KT1210W Temperature Controller
1. Overview
•
Wide range working voltage.
•
Support delay start and time shutdown.
•
Heating or cooling mode can be set.
•
All parameters setting can be saved after short circuit.
•
high Control precision 0.1 centigrade
•
Can be used for domestic freezer, water tanks, refrigerator,
industrial chiller, steamer, industrial equipment and other
temperature-controlled system.
2. Specifications
•
Power Supply: AC90~250V 50/60HZ/ DC12V/ DC24V
•
Temperature control range: -50~110°C
•
Difference Set Value: 0.1~30°C
•
Resolution Ratio: 0.1°C(-9.9-99.9); 1°C(other range)
•
Measurement accuracy: ±0.1°C
•
Control accuracy: 0.1°C
•
Measuring inputs: NTC(10K0.5%) Waterproof sensor
•
Output: Relay Contact Capacity 10A/220V normally open
•
Environmental requirements: -20-70°C , humidity 20%
-85%RH
•
Size: 75mm(L)*34mm(W)*85mm(Depth)
•
Hole size: 71(L)*29(W)mm
•
Power consumption: Static current: ≤35MA,attract current:
≤65MA
3. Wiring Diagram
Connection 1:Independent power supply for load
Connection 2:Same power supply for load
Operating Manual
4. Key Instruction
S:Set key,Confirm the setting value,Entry and Set parameter.
:powr on/off, or quit the setting.
:increase value
Work:output indicator
5. Key Operation Instruction
•
In normal working status, hold
hold
3seconds to power on.
•
In normal working status, press S. The led flash.Press
or
to increase or decrease the setting temperature
value. Press S to save it and back to normal screen.
•
In normal working status, press S for 3s to enter set mode.
Press
to switch from HC-A7.(see menu code). Press
S to enter any code,press
for
•
Both press
6. Operation Instruction
•
In normal working status, the screen display RT(real time
temperature value).
•
①Cooling mode: HC set to C. use cooler as load. When
RT ≥ ST (temperature set value) + D (difference value),
work indicator turn on. output relay connect. Load start to
work. When RT ≤ ST, work indicator turn off, output
relay disconnect, load stop working.
•
For example,set 10 ℃ ,difference 3 ℃ ,cooler work when
RT≥13℃.cooler stop when RT≤10℃.
•
② Heating mode: HC set to H,use heater as load. When
RT≤ST-D, work indicator turn on. output relay connect.
load start to work. When RT≥ST, work indicator turn off,
output relay disconnect, load stop working.
•
For example,set 10 ℃ ,difference 3 ℃ ,heater work when
RT≤7℃.heater stop when RT≥10℃.
Code
explain
HC
Heating/Cooling
D
Return Difference
LS
Set low Limit
HS
Set high limit
PU
Delay Start
CA
Temp correction
A7
Timing stop output
:
decrease value
Set:Setting indicator
3seconds to power off,
to change code setting.
3seconds to reset the controller.
Setting
Factory
Range
Setting
H/C
C
0.1-30
2.0
-50
-50
+110
110
0-90minute 0
-10-10
0.0
0-999minute 000