Clearances; Fuet Gas Supply; Flue Vent System; Etectrical Supply - Beckett CG10 Manual

Hide thumbs Also See for CG10:
Table of Contents

Advertisement

Test For Gas Pipe Leaks
Leaking
gas could result in asphyxiation,
explo-
sion, or fire hazard.
The gas supply piping must be absolutely leak-free.
Pressure test the gas piping with air that is at least
three times greater than the gas pressure being
used.
Verify that there are no leaks before proceeding.
O
Clearances
With the burner installed in the appliance, there must be
adequate space in front of and on the sides of the burner
to allow access and operation.
Verify that the clearance
dimensions comply with local codes and with the appli-
ance manufacturer's
recommendations.
O
Fuel
gas
supply
Verify that the gas supply piping complies with all appli-
cable local codes and the latest edition of the National
Fuel Gas Code ANSI Z223.1 (NFPA 54).
Insure that the supply gas pipe size is capable of provid-
ing at least the minimum pressure required to the burner
gas train inlet at the burner's full capacity rating. Refer
to Table 1.
O
Flue
vent
system
The flue gas vent system must be in good condition and
must comply with National Fuel Gas Code ANSI Z223.1
(NFPA 54) and all other applicable codes having jurisdic-
tion for vent construction, capacity, and sizing.
O
Electrical
supply
Check the nameplate on the burner to verify that the
power connections available are correct for the burner.
Refer to Figure 1. All power must be supplied through
fused disconnect
switches and comply with the latest
edition of National Electric Code NFPA 70 (Canada CSA
C22.1) and all other local or applicable codes.
O
Verify
burner
components
Burner model can be checked from burner carton or
rating label on burner
Flange mounting arrangement (Includes high-tem-
perature gasket and/or
fiber rope for pressure fir-
ing)
O
Verify
firing
input
range
Refer to appliance manufacturer's
instructions (if avail-
able) for the firing input range. Otherwise the maximum
recommended firing range for the burner depends on the
length and width of the firing chamber and the distance
from the burner center to the chamber floor. Verify that
the chamber dimensions are at least as large as the min-
imum values given in Figure 2. If the appliance dimen-
sions are smaller, reduce the firing rate accordingly.
i NOTICE
I
Dimensions shown are for cast iron sectional boilers with
uptakes between sections. For minimum dimensions of
other furnace types consult R.W. Beckett Corporation.
Figure 2. Minimum Combustion
Chamber Dimensions
300-400
600-900
18
12
12
26
16
16
6
6
61 04 BCG10
R08

Advertisement

Table of Contents
loading

Table of Contents