SECTION C: Installation
Fig. 24: Horizontal Through-the-Wall Direct Venting
CAUTION: This venting system requires the installa-
tion of a condensate drain in the vent piping per the
vent manufacturer's instructions. Failure to install a
condensate drain in the venting system will void all
warranties on this heater.
Installation
These installations utilize the heater-mounted blower to
vent the combustion products to the outdoors. Com-
bustion air is taken from inside the room and the vent is
Certified Vent
Model
Material
503
753
1003
Category IV
1253
(AL29-4C)
1503
1753
2003
* Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.
** Subtract 10 ft per elbow. Max. 4 elbows.
Table M: Category IV Horizontal Vent & Horizontal Direct Vent
Horizontal
Vent Size
Vent Length (Ft)*
(in.)
Min.
Max.
6
0
75
8
26
installed horizontally through the wall to the outdoors.
Adequate combustion and ventilation air must be sup-
plied to the equipment room in accordance with the
NFGC (U.S.) or B149.1 (Canada).
The total length of the horizontal through-the-wall flue
system should not exceed 75 equivalent ft in length. If
horizontal run exceeds 75 equivalent ft, an appropri-
ately sized variable-speed extractor must be used. Each
elbow used is equal to 10 ft of straight pipe. This will
allow installation in one of the four following arrange-
ments:
• 75' of straight flue pipe
• 65' of straight flue pipe and one elbow
• 55' of straight flue pipe and two elbows
• 45' of straight pipe and three elbows
The vent cap is not considered in the overall length of
the venting system.
The vent must be installed to prevent flue gas leakage.
Care must be taken during assembly to ensure that all
joints are sealed properly and are airtight. The vent
must be installed to prevent the potential accumulation
of condensate in the vent pipes. It is required that:
1. The vent must be installed with a condensate drain
located in proximity to the heater as directed by
the vent manufacturer.
2. The vent must be installed with a slight upward
slope of not less than 1/4 inch per foot of horizon-
tal run to the vent terminal.
Combustion Air
Intake Pipe
Material
Galvanized Steel,
PVC,
ABS,
CPVC
Air Inlet
Max. Length (Ft) **
6"Ø 8" Ø 10" Ø
45
100
N/A
N/A
45
85