SigTEL (1-16 Line) EVCS - Quick Start Installation Guide
THIS GUIDE IS FOR EXPERIENCED INSTALLERS ONLY and summarises key information provided in the full manual (Document No. DAU0000081). Page numbers, e.g.
Networked systems are not included in this guide.
SigTEL EV S Wiring Overview
EVC302F
Fig 1
2
8 lines of 2-core (1.5mm
and
)
earth/CPC cable, enhanced
fire-rated, up to 1km in length.
Fixed wiring, 2-core and earth/cpc
2
2
cable (0.75mm
to 2.5mm
) fed from
switched spur, fused at 3 amps.
8 x Lines from Type A or Type B Outstations
Fig 2
All screens connect
to Earth terminal
I/P A I/P B I/P C
+ - + - + -
+ - + -
+ - + -
+ - + -
+ - + -
L1
L2
L3
L4
L5
L6
L7
L8
ECU-8 or ECU-8S
A
B
Exchange PCB
C D
SigTEL
Emergency Voice
Communication System
EVC302S
THS1-E/MK4
Master/Slave interconnection via
supplied looms and short length of
steel conduit (25mm OD, max. length
60mm). Mount slave directly adjacent
to the master.
additional
8 x
outstations
outstation lines
ECU-8
ECU-8S
(optional)
3A fused spur
F U S E
Wiring and Cable Entry
See Fig 1 above for cable types. Install all wiring in accordance with the current edition of the IEE Wiring Regs (BS 7671), or relevant national
standards. Use enhanced fire-rated cables between outstations and control equipment.
Test Outstation Lines
Pg19
Test all lines for faults before terminating outstation lines to the ECU-8/ECU-8S. In addition, test outstation lines using a FITT telephone line
tester (see component list above).
CAUTION: DO NOT use an Insulation Resistance Tester (Megger) with any devices connected as they will be destroyed.
N/O C N/C 0V +24 OP3 OP2 OP1
Fit Outstations
Pg18
See Fig 1 above for cable type. Maximum recommended cable distance is 1 km, beyond which audio quality may degrade. For wiring and
connection details refer to Type A outstation instructions (Doc. No. DAU0000001) and Type B outstation instructions (Doc. No. DAU0302000).
Connect Outstation Lines to the Control Equipment
Do not connect outstation lines to the ECU-8, or optional ECU-8S, until they have been tested, fault-free and suitable cable glands fitted.
Connect outstation lines directly to the Exchange PCB (see Fig 2 left). Connect screens to the earth terminal in the back of the enclosure.
Approved Document No. DAU0302001 Rev 1
Part No.
ECU-8
ECU-8S
EVC302F
EVC302S
THS1-E/MK4
THS1-ET/MK4
BF359/1
BF359/2
FITT
BC286/2
AFP385
T-BEZ
Install the EV S
Location
Pg11
Site all equipment indoors in well-lit areas, free from obstruction. If background noise exceeds 40 dB, use
an acoustic hood. Site control unit(s) in the control room or lobby, 1.4 metre above final floor level (FFL).
Fit Type A (fire telephone) outstations in fire fighting lobbies and fire access points, 1.3 to 1.4 metres
above FFL. Fit type B (disabled refuge) outstations in disabled refuges, 0.9 to 1.0 metre above FFL.
Mounting
Pg12
Remove base PCBs before first fix installation to protect them and expose the base mounting holes.
Wall mount the control units, either surface or semi-flush. Fix the base securely onto a wall using No. 8
round-head, or countersunk screws. If an optional ECU-8S is fitted make the interconnections to the
ECU-8 using supplied looms and short length of steel conduit (25 mm OD, max. length 60 mm).
After mounting, remove any dust/swarf and re-install base PCBs. Ensure all connecting looms are refitted
correctly; ECU-8 internal connections are B to B, C to C. ECU-8 to ECU-8S (optional) is A to A, D to B.
Pg7
Pg19
refer to the main manual.
Pg11
SigTEL EVCS Components
Description
8-line Master EVC Control Unit c/w line cards, handset and LCD
8-line Slave EVC Expansion Unit (expands ECU-8 to 16 lines)
Disabled Refuge (Type B) Outstation, handsfree, duplex, flush mounted
Disabled Refuge (Type B) Outstation, handsfree, duplex, surface mounted
Fire Telephone (Type A) Outstation c/w red steel case, handset & key
Fire Telephone (Type A) Outstation c/w red steel case, handset & T-Bar
Weatherproof enclosure for EVC302F
Anti-tamper enclosure for ECU-8 or ECU-8S
EVC Telephone Line Tester
24 V, 7 Ah battery used with ECU-8
Grey flush bezel for ECU-8 or ECU-8S
Red flush bezel for THS1-E/MK4 and THS1-ET/MK4
1 of 2