LIEBERT® AC8
Product Specification/Installation Guide
Liebert AC8
TM
The Liebert AC8 coordinates
control of systems with redundant
equipment, such as multiple
thermal-management units or
pumps. The AC8 can control
stand-by functions and unit
rotation, perform testing on
stand-by devices, stage operation
based on sensor-reading levels,
and monitor alarm status of
connected devices. The Liebert
AC8 interfaces with any device
that closes an electrical contact.
The AC8 tracks data in alarm,
event, and trend logs. System
configuration and data monitoring
is accessible using a local, LCD
interface and a remote dial-up
interface. The AC8 also interfaces
with Liebert's SiteScan® Web
monitoring product.
TM
FEATURES
• Custom configuration for
specific applications
• Paging capability—up to 4
contact numbers
• Preconfigured, on-board
modem
• Alarm, Event and Trend logs
with time-and-date stamp
• Battery back-up to ensure
alarm notification
• Back-up and download
configuration files
• User interface via RS232 or
modem connection
• On-board audible alarm
• Configuration data and
operating program
permanently stored in
nonvolatile Electrically
Erasable Programmable Read
Only Memory (EEPROM) for
protection against power loss
• Real-time clock
• Status LEDs for verification
and diagnostics
AC8 Enclosure
The AC8 enclosure includes a key
lock for added security, is made of
metal to protect from
environmental exposure, and
includes top and bottom access
slots for cables and wiring.
590-1661-501A/SL-31101_REV2_7-17
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the Liebert AC8 and is the answer not in the manual?

Questions and answers

Summary of Contents for Vertiv Liebert AC8

  • Page 1 LIEBERT® AC8 Product Specification/Installation Guide Liebert AC8 FEATURES The Liebert AC8 coordinates • Configuration data and control of systems with redundant operating program • Custom configuration for equipment, such as multiple permanently stored in specific applications thermal-management units or nonvolatile Electrically •...
  • Page 2 LIEBERT® AC8 Product Specification/Installation Guide DIMENSIONS - Controller Input and Output FRONT, TOP/BOTTOM The controller supports the following connections: ENCLOSURE • 8 devices with 1 digital input FRONT VIEW and 1 digital output per device • 4 zones with staging for each zone •...
  • Page 3 LIEBERT® AC8 Product Specification/Installation Guide WIRING SPECIFICATIONS CONNECTION MAXIMUM LENGTH, ft (m) RATING SUPPORTED TYPE Digital Input/ Dry-contact, 24 VDC, 750 (225) EPOP 10 mA 18 – 22 AWG 4 -20 mA signal input, Analog Input stranded, unshielded 750 (225) selectable power 2-wire transducer (18 AWG recommended)
  • Page 4 To contact Vertiv Technical Support: visit www.VertivCo.com © 2017 Vertiv Co. All rights reserved. Vertiv, the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions.