Tdc-bh-u series. intelligent duct humidistat

Advertisement

Duct humidistat TDC-BH-U-W24
Configuration parameters
The TDC-BH-U can be adapted to wide variety of applications. The adaptation is done with parameters. The
parameters can be changed on the unit without the need of additional equipment.
Identifying the firmware version
The parameters and functionality of controller depend on its firmware revision. It is therefore important to use
a matching product version and parameter set. The firmware version is marked on the package box of your
product. In order to identify the firmware version of an installed controller, press UP and DOWN keys
simultaneously for three seconds: The display will indicate the firmware version in the upper large digits and
the revision in the lower small digits. Press the LEFT key to return to normal operation.
Setting of user parameters
The TDC-BH-U can be adapted to fit perfectly into your application. The control operation is defined by
parameters. The parameters are set during operation by using the control buttons.
The parameters may only be accessed by entering a code. There are two levels of parameters: User
operation parameters for access control settings, and Expert parameters for control functions and unit setup.
The codes for user levels and expert levels are different. Only control experts should be given the control
parameter code.
The parameters can be changed as follows:
1.
Press UP and DOWN button simultaneously for three seconds. The display shows the software
version in the large digits and the product code in the small digits.
2.
Pressing the OPTION button will indicate CODE on the small digits and 000 on the large digits.
3.
The code for accessing the user parameters is 009
4.
Select this using UP or DOWN buttons.
5.
Press OPTION button after selecting the correct code.
6.
Once logged in, the parameter is displayed immediately.
7.
Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION
button. Three triangles will show up on the lower right and indicate that the parameter may be
modified now. Use UP or DOWN buttons to adjust the value.
8.
After you are done, press OPTION or POWER in order to return to the parameter selection level.
Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button
is pressed for more than 5 minutes.
User parameters (password 09)
Parameter
Description
UP 00
Enable change of operation modes
UP 01
Enable change of set points
UP 02
Enable access to Time programs
UP 03
State after power failure:
0 = Switched OFF, 1 = Switched ON, 2 = state before
power failure
UP 04
Enable Economy functionality
UP 05
Celsius or Fahrenheit, Select ON for Fahrenheit, OFF for
Celsius
UP 06
Select contents of small digits in standard mode:
00 = OFF
01 = Set point
02 = Humidity Sensor
03 = External Temperature Sensor
04 = Clock
UP 07
New: Resolution 0.5% or 1% RH
OFF
= Display resolution is 0.5% RH
ON
= Display resolution is 1% RH
UP 08
Clock display type:
Deluxe only
OFF
= Show 24hour clock
ON
= Show 12hour clock (AM, PM)
UP 09
Reset timer for override mode: Only available for deluxe
Deluxe only
version
0
= Reset of override mode is not active.
1...255 = delay in minutes to return to scheduled operation
if the device is activated while scheduled to be
in OFF or ECO mode.
Doc: 70-07-0114B-24, V1.4, 20160912
Control parameters (access code: 241)
Warning! Only experts should change these settings! See user parameters for login procedure.
Parameter
CP 00
Minimum set point limit in humidification mode
CP 01
Maximum set point limit in humidification mode
CP 02
Minimum set point limit in de-humidification mode
CP 03
Maximum set point limit in de-humidification mode
Controls configuration
CP 04
Economy humidity shift
CP 05
Dead zone between humidifying & de-humidifying set point
X
DZ
Delay on humidify – de-humidify change over
CP 06
CP 07
Switching Hysteresis
CP 08
Delay OFF (Minimum running time) [MM:SS]
CP 09
Delay ON (Minimum stopping time) [MM:SS]
CP 10
Configuration of control mode
0 =W20 = Both Humidification and de-humidification
1 = W24 = Humidification only
2 = W25 = De-humidification only
Output configuration
Enable fan (only if CP 10 ≠0)
CP 11
CP 12
Start delay for fan [MM:SS]
(Time the fan runs before control output starts)
CP 13
Stop delay for fan [MM:SS]
(Time the fan keeps running after control output stops)
Temperature setback configuration
CP 14
Enable temperature setback
OFF = Temperature setback is disabled
ON = Temperature setback is enabled
CP 15
Set point limit at full setback
Range
Default
CP 16
Lower temperature limit:
ON, OFF
ON (Enabled)
Outside temperature with maximum setback
The set point will be equal to the minimum set point limit
ON, OFF
ON (Enabled)
CP 17
Upper temperature limit:
ON, OFF
ON (Enabled)
Outside temperature at begin of setback.
0, 1, 2
2
Input signal configuration
CP 18
Number of seconds taken into account to calculate the
averaging input signal.
ON, OFF
OFF
Low value = fast response
(Disabled)
High value = slow response
ON, OFF
ON (°F)
0...5
04 Deluxe:
show clock
01 Standard:
show set point
ON, OFF
OFF
(0.5% RH)
ON, OFF
ON (12h)
0...255
60 (Min)
Duct humidistat TDC-BH-U-W24
Description
Range
Default
0...100%
10%
0...100%
90%
0...100%
10%
0...100%
90%
0...100%
10%
0...100%
10%
0...255 min
5 min
0...100%
3%
00:00 to 98:30
00:10s
00:00 to 98:30
00:10s
0 - 2
TDC-BH-W20: 0
TDC-BH-W24: 1
TDC-BH-W25: 2
ON, OFF
TDC-BH-W20:
TDC-BH-W24: ON
TDC-BH-W25:ON
00:00 – 98:30
00:10
00:00 – 98:30
01:30
ON, OFF
ON
0...100%
20%
-40...60°C
-30°C (-22°F)
-40...160°F
-40...60°C
0°C (32°F)
40...160°F
0...100
10