1. Safety and EMC Instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1.1 Installation See installation instructions before connecting to the supply. ★ Condensation may occur if the UPS is moved directly from a cold ★...
★ UPS has provided earthed terminal, in the final installed system configuration, equipotential earth bonding to the external UPS battery cabinets. ★ An appropriate disconnect device as short-circuit backup protection should be provided in the building wiring installation. Please see the disconnect device specification in chapter 5.2. Equipment the powered more than one source.
Do not remove the enclosure. This system is to be serviced by ★ qualified service personnel only. Remove the protective panel only after disconnecting the terminal ★ connections. Use No. 12AWG (for I3000(S) output terminal), 9 copper wire ★ 0 ℃ and 12 lb-in Torque force when connecting to terminal block.
★ When changing batteries, replace with the same quantity and the same type of batteries. Do not attempt to dispose of batteries by burning them. It could ★ cause explosion. Do not open or destroy batteries. Effluent electrolyte can cause ★...
2. Description of Commonly Used Symbols Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourself with them and understand their meaning:...
3. Introduction This On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers. The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current.
4. Panel Description The Display Panel Switch Function Turn on UPS system: By pressing the ON-Button “I” the UPS system is turned on. ON-Button Deactivate acoustic alarm: By pressing this Button an acoustic alarm can be deactivated. When mains power is normal, the UPS system switches to No output or Bypass mode by pressing OFF-Button “...
The LCD Display Display Function Input Information Indicates the input Line voltage value, which could be displayed from 0 to 999Vac Indicates the frequency value of input Line voltage, which could be displayed from 0 to 99Hz Indicates the input Line current value, which could be displayed from 0 to 99.9A Indicates the input Line voltage is higher than the SPEC value and the UPS would be in the battery mode...
Indicates the input Line voltage is lost and the UPS would be in the battery mode Output Information Indicates the UPS output voltage value, which could be displayed from 0 to 999Vac Indicates the frequency value of the UPS output voltage, which could be displayed from 0 to 99Hz Indicates the UPS output current value, which could be displayed from 0 to 99.9A...
Page 14
Indicates the battery is charging Indicates the battery is discharging UPS status Information Indicates USP operating status including the operating mode, or some warnings or faults in the UPS, and the codes are illuminated in detail in the following chapter Indicates the UPS is working in bypass mode, the load is directly supplied by the input power through bypass Indicates the UPS is working in line mode...
5. Connection and Operation The system may be installed and wired only by qualified electricians in accordance with applicable safety regulations! When installing the electrical wiring, please note the nominal amperage of your incoming feeder. 5.1 Inspection: Inspect the packaging carton and its contents for damage. Please inform the transport agency immediately should you find signs of damage.
Page 16
UPS INPUT NFB Model No. VOLTAGE CURRENT I1000(S) 300Vac I2000(S) 300Vac I3000(S) 300Vac (2) UPS Output Connection The output of the UPS is IEC socket-types. Simply plug the load power cord to the output sockets to complete connection. Use one cord for every 5A load.
(3) EPO Connection: User can select the polarity of EPO. ● Normally open Normally the EPO connector is open on the rear panel. Once the connector is closed with a wire, the UPS would stop the output until the EPO status is disabled. Disable the EPO status Enable the EPO status ●...
Press “I” button continuously for more than 1 second to turn on the UPS, the UPS will get into the inverter mode, the LCD screen will indicate the state of the UPS. (2) Without utility power connecting: If UPS is cold start without utility power connecting, user need to push “I”button twice, first pushing “I”...
5.7 Audible alarm mute function: If the alarm is too annoying in battery mode, you may press “I” button continuously for more than 1 second to clear it. Moreover, the alarm will be enabled when the battery is low to remind you to shutdown the load soon.
Page 20
(6) The red wire is connected to the "+" terminal of the battery. The black wire is connected to the "-" terminal of the battery. (Note: the green/yellow wire is grounded for protection purpose.) (7) Make sure the wires are fasten, install the terminal block cover on the rear panel of the UPS.
