C. Common Condensate Pump/Sump - Bryant BFIT 1000 Installation, Operation And Maintenance Manual

Condensing hydronic boiler. condensing with the power to fit
Table of Contents

Advertisement

VIII. Condensate disposal (continued)
1. Some jurisdictions may require that the
B. Condensate Neutralizer Installation
condensate be neutralized before being
disposed of. Follow local codes pertaining to
condensate disposal.
2. A condensate neutralizer kit is available from
factory as optional equipment. Refer to Table
12 for size specific part number . Follow local
codes and instructions enclosed with the kit
for condensate neutralizer installation.
3. Limestone chips will get coated by neutral
salts (product of chemical reaction between
limestone and acidic condensate) and
lose neutralizing effectiveness over time.
Therefore, periodic condensate neutralizer
maintenance and limestone chip replacement
must be performed.
Table 12: Condensate Newutralizer Kit
Condensate
Boiler
Neutralizer
Model
BFIT 1000
107860-01
BFIT 1250
107860-02
BFIT 1500
107860-02
BFIT 2000
107860-02
1. A common condensate pump/sump may

C. Common Condensate pump/Sump

be used. Run separate piping from each
condensate drain to the sump. A common drain
may be used to discharge condensate from the
sump.
2. If a common sump is used, individual drain
lines should be constructed, using material
listed above, such that one drain cannot back
feed into another drain.
3. Do not manifold boiler condensate and vent
drains together.
Condensate
Neutralizer,
107886-01
Kit, PN
Refill Kits
107886-02
107866-02
107866-02
Failure to fill the condensate trap with water
prior to boiler start-up could cause flue gas to
enter the building, resulting in personal injury
or death.
Failure to install the condensate drain in
accordance with the above instructions could
cause flue gas to enter the building, resulting in
personal injury or death.
Boiler
condensate
condensate drain line in a manner such that
any condensate leakage will not cause property
damage.
If the condenate line is obstructed in any way,
the float switch will prevent the appliance from
firing.
Some jurisdictions may require that condensate
be neutralized prior to disposal.
The condensate drain trap should be flushed
with clean water as part of your boiler
maintenance schedule to remove any debris
that might have accumulated.
34
WARNING
NOTICE
is
corrosive.
Route