Watt Stopper PW-100-24 Installation Instructions Manual

Watt Stopper PW-100-24 Installation Instructions Manual

Passive infrared low voltage wall switch occupancy sensor

Advertisement

Passive Infrared Low Voltage
Wall Switch Occupancy Sensor

Specifications

Voltage . . . . . . . . . . .18-24VDC, 24VAC or Half-wave rectified AC
Current Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20mA
Power Supply . . . . . . . . . . . . . . . . . . .Watt Stopper Power Packs
Isolated Relay Rating . . . . . . . . . . . . . . . . . . . . .1A @30VDC/VAC
Time Delay Adjustment . . . . . . . . . . . . . . . . . . . .5 to 30 minutes
Walk-Through Mode . .3 minutes if no activity after 30 sec.
Test Mode . . . 5 sec. at initial power up or DIP switch reset
PIR Adjustment . . . . . . . . . . . . . . . . . . .High or Low (DIP switch)
Light Level Adjustment . . . . . . . . . . . . . . . . . . . . . . .8fc to 180+fc
Alerts
. . . . . . . . . . . . . . . . . . . . . .Selectable Audible & Visual
PW-100-24
US Patents: 5640113, 6617560B2,
A4787722, A4874962
Santa Clara, CA 95050
800.879.8585

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PW-100-24 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Watt Stopper PW-100-24

  • Page 1: Specifications

    Current Consumption ......20mA Power Supply ....Watt Stopper Power Packs Isolated Relay Rating .
  • Page 2: Unit Description And Operation

    The PW-100-24 Passive Infrared Low Voltage Wall Switch sensors use advanced passive infrared (PIR) technology. The PW-100-24 sensor can turn a load on, and hold it on as long as the sensor detects occupancy. After no movement is detected for the selected time delay, the lights switch off.
  • Page 3: Time Delays

    Time Delays The PW-100-24 holds the load ON until no motion is detected for the selected time delay. Select the time delay using DIP switch settings. The sensor automatically sets the time delay when Auto/Test is enabled for maximum energy savings.
  • Page 4: Coverage Patterns

    Alerts The PW-100-24 can provide audible and/or visible alerts as a warning before the load turns OFF. Visible Alert When only one minute is left in the time delay, the load connected to the relay turns OFF for one second. This...
  • Page 5: Installation

    6. Attach the cover plate. White (Neutral) Red (Line) Lighting White Load Power Neutral Pack Black (Load) +24 VDC Common Isolated Relay Outputs Control Outputs Normally closed contact Common Normally open contact Not used PW-100-24 Wiring Visit our website for FAQs: www.wattstopper.com...
  • Page 6: Dip Switch Settings

    DIP SWITCH SETTINGS ON Mode Time Visible Not Used Delay Alerts 1 2 3 Time Delay Auto/Test 5 minutes Audible Alert Disabled 10 minutes Walk-Through Audible Alerts Enabled 15 minutes PIR Sensitivity 20 minutes 25 minutes PIR Sensitivity ON Mode 30 minutes High Auto On...
  • Page 7: Sensor Adjustment

    ADJUSTMENTS Sensor Adjustment Remove the wall plate. Remove the button cap by firmly squeezing together the top sides of the button assembly. Gently pull it away from the unit. When the adjustments are completed, replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the button while pressing it into the unit.
  • Page 8: Ordering Information

    * One ASP-211 Cover Plate for single gang box is included with each switch. Warranty Information Watt Stopper/Legrand warranties its products to be free of defects in materials and workmanship for a period of five years. There are no obligations or...