Weight of the displays........................1-3 1.4. Dimensions of the DC-24 and DC-25....................1-3 1.4.1. Dimensions of the DC-24S and DC-25S.................. 1-3 1.4.2. Dimensions of the DC-24D and DC-25D.................. 1-3 1.4.3. Dimensions of the sensor case....................1-3 1.5.
Page 4
4.1.1. Displays DC-24/X. Read values from the display ..............4-2 4.1.2. Displays DC-25/X. Send values to the display ................. 4-2 4.2. PROTOCOL MODBUS RTU - ASCII for RS-485 ................4-4 4.3. PROTOCOL MODBUS RTU - Word for RS-485 ................4-6 4.4.
CHAPTER 1 INTRODUCTION AND GENERAL CHARACTERISTICS 1. INTRODUCTION AND GENERAL CHARACTERISTICS Numerical displays DC-24 and DC.21 are temperature and humidity displays. DC-24 displays admit form 1 to 5 sensors, calculating the °C mean value of all them. It automatically detects the number of sensors and displays its state once the display is initialized.
CHAPTER 1 1.1. Characteristics of the DC-24 and DC-25 displays Supply Voltage........... 88 to 264 VAC 47 to 63Hz. Consumption DC-24S and DC-25S ..12VA. Consumption DC-24S and DC-25S ..24VA. Display ............7 segments, 100mm high + decimal point.
CHAPTER 1 INTRODUCTION AND GENERAL CHARACTERISTICS 1.3. Weight of the displays. The weight of the DC-24S and DC-25S is 5kg. The weight of the DC-24D and DC-25D is 7kg. 1.4. Dimensions of the DC-24 and DC-25. 1.4.1. Dimensions of the DC-24S and DC-25S.
1.5. Display mounting 1.5.1. Mounting of the DC-24S and DC-25S. The DC-24S and DC-25S displays can be fixed to the wall in two ways: 1– Hanged. Place 2 of the supplied plug at 410mm from one to the other. Insert the screws leaving their head outside for 4mm.
CHAPTER 1 INTRODUCTION AND GENERAL CHARACTERISTICS Screwed: PARED 1.5.2. Mounting of the DC-24D and DC-25D. The DC-24D and DC-25D displays must be hanged using the rings the display has. Cables or chains can be used The power cables and the sensor can be fixed to the mounting elements without tightening them.
CHAPTER 2 INSTALLATION 2. INSTALLATION The installation of the DC-24 and DC-25 is not particularly delicate but some important considerations must be taken into account. The display must not be anchored to places subject to vibrations, nor should it be installed in places which generally surpass the limits specified in the display characteristics, both in terms of temperature and humidity.
INSTALLATION CHAPTER 2 2.3. Serial line connection. The displays of the series DC-24X and DC-25X admit connection through the RS-485 line. The connection must be done using a DB9 connector placed in the interior of the display The connection schematic is the one that follows Plug RS-485 2.4.
Page 13
CHAPTER 2 INSTALLATION In the sensor placing must be avoided: 1. The air streams due to doors 2. Placing it in climate control systems outputs 3. Proximity to fridges 4. Walls with direct sunlight In case the sensor cable must be extended, the colours of the cables must be respected. The colour identification is = White MAR = Brown...
CHAPTER 3 OPERATION 3. OPERATION. 3.1. Initial reset. Before connecting the display to the network, we must ensure that all of the connections have been carried out correctly and that the display is firmly in place. Each time we connect the display to the power supply network, an initial reset occurs which tests all of the segments comprising the display.
OPERATION CHAPTER 3 3.2.1. Modify parameters RS-485, Ethernet or Wifi. To modify the parameters the user must access the three programming keys placed on the top inside the display. See paragraph 3.1 to see how to access inside the display. The programmation keys are placed in the top of the displays.
CHAPTER 3 OPERATION 3.3. RS-485 parameters. 3.3.1. Parameter 1 for RS-485: Address of the display. It allows to configurate the address of the display in the RS-485 network. Value between 0 and 99. 3.3.2. Parameter 2 for RS-485: Serial line configuration. The parameters of the serial line are codified in the following table: Code Baud Rate...
OPERATION CHAPTER 3 3.3.3. Parameter 3 for RS-485: Sensor control and communication protocol This parameter performs two functions Left digit: Sensor control 0-> Disable sensor information 1 -> Enable sensor information Right digit: Communication protocol, The user can select between the following protocols: 0: ASCII: Really simple protocol that uses ASCII characters 1: ModBus RTU-ASCII: This uses the ModBus protocol, but the temperature and humidity data are coded in ASCII in the same block.
CHAPTER 3 OPERATION 3.4. Parameters Ethernet and Wifi. 3.4.1. Parameter 1 for Ethernet and Wifi: MAC address of the display. To know the MAC address, access parameter 1 and, using the “*” key, access the 3 last values of the MAC address. The first 3 numbers are always 00 -20 - 4A, so the first value displayed in the parameter is the 4 value of the MAC.
CHAPTER 4 COMMUNICATION PROTOCOLS 4. COMMUNCATION PROTOCOLS In this paragraph, the different protocols will be explained, as well as the programmation of the displays through them. The formats of values of the numbers and characters are written in this manual are: ...
COMMUNICATION PROTOCOLS CHAPTER 4 4.1.1. Displays DC-24/X. Read values from the display To read the current values of the temperature and humidity, the following message must be sent: Header Address Code End of block Characters High Carry return Decimal 80d 84d Hexadecimal 50h 54h The address of the display is formed by 2 digits between 0 and 99...
