CC-Link Communication Converter
Quick Instruction
COM-JC
[For SRZ]
All Rights Reserved, Copyright © 2007, RKC INSTRUMENT INC.
In order to achieve maximum performance and ensure proper operation of your new
instrument, carefully read all the instructions in the manual. Please place this manual
in a convenient location for easy reference.
This manual describes the basic operation only.
For detailed handling procedures and functions, refer to separate COM-JC
[For SRZ] Instruction Manual (IMR01Y34-E ).
The manual can be downloaded from the official RKC website:
http://www.rkcinst.com/english/manual_load.htm.
1. HANDLING PROCEDURES
Communication setting
Refer to 2. COMMUNICATION SETTING
• Refer to COM-JC [For SRZ] Installation Manual
Mounting and Wiring
(IMR01Y22-E )
• For SRZ, refer to Z-TIO Instruction Manual (IMS01T01-E )
and Z-DIO Instruction Manual (IMS01T03-E ).
PLC setting
Refer to 4.2 Setting the Instruments Used
• Refer to 4.2 Setting the Instruments Used
Controller setting
• Refer to Z-TIO Host Communication Quick
Instruction Manual (IMS01T02-E ) and Z-DIO
Instruction Manual (IMS01T03-E ).
Device assignment
Refer to 4.3 Device Assignment Example
Program creation
Refer to 4.4 Sample Program
To avoid error at operation start-up, COM-JC must be powered on LAST
(after the Controller, PLC, etc.).
2. COMMUNICATION SETTING
CAUTION
Do not separate the mainframe from the terminal base with the power turned
on. If so, instrument failure may result.
2.1 Station Number Setting
Set the station number of CC-Link using a small blade screwdriver.
Station number
setting switch
High-order digit
setting
(Set value × 10)
Low-order digit
setting
(Set value × 1)
Setting range:
1 to 61 ( 4 stations occupied 1 time,
4 stations occupied 2 times,
4 stations occupied 4 times)
1 to 64 (1 station occupied 1 time)
Factory set value: 0
When set to any value out of the setting range, the COM-JC becomes the
FAIL state.
2.2 Communication Speed Setting
Set the communication speed of CC-Link using a small blade screwdriver.
Communication speed
setting switch
Setting range: 0 to 4
Factory set value: 0 (156 kbps)
Left side
When set to any value out of the setting range, the COM-JC becomes the
FAIL state.
Communication speed and maximum transmitter distance
Manual
[Use the CC-Link dedicated cable Ver. 1.10]
Communication speed
Communication speed
setting
IMR01Y26-E2
0
156 kbps
1
625 kbps
2
2.5 Mbps
3
5 Mbps
4
10 Mbps
2.3 Occupied Stations/Extended Cyclic and
Controller Communication Speed Setting
Set the number of occupied stations/extended cyclic and controller communication speed.
Left side
1
2
Controller communication speed
OFF
OFF
38400 bps
ON
OFF
9600 bps
OFF
ON
19200 bps
ON
ON
38400 bps
Factory set value: 19200 bps
3
4
5
Number of occupied stations/extended cyclic setting
OFF
OFF
OFF
4 stations occupied 1 time (8 channels assignment)
ON
OFF
OFF
4 stations occupied 1 time (16 channels assignment)
OFF
ON
OFF
4 stations occupied 2 times (16 channels assignment)
ON
ON
OFF
4 stations occupied 2 times (32 channels assignment)
OFF
OFF
ON
1 station occupied 1 time
ON
OFF
ON
1 station occupied 1 time
OFF
ON
ON
4 stations occupied 4 times (32 channels assignment)
ON
ON
ON
4 stations occupied 4 times (64 channels assignment)
Factory set value: 4 stations occupied 1 time (8 channels assignment)
6
7
8
OFF
OFF
OFF
3. CC-Link FLAG OPERATION
Remote input/output and remote register flag operations are as follows.
[Example] When the occupied station/extended cyclic of COM-JC is set to 4 stations
occupied 1 time.
Initialize request processing at power on
Initialize processing request from remote device station (COM-JC)
If the COM-JC is initialized at power on, the initialize data processing request flag [RX(n+7)8]
is turned on. Thus, turn on the initialize data processing completion flag [RY(n+7)8].
When COM-JC becomes a ready state, a remote ready [RX(n+7)B] is turned on.
ON
Initialize data processing
request flag [RX(n+7)8]
OFF
ON
Initialize data processing
completion flag [RY(n+7)8]
OFF
ON
Remote ready [RX(n+7)B]
OFF
Initialize processing request from master station (PLC)
This is a COM-JC initialize setting request. As there is no initialize data specifically, no
processing is required.
ON
Initialize data setting
request flag [RY(n+7)9]
OFF
ON
Initialize data setting
completion flag [RX(n+7)9]
OFF
ON
Remote ready [RX(n+7)B]
OFF
Error flag/error reset processing
If the Error reset request flag [RY(n+7)A] is turned on while the Error status flag [RX(n+7)A]
is turned on, the Error status flag history is cleared and the flag [RX(n+7)A] turns off.
ON
Maximum transmitter
Error status flag
distance
[RX(n+7)A]
1200 m
OFF
900 m
ON
Error reset
400 m
request flag
160 m
[RY(n+7)A]
OFF
100 m
ON
Remote ready
[RX(n+7)B]
OFF
Extension number for display selection processing
After the extension number for display [RYn0 to RYn5, RY(n+1)0 to RY(n+1)2] is set, turn
on the extended display flag [RYnC]. After the data in the remote register [RWrn to
RWrn+F] is displayed, check that extended display completion [RXnC] is turned on and
then turn off the extended display flag [RYnC]. If the extended display flag is turned off, the
extended display completion is turned off.
Dip switch
ON
ON
Extension number
ON
ON
