RM7895A,B,C,D/EC7895A,C; RM7896A,C,D 7800 SERIES RELAY MODULES
Termina
l
Number
Description
G
Flame Sensor Ground
Earth G
a
Earth Ground
L2(N)
Line Voltage Common
3
Alarm
4
Burner Motor
5
Line Voltage Supply (L1)
6
Burner Controller and Limits
7
Lockout Interlock
8
Pilot Valve/Ignition
9
Main Fuel Valve
10
Ignition
F(11)
Flame Sensor
12 to 20 Unused
21
2nd Stage Main Valve
(EC7895C, RM7895C,D;
RM7896C,D)
22
Shutter
a
See Table 2.
b
2000 VA maximum load connected to RM7895A,B,C,D/EC7895A,C/RM7896A,B,C,D Assembly.
c
See Tables 4 and 5.
d
Requires 220-240 Vac, 10 VA minimum, stepdown transformer to operate the shutter.
Combination Number
1
C
2
B
3
F
4
F
5
F
6
D
7
D
8
D
9
D
a
RM7895C,D: EC7895C, RM7896C,D only, jumper terminals 8 to 9.
A
4.5A ignition
50 VA Pilot Duty
4.5A ignition.
a
Pilot Duty refers to solenoid-type valves.
32-00156—01
Table 3. Terminal Ratings.
120 Vac, 1A pilot duty.
120 Vac, 9.8A AFL, 58.8 ALR
(inrush).
120 Vac (+10/-15%), 50 or 60 Hz
b
(±10%).
120 Vac, 1 mA.
120 Vac, 8A run, 43A inrush.
120 Vac
120 Vac
120 Vac
60 to 220 Vac, current limited.
120 Vac
120 Vac, 0.5A
Table 4. Combinations for Terminals 8, 9, 10 and 21.
Pilot Fuel 8
F
F
No Load
a
F
a
No Load
F
a
No Load
D
a
No Load
Table 5. Composition of each Combination.
B
a
180 VA Ignition plus
plus
motor valves with:
660 VA inrush,
360 VA open,
240 VA hold.
RM7895/RM7896
c
c
c
c
Main 9
No Load
No Load
A
A
A
A
A
A
A
C
2A Pilot Duty.
8
Ratings
EC7895
220-240 Vac, 1A pilot duty.
220-240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac (+10/-15%), 50 or 60 Hz
(±10%).
220-240 Vac, 1 mA.
8A at PF = 0.5, 40A inrush, 2A at PF = 0.2.
220-240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac, 2A at PF = 0.2
60 to 220 Vac, current limited.
220-240 Vac, 4A at PF = 0.5, 20A inrush.
d
220-240 Vac
Delayed Main Valve
Ignition 10
No Load
No Load
No Load
No Load
F
No Load
D
No Load
D
D
a
65 VA Pilot Duty
motor valves with:
3850 VA inrush,
700 VA open,
250 VA hold.
21
F
a
plus