GE Digital Energy B90 Instruction Manual

GE Digital Energy B90 Instruction Manual

Low impedance bus differential system, ur series
Table of Contents

Advertisement

Quick Links

GE
Digital Energy
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEDigitalEnergy.com
*1601-0115-AA2*
Addendum
B90 Low Impedance Bus
Differential System
UR Series Instruction Manual
Manual P/N: 1601-0115-AA2 (GEK-119552A)
IND.CONT. EQ.
B90 revision: 7.2x
E83849
LISTED
52TL
836771A2.CDR
GE Multilin's Quality Management
System is registered to ISO
9001:2008
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the B90 and is the answer not in the manual?

Questions and answers

Summary of Contents for GE Digital Energy B90

  • Page 1 Digital Energy Addendum B90 Low Impedance Bus Differential System UR Series Instruction Manual B90 revision: 7.2x Manual P/N: 1601-0115-AA2 (GEK-119552A) 836771A2.CDR E83849 GE Digital Energy LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1...
  • Page 2 Copyright © 2014 GE Multilin Inc. All rights reserved. B90 Low Impedance Bus Differential System UR Series Instruction Manual revision 7.2x. FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista, CyberSentry, HardFiber, Digital Energy, Multilin, and GE Multilin are trademarks or registered trademarks of GE Multilin Inc.
  • Page 3: Table Of Contents

    1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 SYSTEM REQUIREMENTS ................1-5 1.3.2 SOFTWARE INSTALLATION ................1-5 1.3.3 CONFIGURING THE B90 FOR SOFTWARE ACCESS ........1-6 1.3.4 USING THE QUICK CONNECT FEATURE............1-9 1.3.5 CONNECTING TO THE B90 RELAY............... 1-14 1.3.6 SETTING UP CYBERSENTRY AND CHANGING DEFAULT PASSWORD ... 1-15 1.4 UR HARDWARE...
  • Page 4 USER-PROGRAMMABLE PUSHBUTTONS............5-72 5.2.14 FLEX STATE PARAMETERS ................5-78 5.2.15 USER-DEFINABLE DISPLAYS ................5-78 5.2.16 DIRECT INPUTS AND OUTPUTS..............5-81 5.2.17 INSTALLATION ....................5-88 5.3 SYSTEM SETUP 5.3.1 AC INPUTS.......................5-89 5.3.2 POWER SYSTEM ....................5-90 5.3.3 FLEXCURVES ....................5-91 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 5 REMAINING CONNECTION STATUS .............. 6-7 6.3 METERING 6.3.1 PARALLEL REDUNDANCY PROTOCOL (PRP)..........6-8 6.3.2 METERING CONVENTIONS ................6-8 6.3.3 BUS ZONE......................6-9 6.3.4 CURRENTS ....................... 6-9 6.3.5 VOLTAGES...................... 6-10 6.3.6 FREQUENCY....................6-10 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 6 HIGH BREAKPOINT...................9-4 9.3.3 LOW BREAKPOINT ...................9-5 9.4 SLOPES AND HIGH SET THRESHOLD 9.4.1 DESCRIPTION ....................9-6 9.4.2 EXTERNAL FAULTS ON C-1 ................9-6 9.4.3 EXTERNAL FAULTS ON C-2 ................9-7 9.4.4 EXTERNAL FAULTS ON C-3 ................9-7 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 7 MMXN: ANALOG MEASURED VALUES............C-3 C.2.7 PROTECTION AND OTHER LOGICAL NODES ..........C-3 C.3 SERVER FEATURES AND CONFIGURATION C.3.1 BUFFERED AND UNBUFFERED REPORTING ..........C-5 C.3.2 FILE TRANSFER ....................C-5 C.3.3 TIMESTAMPS AND SCANNING ...............C-5 C.3.4 LOGICAL DEVICE NAME..................C-5 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 8 G. RADIUS SERVER G.1 RADIUS SERVER CONFIGURATION G.1.1 RADIUS SERVER CONFIGURATION ..............G-1 H. MISCELLANEOUS H.1 CHANGE NOTES H.1.1 REVISION HISTORY..................H-1 H.1.2 CHANGES TO THE B90 MANUAL ..............H-1 H.2 ABBREVIATIONS viii B90 Low Impedance Bus Differential System GE Multilin...
  • Page 9 TABLE OF CONTENTS H.2.1 STANDARD ABBREVIATIONS .................H-4 H.3 WARRANTY H.3.1 GE MULTILIN WARRANTY ................H-6 INDEX GE Multilin B90 Low Impedance Bus Differential System...
  • Page 10 TABLE OF CONTENTS B90 Low Impedance Bus Differential System GE Multilin...
  • Page 11: Getting Started

    1.1 IMPORTANT PROCEDURES 1 GETTING STARTED 1.1IMPORTANT PROCEDURES Use this chapter for initial setup of your new B90 Low Impedance Bus Differential System. 1.1.1 CAUTIONS AND WARNINGS Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.
  • Page 12: Inspection Procedure

    • GE EnerVista™ DVD (includes the EnerVista UR Setup software and manuals in PDF format) • Mounting screws If there is any noticeable physical damage, or any of the contents listed are missing, contact GE Digital Energy as follows. GE DIGITAL ENERGY CONTACT INFORMATION AND CALL CENTER FOR PRODUCT SUPPORT:...
  • Page 13: Ur Overview

    The remote inputs and outputs provide a means of sharing digital point state information between remote UR-series devices. The remote outputs interface to the remote inputs of other UR-series devices. Remote outputs are FlexLogic oper- ands inserted into IEC 61850 GSSE and GOOSE messages. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 14: Software Architecture

    Employing OOD/OOP in the software architecture of the B90 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functional classes.
  • Page 15: Enervista Ur Setup Software

    Ethernet port of the same type as one of the UR CPU ports or a LAN connection to the UR • Internet access or a DVD drive The following qualified modems have been tested to be compatible with the B90 and the EnerVista UR Setup software: • US Robotics external 56K FaxModem 5686 •...
  • Page 16: Configuring The B90 For Software Access

    To configure the B90 for remote access via the rear Ethernet port, see the Configuring Ethernet Communications sec- tion. • To configure the B90 for local access with a computer through either the front RS232 port or rear Ethernet port, see the Using the Quick Connect Feature section. B90 Low Impedance Bus Differential System...
  • Page 17 10. Click the Read Order Code button to connect to the B90 device and upload the order code. If a communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values.
  • Page 18 MODBUS PROTOCOL 21. Click the Read Order Code button to connect to the B90 device and upload the order code. If an communications error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values.
  • Page 19: Using The Quick Connect Feature

    USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the B90 from a computer through Ethernet, first assign an IP address to the relay from the front panel keyboard. Press the MENU key until the SETTINGS menu displays.
  • Page 20 Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. Click the “Use the following IP address” box. 1-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 21 1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE Enter an IP address with the first three numbers the same as the IP address of the B90 relay and the last number different (in this example, 1.1.1.2). Enter a subnet mask equal to the one set in the B90 (in this example, 255.0.0.0).
  • Page 22 If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been discon- nected from the B90 relay. Start the Internet Explorer software. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup. 1-12 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 23 Click the Quick Connect button to open the Quick Connect dialog box. Select the Ethernet interface and enter the IP address assigned to the B90, then click the Connect button. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Connect”...
  • Page 24: Connecting To The B90 Relay

    The EnerVista UR Setup software has several quick action buttons to provide instant access to several functions that are often performed when using B90 relays. From the online window, users can select the relay to interrogate from a pull-down window, then click the button for the action they want to perform. The following quick action functions are available: •...
  • Page 25: Setting Up Cybersentry And Changing Default Password

    . Be sure to disable this bypass setting after SETTINGS > PRODUCT SETUP > SECURITY > SUPERVISORY commissioning the device. You can change the password for any role either from the front panel or through EnerVista. GE Multilin B90 Low Impedance Bus Differential System 1-15...
  • Page 26 It is strongly recommended that the password for the Administrator be changed from the default. Changing the passwords for the other three roles is optional. Figure 1–10: CHANGING THE DEFAULT PASSWORD 1-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 27: Ur Hardware

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the B90 rear communications port. The converter terminals (+, –, GND) are connected to the B90 communication module (+, –, COM) terminals. See the CPU Communica- tion Ports section in chapter 3 for details.
  • Page 28: Using The Relay

    MESSAGE LEFT key from a setting value or actual value display returns to the header display. HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE)  SETTINGS  SECURITY ACCESS LEVEL:  PRODUCT SETUP  Restricted  SETTINGS  SYSTEM SETUP 1-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 29: Relay Activation

    For more information, see the CyberSentry content in the Security section of the next chapter. 1.5.6 FLEXLOGIC CUSTOMIZATION FlexLogic equation editing is required for setting user-defined logic for customizing the relay operations. See the FlexLogic section in Chapter 5. GE Multilin B90 Low Impedance Bus Differential System 1-19...
  • Page 30: Commissioning

    As such, no further functional tests are required. The B90 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the Relay Self-tests section in chapter 7). However, it is recommended that B90 maintenance be scheduled with other system maintenance.
  • Page 31: Product Description

    The B90 Low Impedance Bus Differential System is a microprocessor-based architecture that provides protection and metering for busbars with up to 24 feeders. The B90 protection system is a centralized architecture built on one B90 IED as per requirements of a particular application. The IED is a full-featured B90 and as such can be accessed and programmed individually.
  • Page 32 Digital elements (48 per IED) Setting groups (6) Direct inputs and outputs (96) Time synchronization over IRIG-B or IEEE 1588 DNP 3.0 or IEC 60870-5-104 communications Time synchronization over SNTP Dynamic bus replica User definable displays B90 Low Impedance Bus Differential System GE Multilin...
  • Page 33: Security

