Operation terminal OPU-D42-W50
Configuration parameters for firmware version 2.0 –W50
This controller can be adapted to wide variety of fan coil applications. The adaptation is done with
parameters. The parameters can be changed on the unit without the need of additional equipment.
Identifying the firmware version
The parameters and functionality of controller depend on its firmware revision. It is therefore important to use
a matching product version and parameter set. The firmware version is shown on the large LCD digits when
pressing UP and DOWN buttons for more than 3 seconds simultaneously.
Changing parameters
The parameters may only be accessed by entering a code. There are two levels of parameters: User
operation parameters for access control settings and Expert parameters for control functions and unit setup.
The codes for user levels and expert levels are different. Only control experts should be given the control
parameter code.
The parameters can be changed as follows:
1.
Press UP and DOWN button simultaneously for three seconds. The display shows the
software version in the large digits and the software revision in the small digits.
2.
Pressing the OPTION button will indicate CODE on the small digits and 000 on the large
digits.
3.
The code for accessing the user parameters is 009
4.
Select this using UP or DOWN buttons.
5.
Press OPTION button after selecting the correct code.
6.
Once logged in, the parameter is displayed immediately.
7.
Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the
OPTION button. The MIN and MAX symbols show up and indicate that the parameter may
be modified now. Use UP or DOWN buttons to adjust the value.
8.
After you are done, press OPTION or POWER in order to return to the parameter selection
level.
9.
Press the POWER button again so as to leave the menu. The unit will return to normal
operation if no button is pressed for more than 5 minutes.
User Parameters (Access Code: 009)
Parameter Description
UP 00
Enable change of operation modes,
UP 01
Enable change of set points
UP 02
Enable manual control fan speeds
UP 03
Enable manual change of Heating/Cooling Mode.
Applies only for 2-pipe or 4-pipe systems.
UP 04
Enable Access to time programs
UP 05
State after power failure: 0 = OFF, 1 = ON, 2 = Last State
UP 06
Enable Economy (unoccupied) Mode.
Shift the setpoint to a lower temperature in winter or higher
temperature in summer in order to save energy. May be activated
through the POWER button, or with the external input (typically
for key card switches in hotel rooms or motion detectors for
meeting rooms.)
UP 07
Celsius or Fahrenheit, OFF for Celsius, ON for Fahrenheit
UP 08
Calibrateinternal temperature sensor
–10° to +10° in 0.1° steps. (Sensor is factory calibrated, use this
feature for field adjustment only as required.)
UP 09
Enable Frost Protection.
Activates the output independent of operation mode when the
control temperature drops below 5°C or 41°F. The controller
returns to normal operation when the temperature increases
above 10°C or 50°F.
UP 10
Select contents of Large LCD display in standard mode:
00 = OFF
03 = Output Fan Speed
01 = Setpoint
04 = Clock
02 = Temperature Sensor
05 = Alternative Sensor
06 = Output in Percent
UP 11
Select contents of small LCD display in standard mode
00 = OFF
03 = Output Fan Speed
01 = Setpoint
04 = Clock
02 = Temperature Sensor
05 = Alternative Sensor
06 = Output in Percent
UP 12
Contents of vertical bar in standard mode
OFF
= Fan Speed
ON
= Control output
UP 13
Clock display type: Only available for deluxe version
OFF
= Show 24hour clock
ON
= Show 12hour clock (AM, PM)
UP 14
Reset timer for override mode: Only available for deluxe version
0
= Reset of override mode is not active.
1...255 = delay in minutes to switch off device if ON/Economy
mode is activated while the unit is scheduled to be in
OFF mode
Doc: 70-00-0326B-50, V2.0, 2013-01-07
Control Settings (Access Code: 241)
Warning! Only experts should change these settings!
Set point limits
Parameter
Description
FC 00
Minimum setpoint limit in Heating mode
FC 01
Maximum setpoint limit in Heating mode
FC 02
Minimum setpoint limit in Cooling mode
FC 03
Maximum setpoint limit in Cooling mode
Fan control sequence
FC 04
Economy (unoccupied) Mode temperature shift:
The comfort (occupied) setpoint is shifted by the value
set with parameter. If heating is active the comfort
setpoint will be decreased, if cooling is active, the
setpoint will be increased. (Enable with UP06.)
