Indication Of 1St Standby Generator; Light Load Cancel Mode; Light Load Indication; High Load Indication - Selco C6200 FlexGen Configuration Manual

Gencontroller
Hide thumbs Also See for C6200 FlexGen:
Table of Contents

Advertisement

Priority 3 → Input 7 connected to COM
Priority 4 → Input 8 connected to COM
Priority 5 → Inputs 5 and 8 connected to COM
Priority 6 → Inputs 6 and 8 connected to COM
Priority 7 → Inputs 7 and 8 connected to COM
Etc.
Priority 1 means that this generator will be started first and stopped last.

4.13.20 Indication of 1st standby generator

It is possible to use one of the programmable outputs for indication of the first standby generator.
When activated, this output will activate as soon as the respective generator becomes the first
standby generator. Use following command for activation of this function:
Program command Function
WRITE IOFUNC

4.13.21 Light Load Cancel Mode

In some cases it is necessary to disable the load depending stop function, while having load
depending start still activated.
This can be achieved by following command:
Program command Function
WRITE IOFUNC

4.13.22 Light Load Indication

The programmable outputs can be used for indication that the load of the generator is lower than the
load depending stop level:
Program command Function
WRITE IOFUNC

4.13.23 High Load Indication

The programmable outputs can be used for indication that the load of the generator is higher than
the load depending stop level:
Program command Function
Revision: 20-10-2017
1STANDBYINDICATION
LIGHTLOADCANCEL IN1
LIGHTLOADINDICATION
Input Output Alarm
OUT1
Input Output Alarm
Input Output Alarm
OUT1
Input Output Alarm
C6200 FlexGen
Page 53 of 73