Single Phase Charging Charts - Nordyne S5BMX-018E Installation Instructions Manual

Split system air conditioner - for export only 1.5, 2, 2.5, & 3 ton, single phase, r-22 models
Table of Contents

Advertisement

application noteS For USing r22 reFrigerant
• this equipment's cooling system contains refrigerant under high pressure. always use safe and
environmentally sound methods when handling refrigerant handling or servicing the unit. review the
factory literature and safety warnings prior to servicing.
• When repairing system leaks, always use a nitrogen (inert) gas to protect the refrigerant system and pressure
check the repair before re-charging. Always replace the filter-dryers when performing any repair to the refrigeration
system with one capable of acid removal. After completing the repairs, evacuate the system to 350 - 500 microns
and weigh in the refrigerant to the amount specified on the unit rating label.
• These refrigerant charging charts are valid for a wide variety of indoor return air conditions (temperature and airflow)
and are most influenced by the outdoor ambient temperature, outdoor fan operation, and unit operating voltage.
Before using these charging charts, make sure the unit is in a steady operating mode. As shown in Figures 6-14
(pages 14-18) the ideal sub-cooling can vary over the range of operation. Reference these charts to determine
the ideal amount of sub-cooling for a given liquid pressure. Units charged to other values will not perform at the
rated unit capacity and/or efficiency (EER).
• To inspect a systems operation using quality instruments, match the measured liquid temperature to the units
chart. The measured liquid pressure reading should be within 3% of the charts value for most installations.
• For systems that are operating with more than a 5% deviation, inspect the unit for the proper voltage and phase
balance and the refrigeration system for leaks.
• Units that are operating at less then 95% of the nominal voltage or with a 2% phase imbalance may see a more
significant deviation than the amount stated above.
• do not use the charts in systems that have a fan cycling under low-ambient control. Refer to the low-ambient
kit instructions for more information. (If applicable)
2758 (400)
2586 (375)
2413 (350)
2241 (325)
2068 (300)
1896 (275)
1724 (250)
1551 (225)
1379 (200)
1207 (175)
1034 (150)
862 (125)
689 (100)
14
application notes on the Use of charging charts

Single pHaSe cHarging cHartS

Remove refrigerant when above curve
10
13
16
18
21
24
27
(50)
(55)
(60)
(65)
(70)
(75)
(80)
Figure 6. charging chart for 1.5 ton Units (-018e Series)
Add refrigerant when below curve
29
32
35
38
41
43
46
(85)
(90)
(95)
(100)
(105)
(110)
(115)
°C
Liquid Temperature
(°F)
49
52
54
57
60
63
(120)
(125)
(130)
(135)
(140)
(145)
(150)
66