13. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: XR60C frontal 32x74 mm; depth 60mm;
XR60D 4 DIN modules 70x85 mm; depth 61mm
Mounting: XR60C panel mounting in a 71x29mm panel cut-out
XR60D DIN RAIL mounted in a omega (3) din rail
Protection: IP20; Frontal protection: XR60C IP65 with frontal gasket RG-C (optional).
Connections: Screw terminal block 2,5 mm
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac 10%,
50/60Hz, 110Vac 10%, 50/60Hz
Power absorption: 3VA max
Display: 3 digits, red LED, 14,2 mm high; Inputs: 2 NTC or PTC probes.
Digital input: free contact
Relay outputs: compressor SPST relay 8(3) A, 250Vac or SPST relay 16(6)A 250Vac
defrost: SPDT relay 8(3) A, 250Vac
fan: SPST relay 8(3) A, 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B; Pollution grade: normal;Software class: A.
Operating temperature: 0÷60 °C;Storage temperature: -30÷85 °C.
Relative humidity: 2085% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
14. CONNECTIONS
14.1 XR60C – 12VAC/DV OR 24 VAC/DV
8 ( 3 ) A
M a x
8 ( 3 ) A 2 5 0 V ~
1 6 A
1 2 3 4 5
N . C .
C o m p
D e f
F a n
L i n e
NOTE: The compressor relay is 8(3)A or 16(6)A according to the model.
24Vac/dc supply: connect to the terminals 7 and 8.
14.2 XR60C – 120VAC OR 230 VAC
8 ( 3 ) A
M a x
8 ( 3 ) A 2 5 0 V ~
1 6 A
1 2 3 4 5
N . C .
C o m p
D e f
F a n
L i n e
NOTE: The compressor relay is 8(3)A or 16(6)A according to the model.
120Vac supply: connect to the terminals 6 and 7.
14.3 XR60D: 8A COMPRESSOR
1 2 3
4
8(3)A/250Vac
13 14 15 16 17 18 19 20 21
n.c.
Comp
Line
24Vac/dc supply: connect to the terminals 11 and 12.
120Vac supply: connect to the terminals 11 and 12.
230Vac supply: connect to the terminals 11 and 12.
1592007251 XR60C-D GB r1.0 08.04.2015
2
wiring.
9 1 01 11 2
6
7
8
H o t K e y
9 1 01 11 2
6
6
7
H o t K e y
Power
Supply
5
6
11 12
8(3)A/250Vac
8(3)A/250Vac
n.c.
14.4 XR60D: 20A COMPRESSOR
Line
24Vac/dc supply: connect to the terminals 11 and 12.
120Vac supply: connect to the terminals 11 and 12.
230Vac supply: connect to the terminals 11 and 12.
15. DEFAULT SETTING VALUES
Label
Set Set point
Hy
Differential
LS
Minimum set point
US
Maximum set point
Ot
Thermostat probe calibration
P2P Evaporator probe presence
OE Evaporator probe calibration
OdS Outputs delay at start up
AC Anti-short cycle delay
CCt Continuos cycle duration
COn Compressor ON time with faulty probe
COF Compressor OFF time with faulty probe
CF
Temperature measurement unit
rES Resolution
Lod Probe displayed
tdF Defrost type
dtE Defrost termination temperature
IdF Interval between defrost cycles
MdF (Maximum) length for defrost
dSd Start defrost delay
dFd Displaying during defrost
dAd MAX display delay after defrost
Fdt Draining time
dPo
First defrost after startup
dAF Defrost delay after fast freezing
Fnc Fan operating mode
Fnd Fan delay after defrost
Fct Differential of temperature for forced
activation of fans
FSt Fan stop temperature
ALc Temperat. alarms configuration
ALU MAXIMUM temperature alarm
ALL Minimum temperature alarm
ALd Temperature alarm delay
dAO Delay of temperature alarm at start up
i1P Digital input polarity
i1F Digital input configuration
did Digital input alarm delay
Nps Number of activation of pressure switch
odc Compressor and fan status when open
door:
PbC Kind of probe
dP1 Room probe display
dP2 Evaporator probe display
rEL Software release
Ptb Map code
Hidden parameters
XR60C – XR60D
1
2
3
4
5
6
8(3)A/250Vac
8(3)A/250Vac
20(8)A/250Vac
15 16 17 18 19 20 21
n.c.
Comp
Name
Range
LS÷US
0,125.5°C/ 1 255°F
-50°CSET/-58°FSET
SET110°C/ SET 230°F
-1212°C /-120120°F
n=not present; Y=pres.
-1212°C /-120120°F
0÷255 min
0 50 min
0.0÷24.0h
0 255 min
0 255 min
°C °F
in=integer; dE= dec.point
EL=el. heater; in= hot gas
-50 50 °C
1 120 ore
0 255 min
0÷99min
rt, it, SEt, DEF
0 ÷ 255 min
0÷120 min
n=after IdF; y=immed.
0 ÷ 23h e 50'
C-n, o-n, C-y, o-Y
0÷255min
0÷50°C
-50÷50°C/-58÷122°F
rE= related to set;
Ab = absolute
Set110.0°C; Set÷230°F
-50.0°CSet/ -58°FSet
0 255 min
0 23h e 50'
oP=opening;CL=closing
EAL=extern. alarm; bAL=lock regulation;
PAL=press. switch; dor=door switch;
dEF=defrost; LHt=disabled; Htr = heating
- cooling
0÷255min
no = normal; Fan = Fan OFF; CPr =
Compr. OFF; F_C = Compr & fan OFF
Ptc; ntc
Power
Supply
11 12
°C/°F
-5/0
2/4
-50/-58
110/230
0
y
0
0
1
0.0
15
30
°C/°F
dE/-
P1;P2
P1
EL
8/46
6
30
0
it
30
0
n
0.0
o-n
10
10
2/35
Ab
110/230
-50/-58
15
1.30
CL
dor
15
15
0 ÷15
F-C
ntc/Ptc
--
--
--
--
--
2.7
--
-
4/4
Need help?
Do you have a question about the Dixell XR60C and is the answer not in the manual?