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the B90, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password applies.
  • Page 34 No password or security information are displayed in plain text by the EnerVista software or UR device, nor are they ever transmitted without cryptographic protection. CYBERSENTRY USER ROLES B90 Low Impedance Bus Differential System GE Multilin...
  • Page 35 |------------ Grouped Elements |------------ Control Elements |------------ Inputs / Outputs |--------------- Contact Input Contact Input thresh- |--------------- |--------------- Virtual Inputs |--------------- Contact Output |--------------- Virtual Output |--------------- Remote Devices |--------------- Remote Inputs GE Multilin B90 Low Impedance Bus Differential System...
  • Page 36 The UR has been designed to automatically direct authentication requests based on user names. In this respect, local account names on the UR are considered as reserved, and not used on a RADIUS server. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 37: Iec 870-5-103 Protocol

    103 communication messages. The UR implementation of IEC 60870-5-103 consists of the following functions: • Report binary inputs • Report analog values (measurands) • Commands • Time synchronization The RS485 port supports IEC 60870-5-103. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 38: Order Codes

    Before ordering the B90 system, an analysis of the required protection and monitoring functions is required. Please refer to the UR overview section in chapter 1 for details of the B90 architecture. Also, detailed analyses of required AC inputs and input/output contacts must be performed to select appropriate hardware configurations for each of the B90's IEDs.
  • Page 39 IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + four-zone 24-feeder bus protection + breaker failure + IEC 61850 IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 1 + single-zone 24-feeder bus protection + breaker failure + IEC 61850 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 40 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels 2-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 41: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the serial number of your existing unit. Not all replacement modules may be applicable to the B90 relay. Only the modules specified in the order codes are available as replacement modules.
  • Page 42: Specifications

    0.1 to 2.0  CT rating: ±0.75% of reading or ±2% of rated TD multiplier: 0.00 to 600.00 in steps of 0.01 (whichever is greater) Reset type: Instantaneous or Timed (per IEEE) 2-12 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 43: User-Programmable Elements

    Data: AC input channels; element state; con- Data storage: in non-volatile memory tact input state; contact output state GE Multilin B90 Low Impedance Bus Differential System 2-13...
  • Page 44: Metering

    Unreturned message alarm: Responding to: Rate of unreturned messages in the ring configuration Monitoring message count: 10 to 10000 in steps of 1 Alarm threshold: 1 to 1000 in steps of 1 2-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 45: Power Supply

    Operate time: < 0.6 ms FORM-A VOLTAGE MONITOR Internal Limiting Resistor: 100 , 2 W Applicable voltage: approx. 15 to 250 V DC Trickle current: approx. 1 to 2.5 mA GE Multilin B90 Low Impedance Bus Differential System 2-15...
  • Page 46: Communication Protocols

    Typical distance 2 km Duplex full/half Redundancy ETHERNET (10/100 MB TWISTED PAIR) Modes: 10 MB, 10/100 MB (auto-detect) Connector: RJ45 SIMPLE NETWORK TIME PROTOCOL (SNTP) clock synchronization error: <10 ms (typical) 2-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 47: Inter-Relay Communications

    – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days). GE Multilin B90 Low Impedance Bus Differential System 2-17...
  • Page 48: Type Tests

    IEC 60255-27 Insulation: class 1, Pollution degree: 2, Over voltage cat II 2.3.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. 2-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 49: Approvals

    To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. GE Multilin B90 Low Impedance Bus Differential System 2-19...
  • Page 50 2.3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2-20 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 51: Hardware

    3.1.1 PANEL CUTOUT The B90 Low Impedance Bus Differential System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 52 3.1 DESCRIPTION 3 HARDWARE Figure 3–2: B90 HORIZONTAL MOUNTING (ENHANCED PANEL) Figure 3–3: B90 HORIZONTAL MOUNTING AND DIMENSIONS (STANDARD PANEL) B90 Low Impedance Bus Differential System GE Multilin...
  • Page 53: Rear Terminal Layout

    (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. Figure 3–5: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin B90 Low Impedance Bus Differential System...
  • Page 54: Wiring

    3.2 WIRING 3 HARDWARE 3.2WIRING 3.2.1 TYPICAL WIRING Figure 3–6: B90 IS A MULTI-IED PROTECTION SYSTEM B90 Low Impedance Bus Differential System GE Multilin...
  • Page 55 The wiring diagrams on the next four pages are based on the following order code: B90-H02-HCL-F8H-H6H-L8H-N6A-S8H-U6H-W7H. The purpose of these diagrams is to provide examples of how the B90 is typically wired, not specifi- cally how to wire your own relay. See the sections following the wiring diagrams for examples on con- necting your relay correctly based on your relay configuration and order code.
  • Page 56 3.2 WIRING 3 HARDWARE Figure 3–7: TYPICAL WIRING DIAGRAM (PHASE A; T MODULE SHOWN FOR CPU) B90 Low Impedance Bus Differential System GE Multilin...
  • Page 57 3 HARDWARE 3.2 WIRING Figure 3–8: TYPICAL WIRING DIAGRAM (PHASE B; T MODULE SHOWN FOR CPU) GE Multilin B90 Low Impedance Bus Differential System...
  • Page 58 3.2 WIRING 3 HARDWARE Figure 3–9: TYPICAL WIRING DIAGRAM (PHASE C; T MODULE SHOWN FOR CPU) B90 Low Impedance Bus Differential System GE Multilin...
  • Page 59 3 HARDWARE 3.2 WIRING Figure 3–10: TYPICAL WIRING DIAGRAM (BREAKER FAIL AND ISOLATOR MONITORING; T MODULE SHOWN) GE Multilin B90 Low Impedance Bus Differential System...
  • Page 60: Dielectric Strength

    (see the Self-test Errors section in chapter 7) or control power is lost, the relay is de-energize. For high reliability systems, the B90 has a redundant option in which two B90 power supplies are placed in parallel on the bus.
  • Page 61: B90 Low Impedance Bus Differential System

    1 to 50000 A primaries and 1 A or 5 A secondaries may be used. Each B90 voltage input is intended for monitoring a single-phase voltage. The may include phase voltages or neutral volt- age from the open-delta VT.
  • Page 62: Contact Inputs And Outputs

    The terminal configuration for contact inputs is different for the two applications. The contact inputs are grouped with a common return. The B90 has two versions of grouping: four inputs per common return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
  • Page 63 Logic operand driving the contact output should be given a reset delay of 10 ms to prevent damage of the output contact (in situations when the element initiating the contact output is bouncing, at val- ues in the region of the pickup value). GE Multilin B90 Low Impedance Bus Differential System 3-13...
  • Page 64 ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 65 ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin B90 Low Impedance Bus Differential System 3-15...
  • Page 66 3.2 WIRING 3 HARDWARE Figure 3–14: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 67 3.2 WIRING Figure 3–15: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output con- nections. GE Multilin B90 Low Impedance Bus Differential System 3-17...
  • Page 68 Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. 3-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 69 = OFF CONTACT INPUT 1 AUTO-BURNISH = OFF CONTACT INPUT 2 AUTO-BURNISH = ON CONTACT INPUT 1 AUTO-BURNISH = ON CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–18: AUTO-BURNISH DIP SWITCHES GE Multilin B90 Low Impedance Bus Differential System 3-19...
  • Page 70 3.2 WIRING 3 HARDWARE The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto- burnish functionality using an oscilloscope. NOTE 3-20 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 71: Rs232 Faceplate Port

    3.2.6 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the B90 faceplate for programming with a computer. All that is required to use this interface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
  • Page 72 This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the B90 COM terminal (#3); others function cor- rectly only if the common wire is connected to the B90 COM terminal, but insulated from the shield.
  • Page 73 The fiber optic communication ports allow for fast and efficient communications between relays at 100 Mbps. Optical fiber can be connected to the relay supporting a wavelength of 1310 nm in multi-mode. GE Multilin B90 Low Impedance Bus Differential System 3-23...
  • Page 74: Irig-B

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the B90 operates an internal oscillator with 1 µs resolution and accuracy.
  • Page 75: Direct Input/Output Communications

    1 to channel 2 on UR2, the setting should be “Enabled” on UR2. This DIRECT I/O CHANNEL CROSSOVER forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1. GE Multilin B90 Low Impedance Bus Differential System 3-25...
  • Page 76: Fiber: Led And Eled Transmitters

    Order Code tables in Chapter 2. All of the fiber modules use ST type connectors. 3.3.2 FIBER: LED AND ELED TRANSMITTERS The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules. Figure 3–26: LED AND ELED FIBER MODULES 3-26 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 77: Fiber-Laser Transmitters

    Observing any fiber transmitter output can injure the eye. When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. GE Multilin B90 Low Impedance Bus Differential System 3-27...
  • Page 78: Interface

    Remove the module cover screw. Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. 3-28 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 79 Loop Timing Mode: The system clock is derived from the received line signal. Therefore, the G.703 timing selection should be in loop timing mode for connections to higher order systems. For connection to a higher order system (UR- GE Multilin B90 Low Impedance Bus Differential System 3-29...
  • Page 80 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–33: G.703 DUAL LOOPBACK MODE 3-30 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 81: Rs422 Interface

    If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. GE Multilin B90 Low Impedance Bus Differential System 3-31...
  • Page 82 Figure 3–36: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, THREE-TERMINAL APPLICATION Data module 1 provides timing to the B90 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they vary by manufacturer.
  • Page 83: Rs422 And Fiber Interface

    G.703 and fiber interfaces. When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. GE Multilin B90 Low Impedance Bus Differential System 3-33...
  • Page 84: Ieee C37.94 Interface

