Pos: 4.2 /BA_Module_Manuell/Torsteuerung TS 959/04_Sicherheitshinweise @ 6\mod_1344867202506_28.docx @ 757629 @ 1 @ 1 1 General safety information Specified normal use The door control is intended for a power-operated door with a drive unit. The safe operation is only guaranteed with normal specified use. The drive unit is to be protected from rain, moisture and aggressive ambient conditions.
Pos: 5.1 /BA_Module_Manuell/Torsteuerung TS 959/05_Technische Daten @ 6\mod_1344924152708_28.docx @ 757670 @ 1 @ 1 2 Technical data Series TS 959 Dimensions W x H x D 155 x 380 x 80 Assembly vertical Assembly Vibration free of vibration Operating frequency...
Pos: 6.1 /BA_Module_Manuell/Torsteuerung TS 959/06_Mechanische_Montage @ 6\mod_1344924433864_28.docx @ 757688 @ 1 @ 1 3 Mechanical installation Control installation! Only use indoors Mounting only on a level ground free of vibration Only vertical mounting position permissible Door must be visible from the assembly site...
Connection overview for connection cables DES and NES DES connection cable for limit switch connection cables for motor X13 Motor plug X12 Limit switch plug Pin Core Term. Pin Core Term. Phase W 5/wh +24 V safety circuit Phase V 6/bn Channel B (RS485) Phase U...
Carrying out the electrical installation ▶ Remove the covers. ▶ Open cable conduit ① or ②. ▶ Insert and connect control/drive connection cable in the open cable conduit ① (from below) or ② (from above). ▶ Tighten cable gland. Caution - Avoid damage to components! ...
Mains supply 3-phase current, 3-phase current, 1-phase 1-phase with neutral without neutral symmetrical asymmetrical conductor conductor Mains connection to control Completion of electrical installation Connect any other control devices and/or safety devices. Install and tighten cable entries and/or cable glands. For initial operation of the control, leave the covers open.
Pos: 8.1 /BA_Module_Manuell/Torsteuerung TS 959/08_Inbetriebnahme (Schnelleinstellung) @ 6\mod_1344924464383_28.docx @ 757718 @ 122 @ 1 5 Initial operation of the control ▶ Plug in or switch on mains supply line DES: Rapid adjustment of final limit positions 1. Check rotating direction 2.
3. Move to 5 cm in front of the CLOSED final limit position and set S5 pre-limit 4. Move to CLOSED final limit position and set S4 CLOSED limit switch Pos: 8.2 /BA_Module_Manuell/Torsteuerung TS 959/MAL_Seitenumbruch @ 6\mod_1344937085969_0.docx @ 758205 @ @ 1...
Pos: 10.1 /BA_Module_Manuell/Torsteuerung TS 959/10_Programmierung der Steuerung @ 6\mod_1344924529099_28.docx @ 757748 @ 1 @ 1 7 Programming the control 1. Only program after rapid adjustment of final limit positions! 2. Select and confirm the menu 3.a) Set and store functions 3.b) Set and save (DES) positions...
Pos: 11.1 /BA_Module_Manuell/Torsteuerung TS 959/11_Parametereinstellungen @ 6\mod_1344924544071_28.docx @ 757763 @ 1 @ 1 8 Table of menus Operating mode Operating mode Door operating mode OPEN Hold-to-run CLOSE Hold-to-run OPEN Self hold CLOSE Hold-to-run Extended hold-to-run control Turning direction Maintain turning direction...
Door function Door function Relay function on X20 Teach-in door positions via menu 1.7 (DES only) Impulse signal for 1 second Permanent signal Red lamp, permanent light during door movements OPEN final limit position 3 seconds permanent light CLOSE final limit position 3 seconds permanent light Red lamp, permanent light during door movements OPEN final limit position...
Maintenance cycle counter Maintenance cycle counter Maintenance cycle preselection 01-99 corresponds to 1,000 to 99,000 cycles Cycles are counted down Reaction on reaching zero "CS" display with set value of maintenance cycle Changeover to hold-to-run and "CS" display with set value of maintenance cycle Changeover to hold-to-run and "CS"...