for display
[RYn0 to RYn5,
OFF
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
RY(n+1)0 to RY(n+1)2]
ON
Extended display flag
[RYnC]
OFF
Extended display
ON
completion
[RXnC]
OFF
ON
Remote register
[RWrn to RWrn+F]
OFF
Extension number for setting selection processing
The content of the extended setting remote register is selected and the set value is changed.
After the extension number for setting [RYn6 to RYnB, RY(n+1)8 to RY(n+1)A] is set, turn
on the extended setting flag [RYnD]. After the content of the remote register [RWwm to
RWwm+F] is set, check that extended setting completion [RXnD] is turned on and then
turn off the extended setting flag [RYnD]. If the extended setting flag [RYnD] is turned off,
(1 channel assignment)
the extended setting completion [RXnD] is turned off.
(2 channels assignment)
ON
Extension number
for setting
[RYn6 to RYnB,
RY(n+1)8 to RY(n+1)A]
OFF
Extended setting flag
ON
(Setting update flag)
[RYnD]
Fixed
OFF
ON
Extended setting
completion
[RXnD]
OFF
ON
Remote register
[RWwm to RWwm+F]
OFF
Regardless of the number of occupied stations and the extended cyclic, the
above processing is also necessary if the "Set value (SV)" assigned to the
remote register (RWw) as a fixed value is changed.
AT start procedure
Instructs AT execution.
Remote register [RWwn]
(Extension number 4:
PID/AT transfer)
ON
Extended setting flag
(Setting update flag)
[RYnD]
OFF
ON
Extended setting
completion
[RXnD]
OFF
ON
AT setting status
OFF
ON
PID/AT transfer status
[RXn4]
OFF
For remote input/output and remote register, refer to COM-JC [For SRZ]
Communication Data List (IMR01Y30-E ) or COM-JC [For SRZ]
Instruction Manual (IMR01Y34-E ).
4. USAGE EXAMPLE
A usage example of CC-Link communication is described in the following.
4.1 System Configuration
In this usage example, described the following system configuration.
PLC (Mitsubishi Electric
MELSEC Q series)
CPU unit
Q02HCPU
Extension number 0
Extension number 1
CC-Link communication
converter COM-JC
Remote device station
(Slave station)
Station number: 1
4 station occupied 1 time
Extension number 0
Extension number 1
Communication speed:
156 kbps
Use instruments
(R/O data: Automatically updated)
• CC-Link communication converter: COM-JC ............................................ 1
• Controller (SRZ):
• Mitsubishi PLC MELSEC Q series
− CPU unit:
− CC-Link system master local unit: QJ 61BT11N
• CC-Link dedicated cable Ver. 1.10
• COM-JC and controller connection cable
4.2 Setting the Instruments Used
Set the PLC, COM-JC and controller as the following.
PLC setting
For operation of the CC-Link system master local unit QJ61BT11N and MELSEC
sequencer programming software GX Developer, refer to Instruction Manual of PLC.
[CC-Link system master local unit QJ61BT11N setting]
Setting item
Station number
CC-Link communication speed 156 kbps
[Master station network parameter setting by GX Developer]
Setting item
Number of boards in module
Start I/O number
Operational settings
Data usage
Data usage
Type
CC-Link mode setting
Total number of connected
modules
Number of retries
Number of automatic return
modules
Standby master station number Blank
Data = 1
Data = 0
Operation specification when
CPU is down
Scan mode specification
Delay time setting
Station information
(Number of COM-JC
connection: 1
Station number: 1)
[Automatic refresh parameter setting by GX Developer]
Remote input (RX) refresh device
Remote output (RY) refresh device
Remote register (RWr) refresh device
Remote register (RWw) refresh device
Special relay (SB) refresh device
Special register (SW) refresh device
CC-Link system Master local unit
QJ 61BT11N (Master station)
Station number: 0
Communication speed: 156 kbps
CC Link Ver. 1.10
Controller
(Z-TIO module)
1
2
Module address *
(Controller address)
* The value obtained by
adding "1" to the set
address corresponds
Controller
to the address used
communication
for the actual program.
(RS-485: Modbus)
(Set value: 0 and 1)
Z-TIO module (4 channels type) ....... 2
Q02HCPU
Setting value
0
Setting value
1
0000
Parameter name:
None
Data link disorder station setting: Clear
Case of CPU STOP setting:
Refresh
Master station
Remote net (Ver. 1 mode)
1
5
1
Stop
Asynchronous
10 (500 μs)
Station type:
Remote device
station
Expanded cyclic setting:
Single
Number of occupied stations:
Occupies 4 stations
Remote station points:
128 points
Reserved/invalid station select: No setting
Intelligent buffer select (word): No setting
Setting item
Setting value
X1000
Y1000
W0
W100
SB0
SW0

Advertisement

loading
Need help?

Need help?

Do you have a question about the COM-JC and is the answer not in the manual?

Questions and answers

Summary of Contents for RKC INSTRUMENT COM-JC

  • Page 1 “Set value (SV)” assigned to the (Set value × 10) If the COM-JC is initialized at power on, the initialize data processing request flag [RX(n+7)8] CC-Link mode setting Remote net (Ver. 1 mode) remote register (RWw) as a fixed value is changed.
  • Page 2 Write “2000,” “2500,” “3000,” “3500,” Remote register (RWr): W0 Remote register (RWw): W100 W009 RWr9 When the COM-JC is in the normal state and the error reset “4000,” “4500” and “5000” for extension Special relay (SB): Special register (SW): K4500 W10E action is being requested.