    Connection: as per all fiber optic connections, a Tx to Rx connection is required The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports the IEEE C37.94 standard shown as follows. 3-34 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 85 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. GE Multilin B90 Low Impedance Bus Differential System 3-35...
  • Page 86 Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow- ing figure. Figure 3–41: STATUS LEDS The clock configuration LED status is as follows: • Flashing green — loop timing mode while receiving a valid data packet 3-36 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 87 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid GE Multilin B90 Low Impedance Bus Differential System 3-37...
  • Page 88: C37.94Sm Interface

    For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured. 3-38 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 89 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. Figure 3–42: C37.94SM TIMING SELECTION SWITCH SETTING GE Multilin B90 Low Impedance Bus Differential System 3-39...
  • Page 90 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid 3-40 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 91: Human Interfaces

    In online mode, you can communicate with the device in real-time. The EnerVista UR Setup software is provided with every B90 relay and runs on Microsoft Windows XP, 7, and Server 2008. This chapter provides a summary of the basic EnerVista UR Setup software interface features. The EnerVista UR Setup Help File provides details for getting started and using the EnerVista UR Setup software interface.
  • Page 92 Site List window are automatically sent to the online communicating device. g) FIRMWARE UPGRADES The firmware of a B90 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
  • Page 93: Enervista Ur Setup Main Window

    Device data view windows, with common tool bar Settings file data view windows, with common tool bar Workspace area with data view tabs Status bar 10. Quick action hot links 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW GE Multilin B90 Low Impedance Bus Differential System...
  • Page 94: Extended Enervista Ur Setup Features

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 95 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 96 The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND B90 Low Impedance Bus Differential System GE Multilin...
  • Page 97 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 98: Securing And Locking Flexlogic Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic equation. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 99 FlexLogic entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 100: Settings File Traceability

    When a settings file is transferred to a B90 device, the date, time, and serial number of the B90 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the B90 actual values at any later date to determine if security has been compromised.
  • Page 101 4.2 EXTENDED ENERVISTA UR SETUP FEATURES The transfer date of a setting file written to a B90 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 102 ONLINE DEVICE TRACEABILITY INFORMATION The B90 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 103: Faceplate Interface

    The following figure shows the horizontal arrange- ment of the faceplate panels. Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS GE Multilin B90 Low Impedance Bus Differential System 4-13...
  • Page 104: Led Indicators

    CURRENT: This LED indicates current was involved. • FREQUENCY: This LED indicates frequency was involved. • OTHER: This LED indicates a composite function was involved. • PHASE A: Not used. • PHASE B: Not used. 4-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 105 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every B90, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 106 LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained in the following section. Figure 4–20: LED PANEL 2 (DEFAULT LABELS) 4-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 107: Custom Labeling Of Leds

    Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the B90 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
  • Page 108 Bend the tabs at the left end of the tool upwards as shown below. Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the B90 enhanced front panel and insert the custom labels.
  • Page 109 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the B90 enhanced front panel and insert the custom labels.
  • Page 110 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This attaches the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. 4-20 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 111 The panel templates provide relative LED locations and located example text (x) edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014). GE Multilin B90 Low Impedance Bus Differential System 4-21...
  • Page 112: Display

    Place the left side of the customized module back to the front panel frame, then snap back the right side. Put the clear Lexan front cover back into place. The following items are required to customize the B90 display module: •...
  • Page 113: Menus

    MESSAGE LEFT key from a setting value or actual value display returns to the header display. HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE)  SETTINGS  SECURITY ACCESS LEVEL:  PRODUCT SETUP  Restricted  SETTINGS  SYSTEM SETUP GE Multilin B90 Low Impedance Bus Differential System 4-23...
  • Page 114: Changing Settings

    The VALUE DOWN key decrements the displayed value by the step value, down to the minimum value. While at the minimum value, pressing the VALUE DOWN key again allows the setting selection to continue downward from the maximum value. 4-24 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 115 Press the MENU key until the header flashes momentarily and the message appears on the SETTINGS PRODUCT SETUP display. Press the MESSAGE RIGHT key until the message appears on the display. SECURITY GE Multilin B90 Low Impedance Bus Differential System 4-25...
  • Page 116 Settings > Product Setup > Security > CyberSentry section in the next chapter. The B90 supports password entry from a local or remote connection. Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the faceplate RS232 connection.
  • Page 117 FlexLogic operand is set to “On” and the REMOTE ACCESS DENIED B90 does not allow Settings or Command access via the any external communications interface for the next ten minutes. FlexLogic operand is set to “Off” after the expiration of the ten-minute timeout.
  • Page 118 4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4-28 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 119: Overview

      SETTINGS  AC INPUTS See page 5-89.  SYSTEM SETUP   POWER SYSTEM See page 5-90.   FLEXCURVES See page 5-91.   BUS See page 5-98.  GE Multilin B90 Low Impedance Bus Differential System...
  • Page 120 See page 5-151.   VIRTUAL OUTPUTS See page 5-153.   REMOTE DEVICES See page 5-154.   REMOTE INPUTS See page 5-155.   REMOTE DPS INPUTS See page 5-156.  B90 Low Impedance Bus Differential System GE Multilin...
  • Page 121: Introduction To Elements

    Where the current source is from a single CT, the base quantity is the nominal secondary or primary current of the CT. Use the secondary current base to convert per-unit current settings to/from a secondary current value, and use the primary cur- rent base to convert to/from a primary current value. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 122 The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to the dropout state (logic 0). This could happen when the element is in the operate state if the reset delay time is not 0. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 123: Product Setup

    (both protection B90 FUNCTION and logic), download the same file to all the B90 IEDs, and modify the settings accordingly to finalize the application. Com- munications and settings are typically modified when downloading the common B90 setting file.
  • Page 124 When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the B90, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 125 When an original password has already been used, enter it in the Enter Password field and click the Send Password to Device button. Re-enter the password in the Confirm Password field. Click the OK button. The password is checked to ensure that is meets requirements. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 126 INVALID ATTEMPTS BEFORE LOCKOUT The B90 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 127 The status of this timer is updated every 5 seconds. The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product Setup > Security menu item to display the security settings window. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 128 Select the Security > User Management menu item to open the user management window. Enter a username in the User field. The username must be 4 to 20 characters in length. 5-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 129 The EnerVista security management system must be enabled To modify user privileges: Select the Security > User Management menu item to open the user management window. Locate the username in the User field. GE Multilin B90 Low Impedance Bus Differential System 5-11...
  • Page 130 Access to various functionality depends on user role. The login screen of EnerVista has two options for access to the UR, server and device authentication. Figure 5–1: LOGIN SCREEN FOR CYBERSENTRY 5-12 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 131 But if Modbus is disabled, port 502 is closed. This function has been tested and no unused ports have been found NOTE open. CYBERSENTRY SETTINGS THROUGH ENERVISTA CyberSentry security settings are configured under Device > Settings > Product Setup > Security. Figure 5–2: CYBERSENTRY SECURITY PANEL GE Multilin B90 Low Impedance Bus Differential System 5-13...
  • Page 132 Authentication method used by RADIUS EAP-TTLS EAP-TTLS EAP-TTLS Administrator Authentication server. Currently fixed to EAP-TTLS. Method Timeout Timeout in seconds between re- 9999 Administrator transmission requests Retries Number of retries before giving up 9999 Administrator 5-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 133 Change Text The specified role password-protected. All RADIUS users are Password following Me1# and Administrator, password-protected. Requirement password except for s section section for Supervisor, where requireme it is only itself GE Multilin B90 Low Impedance Bus Differential System 5-15...
  • Page 134 This role can also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role. 5-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 135 LOAD FACTORY DEFAULTS: This setting is used to reset all the settings, communication and security passwords. An Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it. GE Multilin B90 Low Impedance Bus Differential System 5-17...
  • Page 136 FACTORY SERVICE MODE: When enabled (meaning "Yes" is selected) the device can go into factory service mode. For this setting to become enabled a Supervisor authentication is necessary. The default value is Disabled. 5-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 137 The use of CyberSentry for devices communicating through an Ethernet-to-RS485 gateway is not supported. Because these gateways do not support the secure protocols necessary to communicate with such devices, the connection cannot be established. Use the device as a non-CyberSentry device. GE Multilin B90 Low Impedance Bus Differential System 5-19...
  • Page 138 Username — 255 chars maximum, but in the security log it is truncated to 20 characters IP address — Device IP address Role — 16 bit unsigned, of type format F617 ENUMERATION ROLE None Administrator Supervisor Engineer Operator Factory 5-20 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 139: Display Properties

    DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough during programming or reading of actual values. GE Multilin B90 Low Impedance Bus Differential System 5-21...
  • Page 140: Clear Relay Records

    Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The B90 applies a cut- off value to the magnitudes and angles of the measured currents.
  • Page 141: Communications

    MESSAGE MIN TIME: 0 ms : The B90 is equipped with two independent serial communication ports. The faceplate RS485 COM2 BAUD RATE PARITY RS232 port is intended for local use and is fixed at 19200 bit/s baud and even parity. The rear COM2 port is RS485 and has settings for baud rate and parity.
  • Page 142 ETHERNET NETWORK TOPOLOGY The B90 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND oper- ation performed between their respective IP address and mask produces a different result.
  • Page 143 In this configuration, P3 uses the IP and MAC address of P2. Figure 5–5: MULTIPLE LANS, WITH REDUNDANCY Public Network SCADA EnerVista Software LAN1 LAN2 LAN2 ML3000 ML3000 ML3000 IP1/ IP2/ IP2/ MAC2 MAC2 MAC1 Redundancy mode 859709A4.vsd GE Multilin B90 Low Impedance Bus Differential System 5-25...
  • Page 144 Range: None, Failover, PRP PRT2 REDUNDANCY: MESSAGE None, Failover (if no PRP license) None Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF PRT2 PRP MCST ADDR: MESSAGE 01-15-4E-00-01-00 Range: Enabled, Disabled PRT2 GOOSE ENABLED: MESSAGE Enabled 5-26 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 145 2 is performed. The delay in switching back ensures that rebooted switching devices connected to the B90, which signal their ports as active prior to being completely functional, have time to completely initialize themselves and become active. Once port 2 is active again, port 3 returns to standby mode.
  • Page 146 The UR relays support only PRP-1. The relay implements PRP on two of its Ethernet ports, specifically Port 2 and 3 of the CPU module. Use the previous sec- tion (network port configuration) to configure PRP. 5-28 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 147 2 of the General Conditions to be Satisfied by Static Routes. To delete a route: Replace the route destination with the default loopback address (127.0.0.1). When deleting a route, the mask and gateway must be also brought back to default values. GE Multilin B90 Low Impedance Bus Differential System 5-29...
  • Page 148 Port 1 (IP address 10.1.1.2) connects the UR to LAN 10.1.1.0/24 and to the Internet through Router1. Router 1 has an interface on 10.1.1.0/24 and the IP address of this interface is 10.1.1.1. 5-30 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 149 Age, in minutes, of the cache entry. A hyphen (-) means the address is local. Hardware Address LAN hardware address, a MAC address that corresponds to network address Type Dynamic or Static Interface Interface to which this address mapping has been assigned GE Multilin B90 Low Impedance Bus Differential System 5-31...
  • Page 150 This allows the EnerVista UR Setup software to be used on the port. The UR operates as a Modbus slave device only. When using Modbus protocol on the RS232 port, the B90 responds regardless of the pro- MODBUS SLAVE ADDRESS grammed.
  • Page 151 TIMEOUT: 5 s Range: 1 to 255 in steps of 1 DNP UNSOL RESPONSE MESSAGE MAX RETRIES: 10 Range: 0 to 65519 in steps of 1 DNP UNSOL RESPONSE MESSAGE DEST ADDRESS: 1 GE Multilin B90 Low Impedance Bus Differential System 5-33...
  • Page 152 MESSAGE DEFAULT VARIATION: 2 Range: 1, 2, 3, 4, 5 DNP OBJECT 30 MESSAGE DEFAULT VARIATION: 1 Range: 1, 2, 3, 4, 5, 7 DNP OBJECT 32 MESSAGE DEFAULT VARIATION: 1 5-34 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 153 DNP slave should be assigned a unique address. The B90 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which the B90 can connect. The settings in this sub-menu are shown below.
  • Page 154 DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the B90 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
  • Page 155 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored. NOTE Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the B90 is restarted. NOTE GE Multilin...
  • Page 156 The B90 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over Ethernet. The B90 operates as an IEC 61850 server. The Remote Inputs and Out- puts section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
  • Page 157 IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In B90 releases previous to 5.0x, this name string was repre- sented by the setting.
  • Page 158 DESTINATION MAC address; the least significant bit of the first byte must be set. In B90 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the B90) and setting the multicast bit.
  • Page 159 The B90 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 160 Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. 5-42 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 161 MMXU1 HZ DEADBAND change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency. The B90 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the ...
  • Page 162 IEC61850 GOOSE ANALOG INPUT 1 UNITS The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The B90 must be rebooted (control power removed and re-applied) before these settings take effect.
  • Page 163 DNA and UserSt bit pairs that are included in GSSE messages. To set up a B90 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and “GGIO3.ST.Ind2.stVal”.
  • Page 164 CPU resources. When server scanning is disabled, there is no updating of the IEC 61850 logical node status values in the B90. Clients are still able to connect to the server (B90 relay), but most data values are not updated. This set- ting does not affect GOOSE/GSSE operation.
  • Page 165 Changes to the logical node prefixes will not take effect until the B90 is restarted. The main menu for the IEC 61850 MMXU deadbands is shown below. The IEC 61850 MMXU deadband settings cannot be used with the B90 Low Impedance Bus Differential System. NOTE ...
  • Page 166 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the B90 virtual inputs.
  • Page 167 GGIO1 (binary status values). The settings allow the selection of FlexInteger values for each GGIO5 integer value point. It is intended that clients use GGIO5 to access generic integer values from the B90. Additional settings are provided to allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger values to the GGIO5 integer inputs.
  • Page 168 Menu”. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the UR and a computer to an Ethernet network, then enter the IP address of the B90 Ethernet port employed into the “Address”...
  • Page 169 PROTOCOL connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the B90 maintains two sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the B90 at one time.
  • Page 170 MESSAGE 0.0.0.0 The B90 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to which the B90 can connect. A maximum of two simultaneous connections are supported at any given time.
  • Page 171 Spontaneous transmission occurs as a response to cyclic Class 2 requests. If the B90 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the con- trol field of the response).
  • Page 172  IEC103 INPUTS   MEASURANDS Range: see sub-menu below  ASDU 2 MESSAGE  Range: see sub-menu below  ASDU 3 MESSAGE  Range: see sub-menu below  ASDU 4 MESSAGE  5-54 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 173 MESSAGE Range: 0.000 to 65.535 in steps of 0.001 ASDU 4 ANALOG 9 MESSAGE FACTOR: 1.000 Range: -32768 to 32767 in steps of 1 ASDU 4 ANALOG 9 MESSAGE OFFSET: 0 GE Multilin B90 Low Impedance Bus Differential System 5-55...
  • Page 174 FlexAnalog operands. The measurands sent are voltage, current, power, power fac- tor, and frequency. If any other FlexAnalog is chosen, the B90 sends 0 instead of its value. Note that the power is transmit- ted in KW, not W.
  • Page 175 ASDU command comes. A list of available mappings is provided on the B90. This includes 64 virtual inputs (see the following table). The ON and OFF for the same ASDU command can be mapped to different virtual inputs.
  • Page 176: Modbus User Map

    A setting of None causes the RTC and the syn- chrophasor clock to free-run. A setting of PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/SNTP, or PP/PTP/IRIG-B/SNTP causes 5-58 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 177 1 ns, but this requires each and every component in the network achieve very high levels of accuracy and a very high baud rate, faster than normally used for relay communications. When operating over a generic Ethernet net- GE Multilin B90 Low Impedance Bus Differential System 5-59...
  • Page 178 PORT 1 ... 3 FUNCTION • While this port setting is selected to disabled, PTP is disabled on this port. The relay does not generate or listen to PTP messages on this port. 5-60 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 179 The B90 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the B90 can obtain clock time over an Ethernet network. The B90 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded- icated product using a GPS receiver to provide an accurate time.
  • Page 180 DAYLIGHT SAVINGS TIME (DST) Note that when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and so the DST settings are ignored. 5-62 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 181: User-Programmable Fault Report

    The user programmable record contains the following information: the user-programmed relay name, detailed firmware revision (7.2x, for example) and relay model (B90), the date and time of trigger, the name of pre-fault trigger (a specific FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger), and fault values of all programmed analog channels (at the fault trigger).
  • Page 182: Oscillography

    64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. When changes are made to the oscillography settings, all existing oscillography records will be CLEARED. NOTE 5-64 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 183 - entering this number via the relay keypad will cause the corresponding parameter to be displayed. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. GE Multilin B90 Low Impedance Bus Differential System 5-65...
  • Page 184: User-Programmable Leds

    The test responds to the position and rising edges of the control input defined by the set- LED TEST CONTROL ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. 5-66 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 185 2. Once stage 2 has started, the pushbutton can be released. When stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton. GE Multilin B90 Low Impedance Bus Differential System 5-67...
  • Page 186 LED 19 operand LED 8 operand LED 20 operand LED 9 operand LED 21 operand LED 10 operand LED 22 operand LED 11 operand LED 23 operand LED 12 operand LED 24 operand 5-68 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 187: User-Programmable Self Tests

    There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front panels. These are user-programmable and can be used for various applications such as performing an LED test, switching setting groups, and invoking and scrolling though user-programmable displays. GE Multilin B90 Low Impedance Bus Differential System 5-69...
  • Page 188 The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–10: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the B90 is ordered with the 12 user- programmable pushbutton option. STATUS EVENT CAUSE...
  • Page 189 BREAKERS/BREAKER 1/ BREAKER 1 PUSHBUTTON CONTROL Enabled=1 TIMER FLEXLOGIC OPERAND SYSTEM SETUP/ BREAKERS/BREAKER 2/ CONTROL PUSHBTN 1 ON 100 msec BREAKER 2 PUSHBUTTON CONTROL 842010A2.CDR Enabled=1 Figure 5–12: CONTROL PUSHBUTTON LOGIC GE Multilin B90 Low Impedance Bus Differential System 5-71...
  • Page 190: User-Programmable Pushbuttons

    FlexLogic equations, protection elements, and control elements. Typical applications include breaker control, autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of password protection. The user-configurable pushbuttons for the enhanced faceplate are shown below. 5-72 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 191 The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push- button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari- ous system disturbances that may cause transient assertion of the operating signals. NOTE GE Multilin B90 Low Impedance Bus Differential System 5-73...
  • Page 192 PUSHBTN 1 RESET • PUSHBTN 1 LOCAL: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset. 5-74 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 193 “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. GE Multilin B90 Low Impedance Bus Differential System 5-75...
  • Page 194 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–15: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) 5-76 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 195 User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via EnerVista UR Setup with the Maintenance > Enable Pushbutton command. NOTE GE Multilin B90 Low Impedance Bus Differential System 5-77...
  • Page 196: Flex State Parameters

    USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL setting. Any FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate the programmed displays. 5-78 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 197 (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this conversion). GE Multilin B90 Low Impedance Bus Differential System 5-79...
  • Page 198 If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different. NOTE 5-80 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 199: Direct Inputs And Outputs

