Technical Data - Phoenix Contact QUINT-DC-UPS/24DC/40 Manual

Uninterruptible power supply unit for universal use
Table of Contents

Advertisement

Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40

2. Technical Data

t . . . [ m i n ]
J
B a t . - S e l e c t [ A h ]
+
-
2 x 1 2 V
B a t t e r y
I n p u t
D C 2 4 V
Solid
Stranded
2
[mm
]
Input
0.5 - 16
0.5 - 10
Output
0.5 - 16
0.5 - 10
Signal
0.2 - 2.5
0.2 - 2.5
Description
Uninterruptible power supply unit
3.4 Ah battery module
7.2 Ah battery module
12 Ah battery module
Technical Data
Input Data
Nominal input voltage
Input voltage range
Current consumption
Switching threshold
Buffer time
Input fuse
Maximum power dissipation
Output Data
Can be connected in parallel (battery module)
Output Data in Normal Operation
Nominal output voltage
Output voltage
Output current
Current limit
Overload fuse
Output Data in Buffer Mode
Nominal output voltage
Output voltage
Output current
Current limit
Overload fuse
Level of efficiency
Remote shutdown
Charging
Charge characteristic curve
End-of-charge voltage
Charge current
Battery/presence check/time interval
Battery/quality test/time interval
Memory Medium
Nominal voltage
Nominal capacity
Charge current
1 1
R 1
1 2
1 3
R 2
2 1
2 2
+ 2 4 V
2 0 0 m A
2 3
3 1
O u t p u t
0 - 2 0 A D C
3 2
3 3
Torque
AWG
[Nm]
[lb in]
20 - 6
1.2 - 1.5 10.6 - 13.3
20 - 6
1.2 - 1.5 10.6 - 13.3
25 - 14
0.5 - 0.6
4.5 - 5.3
(No load/charging/maximum)
Can be configured
(Ready/buffer mode)
Maximum
Typical
PHOENIX CONTACT page 2 of 9
125 mm (4.921 in.)
66 mm
(2.598 in.)
QUINT-DC-UPS/24DC/40
DC UPS Module
10 mm (0.39 in.)
L [mm]
7 mm (0.28 in.)
Type
QUINT-DC-UPS/24DC/40
QUINT-BAT/24DC/3,4Ah
QUINT-BAT/24DC/7,2Ah
QUINT-BAT/24DC/12Ah
24 V DC
22.5 - 30 V DC
0.1 A/2.5 A/42.5 A
U
< 22 V; dynamic U
- 1 V/0.1 s
a
in
0.5; 1; 2; 3; 10; 15; 20; 30; continuous
Internal, 50 A
20 W/30 W
Yes, to increase the buffer time
24 V DC
U
in
40 A
None
Internal, 50 A
24 V DC
27.9 V DC
40 A (25 A for 3.4 Ah battery module)
45 A
Electronic
98%
Yes
I/U characteristic curve
Temperature compensated
< 2.5 A
60 seconds
180 hours
External
24 V DC
3.4 Ah, 7.2 Ah, 12 Ah
< 2.5 A
U u F
Pcs.
Order No.
Pkt.
1
28 66 24 2
28 66 34 9
28 66 35 2
28 66 36 5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUINT-DC-UPS/24DC/40 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents