Installation, Operation and Maintenance
Owner's Manual
SQ-PA, S1Q-PA, S2Q-PA, S5Q-PA, S8Q-PA, S12Q-PA,
SSM-14, SSM-17, SSM-24, SSM-37, SSM-39
Manufactured in Canada by:
425 Clair Road West • P.O. Box 1719
Guelph, ON • N1L 1R1 • Canada
t. 519.763.1032 • f. 519.763.5069
EPA# 57987-CN-001
e. water@r-can.com
September 2005
i. www.r-can.com
P/N 520104

Advertisement

Table of Contents
loading

Summary of Contents for Sterilight Silver SQ-PA

  • Page 1 Installation, Operation and Maintenance Owner’s Manual SQ-PA, S1Q-PA, S2Q-PA, S5Q-PA, S8Q-PA, S12Q-PA, SSM-14, SSM-17, SSM-24, SSM-37, SSM-39 Manufactured in Canada by: 425 Clair Road West • P.O. Box 1719 Guelph, ON • N1L 1R1 • Canada t. 519.763.1032 • f. 519.763.5069 EPA# 57987-CN-001 e.
  • Page 2 Your Sterilight system uses the most advanced UV technology on the market and is designed to provide you with years of trouble free operation...
  • Page 3: Table Of Contents

    ABLE OF ONTENTS Parts / Schematic Breakdown Safety Instructions Water Chemistry Installing Your UV Disinfection System Disinfection Procedure Operating & Maintenance Instructions Operation 10-13 Troubleshooting 14-15 Silver Series Dose Flow Chart Specifications 16-17 Manufacturer’s Warranty YMBOLS Protective Caution Ground Electrical Fragile Warning Eye Protection...
  • Page 4 ARTS Controller POWER - 100-240V./50-60Hz. BA-ICE-S SILVER “BASIC” SYSTEM BA-ICE-SM SILVER “PLUS” SYSTEM Hard glass, coated Sterilume -EX UV lamps ® for long, consistent life (9000 hours) S212RL FOR SQ-PA lamp connector S287RL FOR S1Q-PA & SSM-14 S330RL FOR S2Q-PA & SSM-17 S463RL FOR S5Q-PA &...
  • Page 5: Safety Instructions

    AFETY NSTRUCTIONS WARNING - to guard against injury, basic safety precautions should be observed, including the following: 1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS. 2. CAUTION - Disconnect power before servicing. 3. DANGER - To avoid possible electric shock, special care should be taken since water is present near electrical equipment.
  • Page 6: Water Chemistry

    ATER HEMISTRY Water quality is extremely important for the optimum performance of your UV system. The following levels are recommended for installation: • Iron: < 0.3 ppm (0.3 mg/L) • Hardness*: < 7 gpg (120 mg/L) • Turbidity: < 1 NTU •...
  • Page 7 1. The above picture shows the installation of a to 4-20mA outlet typical disinfection system and the related components that may be used for the installation. The use of a by-pass assembly is recommended in case the system requires “off- optional 4-20MA “Y”...
  • Page 8 3. Mount the system to the wall using the supplied clamps. Various connection methods can be used to connect the water source to the system, however union type connectors are recommended. The use of a flow restrictor device is strongly recommended when installing your system in order to maintain the manufacturers rated flow rate.
  • Page 9: Disinfection Procedure

    ISINFECTION ROCEDURE UV disinfection is a physical disinfection process and does not add any potentially harmful chemicals to the water. As UV does not provide a disinfection residual, it is imperative that the entire distribution system located after the UV be chemically disinfected to ensure that the water is free from any bacteriological contaminants.
  • Page 10: Operating & Maintenance Instructions