    “Yes”), all direct output messages should be received back. If not, the direct input/output ring CH2 RING CONFIGURATION break self-test is triggered. The self-test error is signaled by the FlexLogic operand. DIRECT RING BREAK GE Multilin B90 Low Impedance Bus Differential System 5-81...
  • Page 200 64 kbps Channel 1 64 kbps Channel 2 64 kbps The G.703 modules are fixed at 64 kbps. The setting is not applicable to these modules. DIRECT I/O DATA RATE NOTE 5-82 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 201 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–18: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. GE Multilin B90 Low Impedance Bus Differential System 5-83...
  • Page 202 The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. 5-84 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 203 Inputs and Outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This is accomplished using a dual-ring configuration as shown here. GE Multilin B90 Low Impedance Bus Differential System 5-85...
  • Page 204 EVENTS: Disabled The B90 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 205 MESSAGE EVENTS: Disabled The B90 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre- turned messages.
  • Page 206: Installation

    "Programmed" state. UNIT NOT PROGRAMMED setting allows the user to uniquely identify a relay. This name will appear on generated reports. RELAY NAME 5-88 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 207: System Setup

    CT F1 SECONDARY: MESSAGE This menu configures the AC current inputs. Upon power up, the B90 recognizes all the AC modules loaded in its chassis and populates the above menu accordingly. The current terminals are denoted in the following format: Xa, where X = {F, L, S} and a = (1, 2,..., 8}. X represents the chassis slot containing the AC input module and a represents the AC channel of each module.
  • Page 208: Power System

    UR-series relays provided the relays have an IRIG-B connection. should only be set to "Disabled" in very unusual circumstances; consult the factory for spe- FREQUENCY TRACKING cial variable-frequency applications. NOTE 5-90 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 209: Flexcurves

    1.03 pu. It is recommended to set the two times to a similar value; otherwise, the linear approximation may result in NOTE undesired behavior for the operating quantity that is close to 1.00 pu. GE Multilin B90 Low Impedance Bus Differential System 5-91...
  • Page 210: B90 Low Impedance Bus Differential System Ge Multilin

    The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE 5-92 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 211 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the B90 are displayed in the following graphs. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 212 Figure 5–26: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–27: RECLOSER CURVES GE113, GE120, GE138 AND GE142 5-94 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 213 Figure 5–28: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–29: RECLOSER CURVES GE131, GE141, GE152, AND GE200 GE Multilin B90 Low Impedance Bus Differential System 5-95...
  • Page 214 Figure 5–30: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–31: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 5-96 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 215 Figure 5–32: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–33: RECLOSER CURVES GE119, GE135, AND GE202 GE Multilin B90 Low Impedance Bus Differential System 5-97...
  • Page 216: Bus

    Please refer to the Ordering section in chapter 2 for detailed infor- mation on the maximum number of zones and inputs for a given B90 model. Four bus differential zones are available. Each zone is associated with its own bus differential protection and CT trouble monitoring elements.
  • Page 217 5 SETTINGS 5.3 SYSTEM SETUP For example, assume that B90 IED 4 is used for isolator monitoring while IEDs 1, 2, and 3 are used for protection. Conse- quently, the setting of IED 4 must be set to “Logic” while...
  • Page 218: Flexlogic

    Figure 5–36: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the B90 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an ele- ment from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.
  • Page 219 Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–12: B90 FLEXLOGIC OPERAND TYPES OPERAND TYPE STATE...
  • Page 220 5.4 FLEXLOGIC 5 SETTINGS The operands available for this relay are listed alphabetically by types in the following table. Table 5–13: B90 FLEXLOGIC OPERANDS (Sheet 1 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed...
  • Page 221 5 SETTINGS 5.4 FLEXLOGIC Table 5–13: B90 FLEXLOGIC OPERANDS (Sheet 2 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT LATCH 1 ON Non-volatile latch 1 is ON (Logic = 1) Non-volatile latches LATCH 1 OFF Non-volatile latch 1 is OFF (Logic = 0)
  • Page 222 5.4 FLEXLOGIC 5 SETTINGS Table 5–13: B90 FLEXLOGIC OPERANDS (Sheet 3 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION INPUTS/OUTPUTS: REMOTE INPUT 1 On Flag is set, logic=1 Remote inputs REMOTE INPUT 2 On Flag is set, logic=1 REMOTE INPUT 3 On Flag is set, logic=1 ...
  • Page 223 5 SETTINGS 5.4 FLEXLOGIC Table 5–13: B90 FLEXLOGIC OPERANDS (Sheet 4 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION SELF- ANY MAJOR ERROR Any of the major self-test errors generated (major error) DIAGNOSTICS ANY MINOR ERROR Any of the minor self-test errors generated (minor error)
  • Page 224: Flexlogic Rules

    When making changes to settings, all FlexLogic equations are re-compiled whenever any new setting value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic during testing, for example, it is suggested to power the unit down and then back up. 5-106 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 225: Flexlogic Example

    Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–38: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS GE Multilin B90 Low Impedance Bus Differential System 5-107...
  • Page 226 Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." 5-108 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 227 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". GE Multilin B90 Low Impedance Bus Differential System 5-109...
  • Page 228 In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) 5-110 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 229: Flexlogic Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". GE Multilin B90 Low Impedance Bus Differential System 5-111...
  • Page 230: Non-Volatile Latches

    LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–44: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC 5-112 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 231: Grouped Elements

    Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if no other group is active (see Section 5.6.3: Setting Groups on page 5–139 for further details). GE Multilin B90 Low Impedance Bus Differential System 5-113...
  • Page 232: Bus Differential

    The biased bus differential function has a dual-slope operating characteristic (see figure below) operating in conjunction with saturation detection and a directional comparison principle (see the Bus zone 1 differential scheme logic figure in this section). 5-114 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 233 CTs operating in their linear mode, i.e. in load conditions and during distant external faults. When adjusting this setting, it must be kept in mind that the restraining signal used by the biased bus differential protection element is created as the maximum of all the input currents. GE Multilin B90 Low Impedance Bus Differential System 5-115...
  • Page 234 BF function to isolate the entire zone of busbar protection. More information on the bus zone differential settings can be found in the Application of Settings chapter. 5-116 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 235 5 SETTINGS 5.5 GROUPED ELEMENTS Figure 5–46: BUS ZONE 1 DIFFERENTIAL SCHEME LOGIC GE Multilin B90 Low Impedance Bus Differential System 5-117...
  • Page 236 Range: Yes, No BF1 USE TIMER 2: MESSAGE Range: 0.000 to 65.535 s in steps of 0.001 BF1 TIMER 2 PICKUP MESSAGE DELAY: 0.000 s Range: Yes, No BF1 USE TIMER 3: MESSAGE 5-118 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 237 Range: Enabled, Disabled BF1 EVENTS: MESSAGE Disabled  BREAKER FAILURE  CURRENT SUPV 2  BREAKER FAILURE 2    BREAKER FAILURE  CURRENT SUPV 24  BREAKER FAILURE 24  GE Multilin B90 Low Impedance Bus Differential System 5-119...
  • Page 238 PRODUCT SETUP B90 FUNCTION setting is “Logic”. The Breaker failure element requires B90 fiber optic interconnection and proper configura- B90 FUNCTION tion of the breaker failure and direct input/output settings. Refer to the Application of settings chapter for additional details.
  • Page 239 BF1 USE SEAL-IN: If set to "Yes", the element will only be sealed-in if current flowing through the breaker is above the supervision pickup level. • BF1 AMP SUPV OP A through C: This setting selects the B90 Remote Inputs that represent operation of the current supervision elements on phase A, B, or C. •...
  • Page 240 BF1 AMP LOSET PICKUP: This setting is used to set the phase current fault detection level. Generally this setting should detect the lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted approximately 90% of resistor current). Figure 5–47: BREAKER FAILURE CURRENT SUPERVISION LOGIC 5-122 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 241 5 SETTINGS 5.5 GROUPED ELEMENTS Figure 5–48: BREAKER FAILURE LOGIC GE Multilin B90 Low Impedance Bus Differential System 5-123...
  • Page 242 DIRECT INPUT 6 BIT NUMBER : "3" (message received from IED 3) DIRECT INPUT 7 DEVICE : "13" (this is BKRSUPV 3 SUPV OP for Phase C) DIRECT INPUT 7 BIT NUMBER 5-124 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 243 BF 3 AMP LOSET OP C The B90 current supervision elements reset in less than 0.7 of a power cycle up to the multiple of pickup of 100 (threshold set at 0.01 of the actual fault current) as shown below.
  • Page 244 The undervoltage element supervises (low-voltage check) current based main protection (that is, differential, breaker fail- ure, end fault, and time overcurrent backup protection). The B90 accepts phase-to-ground or phase-to-phase voltage input configurations. If the intention is to operate all three phases for any one phase voltage collapse, appropriate FlexLogic™...
  • Page 245 See page 5-132. MESSAGE  OVERCURRENT 24  TIME See page 5-133. MESSAGE  OVERCURRENT  TIME See page 5-133. MESSAGE  OVERCURRENT   TIME See page 5-133. MESSAGE  OVERCURRENT 24 GE Multilin B90 Low Impedance Bus Differential System 5-127...
  • Page 246 12.010 7.780 5.564 4.255 3.416 2.845 2.439 181.454 76.174 29.174 16.014 10.374 7.419 5.674 4.555 3.794 3.252 10.0 226.817 95.217 36.467 20.017 12.967 9.274 7.092 5.693 4.742 4.065 IEEE VERY INVERSE 5-128 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 247 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 GE Multilin B90 Low Impedance Bus Differential System 5-129...
  • Page 248 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 5-130 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 249 0.859 0.569 0.419 0.368 0.341 0.325 0.314 0.307 0.301 0.296 1.145 0.759 0.559 0.490 0.455 0.434 0.419 0.409 0.401 0.394 10.0 1.431 0.948 0.699 0.613 0.569 0.542 0.524 0.511 0.501 0.493 GE Multilin B90 Low Impedance Bus Differential System 5-131...
  • Page 250 Range: 0.000 to 65.535 s in steps of 0.001 IOC1 RESET DELAY: MESSAGE 0.000 s Range: FlexLogic operand IOC1 BLOCK: MESSAGE Range: Self-Reset, Latched, Disabled IOC1 TARGET: MESSAGE Self-Reset Range: Enabled, Disabled IOC1 EVENTS: MESSAGE Disabled 5-132 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 251 FlexLogic operands are passed between the IEDs using the B90 fiber optic communications (Direct I/Os). Instantaneous Overcurrent supervision can also be used to prevent tripping feeders with low currents or for definite time backup protection.
  • Page 252 The End Fault Protection (EFP) element operates for dead-zone faults; i.e., faults between the CT and an open feeder breaker. Since a bus protection zone terminates on the CTs, faults between the CT and breaker require special consider- ation. 5-134 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 253 • EFP1 BREAKER OPEN: This setting is a FlexLogic operand indicating an open breaker. The operand shall be "On" when the breaker is open. Typically, this setting is a position of an appropriately wired input contact of the B90. •...
  • Page 254 Off = 0 EFP 1 OP SETTINGS EFP 1 DPO SETTING EFP 1 BRK DELAY: EFP PKP EFP 1 BREAKER OPEN: Off = 0 836004A1.vsd Figure 5–56: END FAULT PROTECTION LOGIC 5-136 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 255: Control Elements