FC 05
Switching Span Heating,
if set to 0, only 1 fan speed will be used
FC 06
Switching Span Cooling
if set to 0, only 1 fan speed will be used
FC 07
Switching Hysteresis is the difference between
switching on and switching off. A small hysteresis will
increase the number of switching cycles and thus the
wear on fan and relays contacts.
FC 08
Mold Protection:
In mold protection, the fan keeps running independent
of temperature as long as the unit is switched on.
FC 09
Delay OFF (Minimum running time)
FC 10
Delay ON (Minimum stopping time)
FC 11
Control option:
0 = Cooling only
1 = Heating only
Range
Standard
2 = 2-pipe system
3 = 4-pipe system
ON, OFF
ON (Enabled)
FC 12
Dead Zone Span:
ON, OFF
ON (Enabled)
The Dead Zone Span lies between the heating and the
cooling setpoint. The output is off while the temperature
ON, OFF
ON (Enabled)
is within the dead zone span. A negative dead zone is
ON, OFF
ON (Enabled)
not possible.
FC 13
Heat/Cool Changeover Delay (if set to FC11 = 3):
ON, OFF
ON (Enabled)
A demand to switch between heating and cooling must
persist for the length of time set with this parameter
0, 1, 2
2
before the controller switches. Prevents activation of a
ON, OFF
OFF
sequence during a short-term change in temperature in
(no economy)
order to protect equipment (with control overshoot for
example)
PID control sequence
FC 14
P – band heating X
FC 15
P – band cooling X
ON, OFF
OFF (Celsius)
FC 16
K
, Integral gain heating, in 0.1 steps, 0 disables ID part
IH
-10...10
0
low value = slow reaction, high value = fast reaction
FC 17
K
, Integral gain cooling, in 0.1 steps
IC
Proportional control (P-band)
ON, OFF
ON (Enabled)
The proportional control function calculates the output based on the difference between setpoint and
measured value. The proportional band (P-band) defines the difference between setpoint and measured
value which will result in a 100% output. Setting the proportional band to 0 disables proportional control.
Integral gain KI
The integral gain defines how fast the output increases in case the setpoint is not met by the room
0...6
02
temperature. A low value indicates a slow reaction, a high value a fast one. If the value is chosen too high,
Temperature
the controller will start to swing. Depending on the room size and heating / cooling equipment used a value
between 0.1 and 1.5 should be sufficient. Below are suggested values:
Heating: KIH: 0.1-0.5, Cooling: KIC: 0.3-0.8
Configuration of Analog outputs
Parameter
Description
0...6
Standard:
FC 18
Configuration of analog output signal
01 Setpoint
0
= 0-10V
Deluxe:
1
= 2-10V
04 Clock
2
= Manual override (useful for commissioning)
When low fan speed: 25% output
ON, OFF
ON (control)
When medium fan speed 50% output
When high fan speed 100% output
FC 19
Function of analog outputs
0
= Disabled
ON, OFF
OFF (24h)
1
= Control: Heating only (AO1 only)
2
= Control: Cooling only (AO2 only)
3
= Control: Heating and cooling (AO1 and AO2)
0...255
60 (Min)
FC 20
Output of AO1 in cooling mode if FC19 = 1 or
Output of AO2 in heating mode if FC19 = 2
For heating only or cooling only option, the analog output may set to a fixed output while the binary
sequence is active. This is used for VAV systems.
Operation terminal OPU-D42-W50
Range
Standard
-40-60°C (160°F)
16°C (61°F)
-40-60°C (160°F)
24°C (75°F)
-40-60°C (160°F)
18°C (64°F)
-40-60°C (160°F)
30°C (86°F)
0...10.0K (20°F)
4.0°C (8°F)
0...10.0K (20°F)
0.0°C (0.0°F)
0...10.0K (20°F)
0.0°C (0.0°F)
0...10.0K (20°F)
0.5°C (1°F)
ON, OFF
ON
0...255 s
10s
0...255 s
10s
0-4
3
0...100°C (200°F)
2.0°C (4°F)
0...255 min
5 min
0...10.0K (20°F)
2.0°C (4.0°F)
PH
0...10.0K (20°F)
2.0° (4.0°F)
PC
0...25.5
0.0
0...25.5
0.0
Range
Standard
0-2
0 (0-10V)
0...3
3
0...100%
0%
© Vector Controls GmbH, Switzerland
Operation terminal OPU-D42-W50
Configuration of binary output
Parameter
Description
FC 21
Function of binary output
0
= Disabled
1
= Control: Heating only
2
= Control: Cooling only
3
= Control: Heating and cooling
4 =
Enable: On if device is on
5 =
Enable: On if device is on and in heating mode
6 =
Enable: On if device is on and in cooling mode
7 =
Frost protection alarm
FC 22
Level to activate binary output if in dual AO-DO mode:
Dual AO-DO mode = both analog and binary outputs
are assigned to same control sequence.