    PLEASE NOTE: As the Silver “PLUS” systems include a 254nm UV intensity monitor, it should be noted that the introduction of the bleach solution required for disinfection WILL trigger a temporary low UV condition. This is due to the fact that the bleach physically “clouds” the raw water. Once the bleach runs through the system, the alarm condition will return to normal.
  • Page 11 3. To install a new lamp, first remove the lamp from its protective packaging, again being careful not to touch the lamp glass itself. Carefully insert the lamp into the reactor vessel (actually inside the quartz sleeve) (Figure 2C). Insert the lamp fully into the chamber leaving about two inches of the lamp protruding from the chamber.
  • Page 12 UV Sensor Replacement / Cleaning: The UV sensor is an extremely sensitive and fragile instrument. Extreme care is required when handling and cleaning. The sensor window itself is constructed from quartz which is extremely fragile, be careful you do not chip or break this quartz window. Manufacturer’s warranty does not cover damage due to neglect or misuse.
  • Page 13: Operation

    PERATION Basic Systems incorporating BA-ICE-S controller: 1. Lamp life remaining (days): The controller tracks the number of days of operation of the lamp and the controller. The default screen will display the total lamp life remaining (in days). The controller will count down the number of days remaining until the lamp requires changing (365 days to 1 day).
  • Page 14 “PLUS” Systems incorporating BA-ICE-SM controller: 1. UV intensity (%): The Silver “PLUS” series of products incorporate a UV sensor which detects the discrete 254 nm wavelength of the UV lamp. This information is relayed to the Silver “PLUS” controller and is the default display shown in “% UV output”. The system will display the UV output between 50 to 99 percent.
  • Page 15 Possible causes for low uv alarm conditions: i) The UV lamp has perhaps reached a level whereby it can no longer adequately provide a sufficient level of disinfection due to age (> 9000 hours). The lamp should be replaced with a new lamp from the manufacturer of the same size and type.
  • Page 16 6. 4-20mA output (optional): For those looking for the capability to transmit the UV intensity data to a remote location via a 4-20 mA signal, an optional “Y” cable is available from your dealer (Figure 5A). Please order PN 260134. This “Y” cable comes with 20 meters (65‘) of cable for the 4-20 mA signal.
  • Page 17: Troubleshooting

    ROUBLESHOOTING TROUBLESHOOTING GUIDE Symptom Possible Causes Solutions • replace filter cartridge with appropriate 5 • sediment pre-filter micron cartridge clogged Note: check source water supply as Pressure Drop fluctuations may occur in source pressure • flow regulator will result in pressure drop •...
  • Page 18: Silver Series Dose Flow Chart

    DISPLAY FAULT MODES • lamp life expired - countdown is at “0” days LED display reads • press reset button for a deferred alarm, replace UV “A3” lamp • controller is in lamp failure mode • power system down, allowing it to reset itself; apply power in order to confirm that the controller is able to LED display is blank power lamp...
  • Page 19: Specifications

    “BASIC”: PECIFICATIONS ILVER MODEL SQ-PA S1Q-PA S2Q-PA S5Q-PA S8Q-PA S12Q-PA US Public 7.5 lpm 12.3 lpm 15 lpm 41.6 lpm 75.7 lpm 110 lpm Health (2 gpm) (3.3 gpm) (4 gpm) (11 gpm) (20 gpm) (29 gpm) 16 mJ/cm (0.5 m /Hr.) (0.7 m /Hr.)
  • Page 20 “PLUS”: PECIFICATIONS ILVER MODEL SSM-14 SSM-17 SSM-24 SSM-37 SSM-39 US Public 12.3 lpm 15 lpm 41.6 lpm 75.7 lpm 110 lpm Health (3.3 gpm) (4 gpm) (11 gpm) (20 gpm) (29 gpm) 16 mJ/cm (0.7 m /Hr.) (0.9 m /Hr.) (2.5 m /Hr.) (4.5 m...
  • Page 21: Manufacturer's Warranty

    ’ ANUFACTURER ARRANTY Manufacturer warrants the ultraviolet disinfection system hardware and electrical systems to be free from defects in material and workmanship for a period of five (5) years from the date of purchase by the original owner (consumer) on a pro-rated basis. Manufacturer warrants the ultraviolet lamps to be free from defects in material and workmanship for a period of one (1) year and the reactor chamber for a period of seven (7) years.