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. GE Multilin B90 Low Impedance Bus Differential System 5-137...
  • Page 256 TRIP BUS 1 RESET: The trip bus output is reset when the operand assigned to this setting is asserted. Note that the operand is pre-wired to the reset gate of the latch, As such, a reset command the front panel interface or via RESET OP communications will reset the trip bus output. 5-138 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 257: Setting Groups

    GROUP 1 NAME: MESSAGE Range: up to 16 alphanumeric characters GROUP 2 NAME: MESSAGE  Range: up to 16 alphanumeric characters GROUP 6 NAME: MESSAGE Range: Disabled, Enabled SETTING GROUP MESSAGE EVENTS: Disabled GE Multilin B90 Low Impedance Bus Differential System 5-139...
  • Page 258 SETTING GROUP 1 NAME SETTING GROUP 6 NAME groups. Once programmed, this name appears on the second line of the  menu GROUPED ELEMENTS SETTING GROUP 1(6) display. 5-140 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 259: Digital Elements

    DIGITAL ELEMENT 01 INPUT: DIG ELEM 01 PKP Off = 0 DIG ELEM 01 OP INPUT = 1 SETTING DIGITAL ELEMENT 01 BLOCK: 827042A2.VSD Off = 0 Figure 5–59: DIGITAL ELEMENT SCHEME LOGIC GE Multilin B90 Low Impedance Bus Differential System 5-141...
  • Page 260 Using the contact input settings, this input will be given an ID name, for example, “Cont Ip 1", and will be set “On” when the breaker is closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated below (EnerVista UR Setup example shown): 5-142 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 261 “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). Figure 5–61: TRIP CIRCUIT EXAMPLE 2 The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and solid-state contact with voltage monitoring. NOTE GE Multilin B90 Low Impedance Bus Differential System 5-143...
  • Page 262: Monitoring Elements

    CT Trouble is declared for the given phase by setting the appropriate FlexLogic output operand. The operand may be configured to raise an alarm and block the bus differential function for the corresponding zone of protection. 5-144 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 263 EVENTS: Disabled Bus protection zone discrimination depends heavily on reliable isolator position feedback. Therefore, two isolator auxiliary contacts – normally open and normally closed – must confirm the status of the isolator via the B90 contact inputs. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 264 ISOLATOR 1 ALARM DELAY: This setting specifies a time delay after which an isolator alarm is issued by asserting the operand assigned to . The delay shall be longer than the slowest operation (transition) time of ISOLATOR 1 ALARM the isolator. 5-146 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 265 ISOLATOR 1 BLOCK delay isolator position valid alarm ISOLATOR 1 ALARM acknowledged alarm acknowledging ISOLATOR 1 RESET signal 836744A1.vsd Figure 5–65: ISOLATOR MONITORING SAMPLE TIMING DIAGRAM GE Multilin B90 Low Impedance Bus Differential System 5-147...
  • Page 266: Inputs/Outputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the B90 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 267 "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. GE Multilin B90 Low Impedance Bus Differential System 5-149...
  • Page 268: Virtual Inputs

    FlexLogic equation, it will likely have to be lengthened NOTE in time. A FlexLogic timer with a delayed reset can perform this function. Figure 5–67: VIRTUAL INPUTS SCHEME LOGIC 5-150 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 269: Contact Outputs

    The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the B90 using the FlexLogic operand to seal-in the contact output as follows: CONT OP 1 ION “Cont Op 1"...
  • Page 270 5 SETTINGS The B90 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop- ulates the setting menu accordingly.
  • Page 271: Virtual Outputs

    Logic equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings would be programmed as follows: GE Multilin B90 Low Impedance Bus Differential System 5-153...
  • Page 272: Remote Devices

    The remote input/output facility provides for 32 remote inputs and 64 remote outputs. b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE/GOOSE MESSAGES In a B90 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the ...
  • Page 273: Remote Inputs

    This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre- sponding settings on the sending device. setting provides for the choice of the B90 fixed (DNA/UserSt) dataset (that is, containing REMOTE DEVICE 1 DATASET DNA and UserSt bit pairs), or one of the configurable datasets.
  • Page 274: Remote Double-Point Status Inputs

    REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUTPUTS DNA- 1(32) BIT PAIR Range: FlexLogic operand  REMOTE OUTPUTS DNA- 1 OPERAND:  DNA- 1 BIT PAIR Range: Disabled, Enabled DNA- 1 EVENTS: MESSAGE Disabled 5-156 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 275: Resetting

    The setting RESET OP (PUSHBUTTON) RESET OP (COMMS) RESET OP (OPERAND) shown above selects the operand that will create the operand. RESET OP (OPERAND) GE Multilin B90 Low Impedance Bus Differential System 5-157...
  • Page 276: Direct Inputs And Outputs

    APPLICATION EXAMPLES The examples introduced in the earlier Direct Inputs and Outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. 5-158 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 277 5 SETTINGS 5.7 INPUTS/OUTPUTS EXAMPLE 1: EXTENDING INPUT/OUTPUT CAPABILITIES OF A B90 RELAY Consider an application that requires additional quantities of contact inputs or output contacts or lines of programmable logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements.
  • Page 278 DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: 5-160 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 279: Iec 61850 Goose Analogs

    The following text must be used in the UNITS setting, to represent these types of analogs: A, V, W, var, VA, Hz, deg, and no text (blank setting) for power factor. GE Multilin B90 Low Impedance Bus Differential System 5-161...
  • Page 280: Iec 61850 Goose Integers

    GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log values in other B90 features, such as FlexElements. The base factor is applied to the GOOSE analog input FlexAn- alog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
  • Page 281: Testing

    TEST MODE FORCING: MESSAGE The B90 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
  • Page 282: Force Contact Inputs

    Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a B90 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
  • Page 283: Force Contact Outputs

    PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin B90 Low Impedance Bus Differential System 5-165...
  • Page 284 5.8 TESTING 5 SETTINGS 5-166 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 285: Actual Values

    See page 6-9.  METERING   CURRENTS See page 6-9.   VOLTAGES See page 6-10.   FREQUENCY See page 6-10.   IEC 61850 See page 6-10.  GOOSE ANALOGS GE Multilin B90 Low Impedance Bus Differential System...
  • Page 286  EVENT RECORDS See page 6-11.   OSCILLOGRAPHY See page 6-11.   ACTUAL VALUES  MODEL INFORMATION See page 6-12.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-12.  B90 Low Impedance Bus Differential System GE Multilin...
  • Page 287: Contact Inputs

    For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of the display indicates the logic state of the contact output. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 288: Virtual Outputs

    STATUS: Fail Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: Fail Range: Fail, OK ETHERNET TRD LINK MESSAGE STATUS: Fail These values indicate the status of the first, second, and third Ethernet links. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 289: Real Time Clock Synchronizing

    PTP-— IRIG-B DELTA being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-B time. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 290: Direct Inputs

    STATUS: Offline Range: Offline, Online DIRECT DEVICE 2 MESSAGE STATUS: Offline  Range: Offline, Online DIRECT DEVICE 16 MESSAGE STATUS: Offline These actual values represent the state of direct devices 1 through 16. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 291: Remaining Connection Status

    N60 is 4. The maximum number for the C60 is 2. The maximum number is 1 for other products with a PMU. The remaining number of aggregators displays here. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 292: Metering

    Mismatches Port B: MESSAGE The B90 Low Impedance Bus Differential System is provided with optional PRP capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
  • Page 293: Bus Zone

    (see chapter 8: Theory of operation for additional details). There is no cutoff level applied to the differential and restraint currents computed by the B90. Therefore, a small dif- ferential current reflecting CT inaccuracies and bus leakage current could be present during balanced conditions.
  • Page 294: Voltages

    MESSAGE 0.000 The B90 Low Impedance Bus Differential System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. See the Order Codes sec- tion of chapter 2 for details.
  • Page 295: Records

    A trigger can be forced here at any time by setting “Yes” to the command. Refer to the  FORCE TRIGGER? COMMANDS menu for information on clearing the oscillography records. CLEAR RECORDS GE Multilin B90 Low Impedance Bus Differential System 6-11...
  • Page 296: Product Information

    Date and time when the boot program was built. 2012/09/15 16:41:32 The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. 6-12 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 297: Commands And

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin B90 Low Impedance Bus Differential System...
  • Page 298 When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time is over-written. The timescale of the entered time is local time, including daylight savings time where and when applicable. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 299: Relay Maintenance