1,000 Firmware version The firmware version of the control is displayed. Deleting all adjustments Deleting all adjustments Deleting all adjustments All (factory setting)! Except for cyclus counter reading Pos: 11.2 /BA_Module_Manuell/Torsteuerung TS 959/MAL_Seitenumbruch @ 6\mod_1344937085969_0.docx @ 758205 @ @ 1...
Pos: 12.1 /BA_Module_Manuell/Torsteuerung TS 959/12_Funktionsdetailbeschreibung @ 6\mod_1344924555665_28.docx @ 757788 @ 1221222222222 @ 1 9 Safety devices X2: Input, door safety switch The door safety switch is fitted to the door and connected to the door control via the spiral cable.
10 Description of functions X1: Mains supply line for control and external supply Mains supply line for control Connection via terminals X1/1.1 to X1/1.4 and PE Various mains connections: 3 N~, 3~, 1 N~ for symmetric and asymmetric motors Note! ▶...
X5: Input, control device Warning! “Hold-to-run” door operating mode: The door must be fully visible from the operating point. Note! ▶ Wire links X5.1 to X5.2 for using the control device without stop button ▶ Note “X5 control device” description Extended hold-to-run function Menu “0.1”, function type “.5”.
X20 potential-free relay contact The relay functions can be found in the “Table of menus” section under menu 2.7. Caution - Avoid damage to components! Maximum current of 1 A at 230 VAC and 0.4 A at 24 VDC ...
After exiting the program, the door must carry out a full opening and closing operation in self- hold mode. The force monitoring is a self-learning system which is effective for an opening width range of 5 cm - 2 m (approx.). Slow progressive changes, e.g. gradual reduction of the spring tension, are compensated for automatically.
Only the middle point is displayed, unless “WSD” is active, in which case both points are displayed. Execution of the “Standby” function is stopped by issuing a command or by operating the “S” selector switch. Pos: 12.2 /BA_Module_Manuell/Torsteuerung TS 959/MAL_Seitenumbruch @ 6\mod_1344937085969_0.docx @ 758205 @ @ 1...
Pos: 13.1 /BA_Module_Manuell/Torsteuerung TS 959/13_Statusanzeige @ 6\mod_1344924569171_28.docx @ 757803 @ 1 @ 1 11 Status display Faults “F” plus a code are displayed in each case Status Fault description Measures for fault correction code Terminals X3.1 – X3.2 are open.
Page 28
Faults “F” plus a code are displayed in each case Status Fault description Measures for fault correction code Triggering of the force monitoring. Check the door mechanism for stiffness. Switch control off and on. ROM fault. Replace control if necessary. Switch control off and on.
Page 29
Commands “E” plus a code are displayed in each case Code Command description An “Open” command is active. Control inputs X5.3 A “Stop” command is active. Control inputs X5.2 A “Close” command is active. Control inputs X5.4...
Page 30
Upwards travel active. Flashing Closing operation active. Flashing Stoppage between the set final limit positions. Stoppage at the “Open” final limit position. Stoppage at the “Close” final limit position. Pos: 13.2 /BA_Module_Manuell/Torsteuerung TS 959/MAL_Seitenumbruch @ 6\mod_1344937085969_0.docx @ 758205 @ @ 1...
Pos: 14.1 /BA_Module_Manuell/Torsteuerung TS 959/14_Zeichen_Erklärung @ 6\mod_1344924585411_28.docx @ 757818 @ 1 @ 1 12 Explanation of symbols Symbol Explanation Request: Read mounting manual Request: Check Request: Note Request: Note the setting of the menu below Default adjustment of the menu...
Page 32
Symbol Explanation Request: Adjustment via built in push button OPEN/CLOSE, OPEN push button upwards; CLOSE push button downwards Request: Press STOP button once via built in push-button Request: Save, press stop-button once via built in push-button Request: Save, press STOP-button for three seconds via built in push-button Request: Reset the control, press stop-button for three seconds via built in push-button Request: Start door positions...
Pos: 15.2 /BA_Module_Manuell/Torsteuerung TS 959/15_Herstellererklärung @ 6\mod_1344924612586_28.docx @ 757833 @ @ 1 Declaration of Incorporation/Declaration of Conformity Declaration of Incorporation pursuant to Machinery Directive 2006/42/EC for a partly completed machine Appendix II Part B GfA - Gesellschaft für Antriebstechnik Dr.-Ing Hammann GmbH & Co KG Declaration of Conformity Wiesenstraße 81...