6. Operating Mode for All Models The different codes could be displayed on the LCD screen corresponding to their own operating modes, and they are illustrated as the following table. At any time, only one normal operating mode or fault mode is presented. But the warning, even several warnings could appear in a certain normal operating mode at one time.
If output overloaded, the load percent is shown and alarm will keep twice every second. You should get rid of some unnecessary loads one by one to decrease the loads connected to the UPS less than 90% of its nominal power capacity. Note: Please follow the following steps to connect the generator :...
■ ■ ■ ■ The Battery mode 6.3 Bypass mode The LCD display in bypass mode is shown in the following diagram. The information about the utility power, the battery, the UPS output and the load could be displayed. The UPS will beep once every 2 minutes in bypass mode.
6.4 NO output mode The LCD display in No output mode is shown in the following diagram. The information about the utility power, the battery, the UPS output and the load could be displayed. The “00” code indicates the UPS is working in the No output mode.
7. Setting by LCD Module The output voltage and frequency and bypass state could be set directly through LCD module. The output voltage could be set to 208V, 220V, 230V and 240V. The output frequency could be set to 50Hz and 60Hz. The bypass state could be set to enable and disable.
Page 26
■ ■ ■ ■ Here is a example for changing the output voltage from 220Vac to 230Vac through the LCD panel. Setp 1: One flickering black dot would appear before “208Vac” after pressing the “Select” button. Setp 2: The flickering dot would move to “230Vac” after pressing the “Select”...
Page 27
Setp 3: The dot before “230Vac” would turn to flickerless after pressing the “Enter” button, and the flickering dot would move to the next “240Vac”. Setp 4: The output voltage would be 230Vac after the UPS is turned -24-...
8. Trouble Shooting If the UPS system does not operate correctly, check the operating status on the LCD display. Normal operating mode Code No output mode Bypass mode Line mode Battery mode Battery test mode ECO mode Converter mode Warning Code Site fail Fan fail...
Page 29
Fault Code Bus fault Inverter fault Overload fault Over temperature fault Inverter short Bus short If the UPS system does not operate correctly, please attempt to solve the problem using the table below. Problem Possible cause Remedy No indication, no No input voltage Check building wiring warning tone even...
Page 30
Battery is over Switching to battery mode Battery over voltage charged automatically, and after the battery voltage is normal and the mains is normal, the UPS would Switching to line mode automatically again. Battery voltage is When audible alarm Battery low sounding every second, battery is almost empty.
Page 31
EPO function is Plug into the EPO switch. EPO active enabled UPS internal fault Notify dealer Bus fault UPS internal fault Notify dealer Inverter fault Over temperature Check the ventilation of the Over temperature UPS, check the ambient fault temperature and ventilation. Output short circuit Remove all the loads.
9. Maintenance 9.1 Operation The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case please contact your dealer. 9.2 Storage If the batteries are stored in temperate climatic zones, they should be charged every three months for 1~2 hours.
10. Technical Data 10.1 Electrical specifications INPUT Model No. I1000(S) I2000(S) I3000(S) Phase Single Frequency (45~55)/(54~66) Hz Current(A) OUTPUT Model No. I1000(S) I2000(S) I3000(S) Power rating 1kVA/0.8kW 2kVA/1.6kW 3kVA/2.4kW Voltage 200/208/220/230/240 V AC × ( 士 ) 50/60 ± 0 .2Hz (Battery mode) Frequency Wave form sinusoidal...
11. Communication Port The communication port is for the monitoring software. A USB port and an intelligent slot are provided. 11.1 USB The USB port is compliance with USB 1.1 protocol. 11.2 RS232 Interface(Option) The following is the pin assignment and description of DB-9 connector.
Page 36
DB-9 Interface of AS400 communication protocol -33-...
12. Software Free Software Download – WinPower WinPower is a brand new UPS monitoring software, which provides user-friendly interface to monitor and control your UPS. This unique software provides safely auto shutdown for multi-computer systems while power failure. With this software, users can monitor and control any UPS on the same LAN no matter how far from the UPSs.