    Various self-checking diagnostics are performed in the background while the B90 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the B90 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.
  • Page 300: Security

    Operator Logoff: Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session. • Clear Security Data: Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the operands associated with the self-tests. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 301: Targets Menu

     MESSAGE Each B90 element with a TARGET setting has a target message that when activated by its element is displayed in sequence with any other currently active target messages in the menu. In the example shown, the Phase TOC4 TARGETS and Digital Element 48 target settings are active and so have their targets displayed.
  • Page 302 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the B90 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
  • Page 303 • What to do: Verify that all the items in the GOOSE data set are supported by the B90. The EnerVista UR Setup soft- ware will list the valid items. An IEC61850 client will also show which nodes are available for the B90.
  • Page 304 How often the test is performed: Upon scanning of each configurable GOOSE data set. • What to do: The “xxx” text denotes the data item that has been detected as oscillating. Evaluate all logic pertaining to this item. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 305 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the B90 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 306 For example, if all three SFP modules fail, then the third SFP target is activated. If the third SFP module failure resolves, then the second SFP target is activated. 7-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 307: Theory Of Operation

    8 THEORY OF OPERATION 8.1INTRODUCTION 8.1.1 BUS DIFFERENTIAL PROTECTION Referring to the figure below, input currents defining (through the dynamic bus replica) the bus differential zone are received by the B90 from current transformers (CTs) associated with the power system. Measuring Unit Unbiased Differential...
  • Page 308: Dynamic Bus Replica Mechanism

    8.2.1 DYNAMIC BUS REPLICA MECHANISM The bus differential zones of the B90 allow for protecting bus sections that include circuits that are switchable between dif- ferent sections. Proper relay operation is achieved by associating a status signal with each input current. This mechanism is referred to as a dynamic bus replica.
  • Page 309: Differential Principle

    Figure 8–2: BIASED OPERATING CHARACTERISTIC The higher slope used by the B90 acts as an actual percentage bias regardless of the value of the restraining signal. This is so because the boundary of the operating characteristic in the higher slope region is a straight line intersecting the origin of the ‘differential - restraining’...
  • Page 310: Differential And Restraining Currents

    HIGH BPNT 5000A : 1000A = 5 pu (1000A is the base unit; see page 8–2 for the example). The same approach applies to the setting of the lower breakpoint, LOW BPNT B90 Low Impedance Bus Differential System GE Multilin...
  • Page 311: Enhanced Security

    8.3 DIFFERENTIAL PRINCIPLE 8.3.3 ENHANCED SECURITY In order to enhance the performance of the B90, the differential characteristic is divided into two regions having diverse operating modes as shown in following diagram. The first region applies to comparatively low differential currents and has been introduced to deal with CT saturation on low- current external faults.
  • Page 312: Directional Principle

    8.4.1 CURRENT DIRECTIONAL PROTECTION For better security, the B90 uses the current directional protection principle to dynamically supervise the main current differ- ential function. The directional principle is in effect permanently for low differential currents (region 1 in Figure 0–1: Two Regions of Differential Characteristic) and is switched on dynamically for large differential currents (Region 2 in the same figure) by the saturation detector (see section 8.5: Saturation Detector) upon detecting CT saturation.
  • Page 313: Saturation Detector

    8.5.1 CT SATURATION DETECTION The saturation detector of the B90 takes advantage of the fact that any CT operates correctly for a short period of time even under very large primary currents that would subsequently cause a very deep saturation. As a result of that, in the case of an external fault, the differential current stays very low during the initial period of linear operation of the CTs while the restraining signal develops rapidly.
  • Page 314: Output Logic And Examples

    Figure 8-10 presents the bus currents and the most important logic signals for the case of an external fault. Despite very fast and severe CT saturation, the B90 remains stable. Figure 8-11 presents the same signals but for the case of an internal fault. The B90 trips in 10 ms (fast form-C output con- tact).
  • Page 315 8 THEORY OF OPERATION 8.6 OUTPUT LOGIC AND EXAMPLES Figure 8–9: EXTERNAL FAULT EXAMPLE GE Multilin B90 Low Impedance Bus Differential System...
  • Page 316 8.6 OUTPUT LOGIC AND EXAMPLES 8 THEORY OF OPERATION Figure 8–10: INTERNAL FAULT EXAMPLE 8-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 317: Application Of Settings

    It is also assumed that the CTs have been selected without considering a B90 application, but the B90 settings are to be calculated for proper relay application. The CT data used in this example are kept to a minimum and in a generic form. The CT data does not reflect any particular notation or national standards.
  • Page 318 RATIO () LEADS (M) CTSEC CT-1 600:5 0.34 CT-2 600:5 0.34 CT-3 1200:5 0.64 CT-4 1000:5 0.54 CT-5, CT-6 1000:5 0.54 CT-7, CT-8 1200:5 0.64 836732A4.CDR Figure 9–2: APPROXIMATE CT MAGNETIZING CHARACTERISTICS B90 Low Impedance Bus Differential System GE Multilin...
  • Page 319: Zoning And Dynamic Bus Replica

    CT-6 and CT-7. The South bus protection should operate the following breakers: B-2 (if S-2 closed), B-3 (if S-4 closed), B-4 (if S-6 closed), B-6 and B-7. NORTH BUS CT-1 CT-7 CT-2 CT-4 CT-3 CT-5 CT-6 CT-8 SOUTH BUS 836734A1.CDR Figure 9–4: SOUTH BUS ZONE GE Multilin B90 Low Impedance Bus Differential System...
  • Page 320: Biased Characteristic Breakpoints

    Assuming 0.003 /m lead resistance and approximating the B90 input resistance for the 5A input CTs as 0.2 VA / (5 A) 0.008 , the limits of the linear operation of the CTs have been calculated and presented in the Limits of Linear Operations of the CTs table.
  • Page 321: Low Breakpoint

    A combination of very high residual magnetism and a DC component with a long time constant may saturate a given CT even with the AC current below the suggested value of the lower breakpoint. The relay copes with this threat by using a 2- out-of-2 operating mode for low differential currents. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 322: Slopes And High Set Threshold

    Table 9–4: EXTERNAL FAULT CALCULATIONS ON C-1 (KA) (A SEC) (MS) (MS) FAULT FAULT SATURATION SATURATION CT-1 14.0 116.67 CT-2 0.00 CT-3 25.00 CT-4 25.00 15.19 CT-6 15.00 35.25 CT-7, CT-8 14.0 58.33 4.70 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 323: External Faults On C-2

    Table 9–6: CALCULATIONS FOR THE EXTERNAL FAULTS ON C-3 (KA) (A SEC) (MS) (MS) FAULT FAULT SATURATION SATURATION CT-1 0.00 CT-2 0.00 CT-3 33.33 11.18 CT-4 25.00 15.19 CT-6 15.00 35.25 CT-7, CT-8 33.33 11.18 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 324 Table 9–8: EXTERNAL FAULT CALCULATIONS ON C-5 (KA) (A SEC) (MS) (MS) FAULT FAULT SATURATION SATURATION CT-1 0.00 CT-2 0.00 CT-3 25.00 CT-4 25.00 15.19 CT-5 11.0 55.00 4.83 CT-7, CT-8 11.0 45.83 7.16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 325 HIGH BPNT 8.96 None of the CTs will saturate for ac currents below 8.96 pu. The dc component, however, may saturate some CTs even for currents below 8.96 pu. The B90 copes with saturation using the current directional principle. HIGH SET 5.94...
  • Page 326: Enhancing Relay Performance

    CTs in any particular bus configuration. 9-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 327: Maintenance

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the B90. 842812A1.CDR Figure 10–1: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)
  • Page 328 The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old CPUs. In the event that there is a mismatch between the CPU and CT/VT module, the relay does not function and error displays. NOTE DSP ERROR HARDWARE MISMATCH 10-2 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 329: Batteries

    10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit. 11. Power on the unit. 12. Dispose of the old battery as outlined in the next section. GE Multilin B90 Low Impedance Bus Differential System 10-3...
  • Page 330 10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit. 11. Power on the unit. 12. Dispose of the old battery as outlined in the next section. 10-4 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 331: Dispose Of Battery

    La batterie est marqué de ce symbole, qui comprennent les indications cadmium (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la batterie à votre fournisseur ou à un point de collecte. Pour plus d'informations, voir: www.recyclethis.info. GE Multilin B90 Low Impedance Bus Differential System 10-5...
  • Page 332 Baterija je označena s tem simbolom, ki lahko vključuje napise, ki označujejo kadmij (Cd), svinec (Pb) ali živo srebro (Hg). Za ustrezno recikliranje baterijo vrnite dobavitelju ali jo odstranite na določenem zbirališču. Za več informacij obiščite spletno stran: www.recyclethis.info. 10-6 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 333 905-294-6222 Latin America +55 11 3614 1700 Europe, Middle East, Africa +(34) 94 485 88 00 Asia +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574 GE Multilin B90 Low Impedance Bus Differential System 10-7...
  • Page 334 10.2 BATTERIES 10 MAINTENANCE 10-8 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 335: Parameter Lists

    Degrees Terminal 14 current angle 28458 L7 Curr Mag Amps Terminal 15 current magnitude 28460 L7 Curr Ang Degrees Terminal 15 current angle 28461 L8 Curr Mag Amps Terminal 16 current magnitude GE Multilin B90 Low Impedance Bus Differential System...
  • Page 336 GOOSE Analog In 1 IEC 61850 GOOSE analog input 1 45586 GOOSE Analog In 2 IEC 61850 GOOSE analog input 2 45588 GOOSE Analog In 3 IEC 61850 GOOSE analog input 3 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 337: Flexinteger Items

    IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 338 A.1 PARAMETER LISTS APPENDIX A B90 Low Impedance Bus Differential System GE Multilin...
  • Page 339: Modbus Communications

