Pentair Raychem NGC-UIT2-0RD Installation Instructions And Specifications page 8

User interface terminal for raychem ngc systems

Advertisement

rs-485 configuration switches
The configuration switches are found on the right side of the
NGC-UIT2-ORD. Refer to the table below for settings.
position
switch
on
Pull-down
(As-shipped default) RS-485 network
"–" signal is forced to a determinate
state when idle.
Pull-up
(As-shipped default) RS-485 network
"+" signal is forced to a determinate
state when idle.
Termination
(As-shipped default) RS-485 network
is terminated with 120-ohm resistor.
reset switch
The Reset switch can be found on the side of the NGC-UIT2-ORD. A
pointed object is required to press the reset switch and restart the
NGC-UIT software.
NORTH AMERICA
Tel: +1.800.545.6258
Fax: +1.800.527.5703
Tel: +1.650.216.1526
Fax: +1.650.474.7711
thermal.info@pentair.com
Pentair and NGC are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right
to change specifications without prior notice.
© 2010-2015 Pentair.
INDUSTRIAL HEAT TRACING SOLUTIONS
off
RS-485 network "–" signal is not
forced to a determinate state when
idle.
RS-485 network "+" signal is not
forced to a determinate state when
idle.
RS-485 network is not terminated.
EuROpE, MIddlE EAsT, AfRICA
Tel: +32.16.213.511
Fax: +32.16.213.603
thermal.info@pentair.com
GB-RaychemNGCUIT20RD-IM-H58531     INSTALL-168      05/15
RS-485-1
Termination
3 2 1
ON
comments
One device (typically this NGC-UIT2-ORD) on the
RS-485 network should force the network "-" signal
to a determinate state.
One device (typically this NGC-UIT2-ORD) on the
RS-485 network should force the network "+" signal
to a determinate state.
Terminate the device (NGC-UIT2-ORD or other) that
is at each end of the RS-485 network, for a total of
two terminated devices. No other devices on the
network should be terminated.
AsIA pACIfIC
Tel: +86.21.2412.1688
Fax: +86.21.5426.2937
cn.thermal.info@pentair.com
RS-485-2
Termination
Reset
WWW.PENTAIRTHERMAL.COM
lATIN AMERICA
Tel: +1.713.868.4800
Fax: +1.713.868.2333
thermal.info@pentair.com