Page 23
CHAPTER 4 COMMUNICATION PROTOCOLS The address of the display is formed by 2 digits between 0 and 99 Example: Data sent to the address 04. Temperature 18.6°C and relative humidity 47%. Header Address Code Temp Space End of block Characters 18,6 Carry return Decimal...
COMMUNICATION PROTOCOLS CHAPTER 4 4.2. PROTOCOL MODBUS RTU - ASCII for RS-485 This protocol allows the user to communicate with devices that dispose of ModBus RTU protocol It uses the function 10h and the data block is in ASCII mode. The values can be read or sent.
Page 25
CHAPTER 4 COMMUNICATION PROTOCOLS To write values in the display, the following message must be sent: Addr. Func. Register Register Words Words Num. High High bytes High CRC Data 25,3 56h 54h 32h 35h 2Ch 33h 34h 37h The first byte is the address of the display inside the network. The three following bytes must be 10h, 01h and 01h.
COMMUNICATION PROTOCOLS CHAPTER 4 4.3. PROTOCOL MODBUS RTU - Word for RS-485 This protocol allows the user to communicate with devices using the protocol Modbus RTU This protocol uses the function 06h to write and the function 03h to read data from the display.
Page 27
CHAPTER 4 COMMUNICATION PROTOCOLS Response block example. Temperature: 23,8ºC Addr. Func. Num. bytes Data Low CRC High CRC 00h EEh To read the humidity value, the data request must be sent to register 0003h (40004). In the following example, the data block structure is detailed for a humidity request. Start Start Num.
COMMUNICATION PROTOCOLS CHAPTER 4 4.4. TCP/IP, UDP/IP PROTOCOL The display only accepts frames ending with a block ending it can see. (End of clock = Carry return = 0Dh) Local Port = 10001. 4.4.1. UDP protocol To use the UDP protocol, the communication port must be programmed with the default configuration To use UDP/IP, the Local Port must be 10001 UDP Datagram Mode...
CHAPTER 4 COMMUNICATION PROTOCOLS 4.4.3. Send values to the display. Displays without sensor. To send the temperature and humidity values to a display without sensor, the following block must be sent Code Temperature Space Humidity End of Block Characters TT.T Carry return Decimal 86d 84d...
4-10 COMMUNICATION PROTOCOLS CHAPTER 4 4.5. ModBus/TCP PROTOCOL The frame must accomplish the ModBus/TC specifications for being accepted by the display. 4.5.1. Modbus/TCP protocol End of block is not necessary. Local Port = 502. 4.5.2. Read data from the display To read the current temperature and humidity, the functions 03h or 10h must be used.
CHAPTER 4 COMMUNICATION PROTOCOLS 4-11 Function 10h Temperature and humidity can be read using the function 10h. In the frame, the following codes must be codified. Unit = 01h Function = 10h Start address = 00h 00h Start Num. Num. Identifier Protocol Unit...
Page 32
4-12 COMMUNICATION PROTOCOLS CHAPTER 4 Function 10h mode ASCII Sending temperature and humidity using the function 10h. In the frame, the following codes must be codified. Unit = 01h Function = 10h Start address = 00h 00h Identifier Protocol Num. bytes Unit Function Start address...
CHAPTER 4 COMMUNICATION PROTOCOLS 4-13 4.1. IP Address. Ethernet option Before being able to communicate with the display an IP address must be assigned. To assign an IP address the DeviceInstaller program from Lantronix must be used, which can be downloaded free from their website: www.lantronix.com Select: Support →...
4-14 COMMUNICATION PROTOCOLS CHAPTER 4 Enter your computer User Name and Password. To access the setup the Local Port, select Channel1->Connection. You will see a screen similar to the one above. In Local Port insert the new value and click OK on the bottom of the page. 4.2.1.
CHAPTER 4 COMMUNICATION PROTOCOLS 4-15 4.3. IP address. Wifi. The easiest way to set up the IP address is by using the Hyperterminal program and the serial line of computer. The cable’s wiring diagram is the classic crossover. DB9 o SAP12 Hembra Hembra Ordenador...
Page 36
4-16 COMMUNICATION PROTOCOLS CHAPTER 4 The attached Hyperterminal set up have been verified and work correctly, but any other set up may work also correctly. DC-24 and DC-25 operation manual...
CHAPTER 4 COMMUNICATION PROTOCOLS 4-17 To set up the Wifi module using the Hyperterminal or any other program, you must follow a time sequence. A time error on steps 5 and 6 forces to return to step 3. 4.3.1. Accessing Wifi module configuration In order to access to Wifi module configuration the next steps must be followed: 1–...
Page 38
4-18 COMMUNICATION PROTOCOLS CHAPTER 4 6– At this time you have 3 seconds to push the Intro key on your keyboard. 7– The following screen is shown. DC-24 and DC-25 operation manual...
Page 39
CHAPTER 4 COMMUNICATION PROTOCOLS 4-19 8– You must set up: 0 Server + Intro 4 WLAN + Intro Example of Server Set up Ask your network administrator the IP and Gateway address. Example of WLAN Set up Ask your network administrator the correct values To exit select 8 (Exit without save) or 9 (Save and exit).
4-20 COMMUNICATION PROTOCOLS CHAPTER 4 4.4. Set up IP Address using the DeviceInstaller. Before being able to communicate with the display an IP address must be assigned. To assign an IP address the DeviceInstaller program from Lantronix must be used, which can be downloaded free from their website: www.lantronix.com Select: Support →...
Page 41
Severo Ochoa, 80 Polígono Industrial Font del Radium 08403Granollers As the builder of the equipment of the LARTET brand: Model: DC-24 in all versions. Model: DC-25 in all versions We declare under our sole responsibility that the aforementioned product complies with the following European directives: Directive: LVD 2006/95/CEE Low Voltage Directive.