page 117
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Temperature sensor failure or test temperature exceed Suction pipe limit. temperature of Sensor connection is incorrect. compressor "Ts" failure Outdoor unit PCB failure. Temperature sensor failure or test temperature exceed Coil Center limit.
Page 118
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting The communication between main PCB DC fan motor drive module failure and DC fan motor DC fan failure drive module failure Outdoor unit main control PCB ERROM Mail PCB failure module failure...
Page 119
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 7. Failure analysis 7.1 Anylisis and Solution for Failure without Failure Code Wired controller communication failure...
Page 120
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Communication failure between indoor and outdoor unit...
Page 121
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Outdoor protection(phase sequence)
Page 122
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Cooling high pressure protection...
Page 123
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Heating high pressure protection...
Page 124
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Cooling low pressure protection...
Page 125
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Heating low pressure protection...
Page 126
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Cooling exhaust temperature protection...
Page 127
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Heating exhaust temperature protection...
Page 128
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Refrigerant shortage or four way valve failure protection...
Page 129
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Sensor failure protection...
Page 130
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 7.2 Anylisis and Solution for Failure without Failure Code No action after power-on...
Page 131
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Poor effect...
Page 132
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting...
Page 133
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Abnormal sound or viberation...
Page 134
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting...
Page 135
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Abnormal odor...
Page 136
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Air switch action when air conditioner starting up...
Page 137
AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting Air conditioner water leakage...
AUKS DC Inverter 1 Drive1 50HZ R410A Controller Part 5 Controller 1. General information..................... 139 2. Remote Controller ......................140 3. Wired controller ......................145 4. Parameters setting of Indoor Unit ................151...
AUKS DC Inverter 1 Drive1 50HZ R410A Controller 1. General information Remote controller, wired controller, display panel and receiver Remote controller, wired controller, display panel receiver Available for Available for Available for Available for all models Available for all Cassette indoor Ceiling&Floor...
AUKS DC Inverter 1 Drive1 50HZ R410A Controller 2. Remote Controller 2.1 Basic condition of remote controller Name Figure Basic condition for operation 1.Power source Use 2 pcs No 7 batteries,working voltage:2.0V-5.0V; 2. Signal frequency:infrared frequency 38kHz; 3. Remote distance:max working distance is7m。...
Page 141
AUKS DC Inverter 1 Drive1 50HZ R410A Controller 4. “COOL”button * Press the COOL button, you can directly enter cooling mode. 5. “HEAT”button * Press the HEAT button, you can directly enter cooling mode. * Note: cooling only unit has no heating function.
Page 142
AUKS DC Inverter 1 Drive1 50HZ R410A Controller 15. “ECO”button * In cooling mode, press this button, the unit will run “ECO” economic operation mode which takes the least power consumption. * After running for 8h, it will automatically quit. You can press “ECO” button once again to quit.
Page 143
AUKS DC Inverter 1 Drive1 50HZ R410A Controller function. Push the button for the second time, cancel the swing function. Feeing button: Press this button for setting the feeling function.The LCD shows the actual room temperature when the function set and it shows the setting temperature when the function cancelled.The function is invalid when the appliance at the fan mode.
Page 144
AUKS DC Inverter 1 Drive1 50HZ R410A Controller MODE button: Select mode , push the button one time, then the operation modes will change in turn as Auto-Cooling-Dehumidify-Heating TEMP + button and TEMP - button: Temperature adjustment range: 16~32 FAN button: Change the fan speed will change in turn as: Low-Medium-High-Auto SWING button: Press this button for the first time when operation, it will start the swing function.
Page 145
AUKS DC Inverter 1 Drive1 50HZ R410A Controller 3. Wired controller 3.1 Basic condition of wired controller Name Figure Basic condition for operation 1. Power source:voltage DC 12V; Wired 2. Work temperature range of PCB:(-10~+70)℃; controller 3. Work humidity range of PCB:RH20%~RH90%;...
Page 146
AUKS DC Inverter 1 Drive1 50HZ R410A Controller 2. After the setting of sleeping mode,the cooling operation enables the set temperature to increase 1℃ after 1 hour and another 1℃ auto matically after 1hour. 3. After the setting of sleeping mode,the heating operation enables the set temperature to drop 2 ℃...
Page 147
AUKS DC Inverter 1 Drive1 50HZ R410A Controller Wired controller: XK-05...
Page 148
AUKS DC Inverter 1 Drive1 50HZ R410A Controller...
Page 149
AUKS DC Inverter 1 Drive1 50HZ R410A Controller Installation of wired controller...
Page 150
AUKS DC Inverter 1 Drive1 50HZ R410A Controller Wired controller: XK-01 ON/OFF button Switch the unit ON/OFF. Mode button: Select mode , push the button one time, then the operation modes will change in turn as below: Auto-Cooling-Dehumidify-Heating Temp + button and Temp - button: Press the button can adjust temperature. Temperature adjustment range: 16~32℃.
Page 151
AUKS DC Inverter 1 Drive1 50HZ R410A Controller 4. Parameters setting of Indoor Unit Indoor models and parameters can be set by remote control, wired remote control. Setting of Indoor Model Based on Remote Controller Serial No. Setting Value (1).With the controller off, pressing the two white button simultaneously more than 5 seconds or more to enter parameters settting.
Page 152
AUKS DC Inverter 1 Drive1 50HZ R410A Controller Setting of Indoor Model Based on Wired remote Controller Indoor NO. Parameter NO. Corresponding parameter value Temp +/- button Clock +/- button Mode button Filter Net button (1).Press [Filter Net Button] for 5 seconds, Indoor number “01” will be displayed in temperature zone of LCD screen and “0101”...
Page 153
AUKS DC Inverter 1 Drive1 50HZ R410A Controller Setting of Indoor Model Based on Wired remote Controller Parameter Parameter meaning Default Min. Max. Description Numbe valu Quiet function 0-Normal selection 1-Silent mode Auto restart function 0- With auto-restart function 1- Without auto-restart function...