KT1210W Temperature Controller

1. Overview

Wide range working voltage.
Support delay start and time shutdown.
Heating or cooling mode can be set.
All parameters setting can be saved after short circuit.
high Control precision 0.1 centigrade
Can be used for domestic freezer, water tanks, refrigerator,
industrial chiller, steamer, industrial equipment and other
temperature-controlled system.

2. Specifications

Power Supply: AC90~250V 50/60HZ/ DC12V/ DC24V
Temperature control range: -50~110°C
Difference Set Value: 0.1~30°C
Resolution Ratio: 0.1°C(-9.9-99.9); 1°C(other range)
Measurement accuracy: ±0.1°C
Control accuracy: 0.1°C
Measuring inputs: NTC(10K0.5%) Waterproof sensor
Output: Relay Contact Capacity 10A/220V normally open
Environmental requirements: -20-70°C , humidity 20%
-85%RH
Size: 75mm(L)*34mm(W)*85mm(Depth)
Hole size: 71(L)*29(W)mm
Power consumption: Static current: ≤35MA,attract current:
≤65MA

3. Wiring Diagram

Connection 1:Independent power supply for load
Connection 2:Same power supply for load
Operating Manual

4. Key Instruction

S:Set key,Confirm the setting value,Entry and Set parameter.
:powr on/off, or quit the setting.
:increase value
Work:output indicator

5. Key Operation Instruction

In normal working status, hold
hold
3seconds to power on.
In normal working status, press S. The led flash.Press
or
to increase or decrease the setting temperature
value. Press S to save it and back to normal screen.
In normal working status, press S for 3s to enter set mode.
Press
to switch from HC-A7.(see menu code). Press
S to enter any code,press
for
Both press

6. Operation Instruction

In normal working status, the screen display RT(real time
temperature value).
①Cooling mode: HC set to C. use cooler as load. When
RT ≥ ST (temperature set value) + D (difference value),
work indicator turn on. output relay connect. Load start to
work. When RT ≤ ST, work indicator turn off, output
relay disconnect, load stop working.
For example,set 10 ℃ ,difference 3 ℃ ,cooler work when
RT≥13℃.cooler stop when RT≤10℃.
② Heating mode: HC set to H,use heater as load. When
RT≤ST-D, work indicator turn on. output relay connect.
load start to work. When RT≥ST, work indicator turn off,
output relay disconnect, load stop working.
For example,set 10 ℃ ,difference 3 ℃ ,heater work when
RT≤7℃.heater stop when RT≥10℃.
Code
explain
HC
Heating/Cooling
D
Return Difference
LS
Set low Limit
HS
Set high limit
PU
Delay Start
CA
Temp correction
A7
Timing stop output
:
decrease value
Set:Setting indicator
3seconds to power off,
to change code setting.
3seconds to reset the controller.
Setting
Factory
Range
Setting
H/C
C
0.1-30
2.0
-50
-50
+110
110
0-90minute 0
-10-10
0.0
0-999minute 000