ABB UniSec Manual page 14

Air-insulated switchgear
Table of Contents

Advertisement

4.3.3 Medium voltage cable locations and lengths
The medium voltage cable lengths (distance of the cable con-
nection point from the floor) depend on the units and acces-
sories used. The following figures and table show the cable
lengths and locations for the different units.
RLC unit
Details
SDC
Basic
SDC
With CT
SDM
Basic
SFC
292 mm fuse
SFC
442 mm fuse
SBC
Basic
WBC
Basic or with CT
DRC
Basic
DRC
With CT
SBR
Basic
RLC/RRC
Basic
(1)
With optional cable terminal
(2)
Distance between panel side wall and fi rst cable connection
Table 4. Medium voltage cable lengths and locations
14
Figure 34. Medium voltage cable lengths
190 mm width
375 mm width
A (mm)
B (mm)
A (mm)
915
600
450
500
1495
310
500 mm width
B (mm)
A (mm)
B (mm)
210
915
275
525
275
200
600
230
200
450
230
165
670
255
530
275
600 mm width
750 mm width
A (mm)
B (mm)
A (mm)
525
(1)
525
500
600
150
(2)
600
400
B (mm)
275
(1)
275
310
165
390