FC 23
Level do deactivate binary output if in dual AO-DO
mode
Dual AO-DO mode = both analog and binary outputs
are assigned to same control sequence.
The three fan outputs are assigned to the fan speed module. Only output 4 can be assigned by this
parameter (FC21). Select if the binary output should work as controls output in heating or cooling only
or both for heating and cooling mode.
Dual AO-DO mode: if both the analog and the binary output is assigned as control output to the same
sequence, the binary output will then switch on when the analog output reaches the value defined in
FC22 for example 95% and switch off when it drops below FC 23 for example 45%. Note: This output
does not follow min running and stopping delays. It only reacts to the conditions mentioned above. In
order to take advantage of this function we recommend using larger proportional bands.
Configuration of inputs
FC 24
External input:
0 = No external input
1 = External temperature sensor
2 = Occupation sensor – Comfort / Economy
3 = Occupation sensor – Comfort / Off
4 = Heat / Cool changeover
5 = Key card with alternative setpoint
6 = Key card with full reset
FC 25
Activation delay (Minutes) = the time the binary input
needs to be open before economy/off mode is activated.
FC 26
Auto-changeover limit heating FC24 = 4
or economy setpoint in heating mode if FC24 = 5
FC 27
Auto-changeover limit cooling FC24 = 4
or economy setpoint in cooling mode if FC24 = 5
FC 28
Comfort setpoint in heating mode if FC24 = 6
FC 29
Comfort setpoint in cooling mode if FC24 = 6
Configuring the function of the external input
FC24 = 1
External control
The external sensor is the control input.
input
FC24 = 2
Switching
Economy (unoccupied) and Comfort (occupied) modes are controlled
Economy and
through an external contact by connecting the input through a dry contact
Comfort modes
to signal common. This function may be used together with key card
switches for hotels or motion detectors for offices.
FC24 = 3
Switching Energy
Opening the input will force the unit into the OFF operation mode. The
Hold OFF and
operation mode cannot be overridden by using the terminal. Connecting
Comfort modes
the input to signal common returns control of the operation mode to the
terminal. This function may be used as window contact to prevent loss of
energy.
FC24 = 4
Heat – Cool
Switch heating and cooling mode based on supply media or outside
changeover
temperature or binary contact. See below for further details.
FC24 = 5
Key card with
As with FC24 = 2, the key card function switches economy (unoccupied)
alternative
and comfort (occupied) modes. Instead of using the setpoint shift, the
setpoint
setpoints in unoccupied mode are defined by parameter FC26 in heating
mode and FC27 in cooling mode.
Fan speed in unoccupied mode is limited to low speed.
Fan speed and setpoint will be remembered after re-inserting the key card.
FC24 = 6
Key card with full
Similar as FC24 = 5 with the difference that setpoints, fan speed and
reset
operation mode are reset each time the key card is inserted. This is helpful
for business hotels. Setpoints will be reset to FC28 or FC29.
Configuring auto changeover input if FC24 = 4:
The auto changeover function automatically changes heating and cooling mode based on supply
media temperature or outdoor temperature. The difference between the two is in the values of the
changeover limits FC26 and FC27. See table below for recommended settings.
Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all
signal ground levels of involved controllers must be the same in case more than one controller is
switched.
Recommended settings for FC26 and FC27:
Change over mode FC24=4
Relation FC26 to FC27
Supply media
FC26> FC27
Outside temperature
FC26< FC27
Dry contact: Heating if contact closed
FC26> FC27
Dry contact: Cooling if contact closed
FC26< FC27
Range
Standard
0...7
1
0...100%
65%
0...100%
15%
0...6
0
0...255 min
5
-40...60°C (160°F)
28°C (82°F)
-40...60°C (160°F)
18°C (64°F)
-40...60°C (160°F)
21°C (70°F)
-40...60°C (160°F)
24°C (75°F)
Example:FC26
Example:FC27
28°C (82F)
18°C (64F)
15°C (59F)
25°C (77F)
25°C (77F)
15°C (59F)
15°C (59F)
25°C (77F)
Subject to alteration