    CRC: This is a two byte error checking code. The RTU version of Modbus includes a 16-bit cyclic redundancy check (CRC-16) with every packet which is an industry standard method used for error detection. If a Modbus slave device GE Multilin B90 Low Impedance Bus Differential System...
  • Page 340: Modbus Rtu Crc-16 Algorithm

    A C programming language implementation of the CRC algorithm will be provided upon request. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 341 No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC GE Multilin B90 Low Impedance Bus Differential System...
  • Page 342: Modbus Function Codes

    NUMBER OF REGISTERS - low DATA #2 - high CRC - low DATA #2 - low CRC - high DATA #3 - high DATA #3 - low CRC - low CRC - high B90 Low Impedance Bus Differential System GE Multilin...
  • Page 343: Execute Operation (Function Code 05H

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high GE Multilin B90 Low Impedance Bus Differential System...
  • Page 344: Store Multiple Settings (Function Code 10H

    EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte B90 Low Impedance Bus Differential System GE Multilin...
  • Page 345: File Transfers

    To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT GE Multilin B90 Low Impedance Bus Differential System...
  • Page 346 EVTnnn.TXT (replace nnn with the desired starting record number) To read from a specific record to another specific record, use the following filename: EVT.TXT xxxxx yyyyy (replace xxxxx with the starting record number and yyyyy with the ending record number) B90 Low Impedance Bus Differential System GE Multilin...
  • Page 347: Memory Mapping

    Virtual Input 14 State 0 to 1 F108 0 (Off) 040E Virtual Input 15 State 0 to 1 F108 0 (Off) 040F Virtual Input 16 State 0 to 1 F108 0 (Off) GE Multilin B90 Low Impedance Bus Differential System...
  • Page 348 1 to 1440 F001 IEC103 Binary Inputs (Read/Write Setting) (96 Modules) 0584 IEC103 Binary Input 1 FUN 0 to 255 F001 0585 IEC103 Binary Input 1 INF 0 to 255 F001 B-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 349 ...Repeated for Binary Input 49 0648 ...Repeated for Binary Input 50 064C ...Repeated for Binary Input 51 0650 ...Repeated for Binary Input 52 0654 ...Repeated for Binary Input 53 0658 ...Repeated for Binary Input 54 GE Multilin B90 Low Impedance Bus Differential System B-11...
  • Page 350 IEC103 ASDU 1 Analog Factor 2 0 to 65.535 0.001 F001 1000 070D IEC103 ASDU 1 Analog Offset 2 -32768 to 32767 F002 070E IEC103 ASDU 1 Analog Param 3 0 to 65535 F600 B-12 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 351 ...Repeated for IEC103 Command 22 07D8 ...Repeated for IEC103 Command 23 07DC ...Repeated for IEC103 Command 24 07E0 ...Repeated for IEC103 Command 25 07E4 ...Repeated for IEC103 Command 26 07E8 ...Repeated for IEC103 Command 27 GE Multilin B90 Low Impedance Bus Differential System B-13...
  • Page 352 0 (Fail) Bus Differential Actual Values (Read Only) (4 Modules) 21D0 Bus Zone 1 Differential Magnitude 0 to 999999.999 0.001 F060 21D4 Bus Zone 1 Differential Angle -359.9 to 0 degrees F002 B-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 353 F612 IEC 61850 Received Integers (Read Only Actual Values) (16 Modules) 26F0 IEC 61850 Received uinteger 1 0 to 4294967295 F003 26F2 IEC 61850 Received uinteger 2 0 to 4294967295 F003 GE Multilin B90 Low Impedance Bus Differential System B-15...
  • Page 354 3202 Size of Currently-available Data Block 0 to 65535 F001 3203 Block of Data from Requested File (122 items) 0 to 65535 F001 Security (Read/Write) 3280 Administrator Alphanumeric Password F202 (none) B-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 355 F126 0 (No) 3351 Engineer Logoff 0 to 1 F126 0 (No) 3352 Administrator Logoff 0 to 1 F126 0 (No) 3353 Clear Security Data 0 to 1 F126 0 (No) GE Multilin B90 Low Impedance Bus Differential System B-17...
  • Page 356 Passwords (Read/Write Setting) 400A Setting Password Setting 0 to 4294967295 F202 Passwords (Read/Write) 4014 Command Password Entry 0 to 4294967295 F202 (none) 401E Setting Password Entry 0 to 4294967295 F202 (none) B-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 357 Main UDP Port Number for the TFTP Protocol 0 to 65535 F001 40A7 Data Transfer UDP Port Numbers for the TFTP Protocol 0 to 65535 F001 (zero means “automatic”) (2 items) GE Multilin B90 Low Impedance Bus Differential System B-19...
  • Page 358 High Enet Traffic Function 0 to 1 F102 0 (Disabled) 413F High Enet Traffic Events 0 to 1 F102 0 (Disabled) 4140 DNP Object 1 Default Variation 1 to 2 F001 B-20 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 359 FlexLogic Operand to Activate LED 0 to 4294967295 F300 42C2 User LED type (latched or self-resetting) 0 to 1 F127 1 (Self-Reset) 42C3 ...Repeated for User-Programmable LED 2 42C6 ...Repeated for User-Programmable LED 3 GE Multilin B90 Low Impedance Bus Differential System B-21...
  • Page 360 0 to 4294967295 F003 IPv4 Route Table (Read/Write Setting) (6 Modules) 4370 IPv4 Network Route 1 Destination 0 to 4294967295 F003 56554706 4372 IPv4 Network Route 1 Netmask 0 to 4294967295 F003 56554706 B-22 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 361 ...Repeated for User-Definable Display 11 4D60 ...Repeated for User-Definable Display 12 4D80 ...Repeated for User-Definable Display 13 4DA0 ...Repeated for User-Definable Display 14 4DC0 ...Repeated for User-Definable Display 15 4DE0 ...Repeated for User-Definable Display 16 GE Multilin B90 Low Impedance Bus Differential System B-23...
  • Page 362 Setting Group 2 Name F203 (none) 5F9C Setting Group 3 Name F203 (none) 5FA4 Setting Group 4 Name F203 (none) 5FAC Setting Group 5 Name F203 (none) 5FB4 Setting Group 6 Name F203 (none) B-24 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 363 ...Repeated for Undervoltage 5 6B2C ...Repeated for Undervoltage 6 6B38 ...Repeated for Undervoltage 7 6B44 ...Repeated for Undervoltage 8 6B50 ...Repeated for Undervoltage 9 6B5C ...Repeated for Undervoltage 10 6B68 ...Repeated for Undervoltage 11 GE Multilin B90 Low Impedance Bus Differential System B-25...
  • Page 364 ...Repeated for Isolator 5 6CF8 ...Repeated for Isolator 6 6D04 ...Repeated for Isolator 7 6D10 ...Repeated for Isolator 8 6D1C ...Repeated for Isolator 9 6D28 ...Repeated for Isolator 10 6D34 ...Repeated for Isolator 11 B-26 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 365 ...Repeated for Terminal Current 10 6F1E ...Repeated for Terminal Current 11 6F21 ...Repeated for Terminal Current 12 6F24 ...Repeated for Terminal Current 13 6F27 ...Repeated for Terminal Current 14 6F2A ...Repeated for Terminal Current 15 GE Multilin B90 Low Impedance Bus Differential System B-27...
  • Page 366 VT Terminal Settings (Read/Write Setting) (12 Modules) 6F9C Terminal Voltage Ratio 1 to 24000 0.01 F060 6F9E Terminal Voltage Secondary 50 to 240 F001 6F9F ...Repeated for Terminal Voltage 2 6FA2 ...Repeated for Terminal Voltage 3 B-28 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 367 ...Repeated for module number 9 7049 ...Repeated for module number 9 704A ...Repeated for module number 9 7051 ...Repeated for module number 10 705A ...Repeated for module number 11 7063 ...Repeated for module number 12 GE Multilin B90 Low Impedance Bus Differential System B-29...
  • Page 368 Breaker Failure 1 Use Timer3 0 to 1 F126 1 (Yes) 7110 Breaker Failure 1 Timer3 Pickup Delay 0 to 65.535 0.001 F001 7111 Breaker Failure 1 Breaker Pos1 0 to 4294967295 F300 B-30 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 369 ...Repeated for Breaker Failure 6 7201 ...Repeated for Breaker Failure 6 7203 ...Repeated for Breaker Failure 6 7205 ...Repeated for Breaker Failure 6 7207 ...Repeated for Breaker Failure 6 7209 ...Repeated for Breaker Failure 6 GE Multilin B90 Low Impedance Bus Differential System B-31...
  • Page 370 ...Repeated for Breaker Failure 9 72A7 ...Repeated for Breaker Failure 9 72A8 ...Repeated for Breaker Failure 9 72B0 ...Repeated for Breaker Failure 9 72B3 ...Repeated for Breaker Failure 9 72B5 ...Repeated for Breaker Failure 9 B-32 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 371 ...Repeated for Time Overcurrent 2 770D ...Repeated for Time Overcurrent 3 7710 ...Repeated for Time Overcurrent 4 7712 ...Repeated for Time Overcurrent 5 7714 ...Repeated for Time Overcurrent 6 7716 ...Repeated for Time Overcurrent 7 GE Multilin B90 Low Impedance Bus Differential System B-33...
  • Page 372 Temp Monitor Actual Values (Read Only Non-Volatile) 81C0 Reserved Register T1 -55 to 125 F002 81C1 Reserved Register T2 -55 to 125 F002 81C2 Reserved Register T3 -2147483647 to F004 2147483647 B-34 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 373 ...Repeated for Digital Element 32 8CC0 ...Repeated for Digital Element 33 8CD6 ...Repeated for Digital Element 34 8CEC ...Repeated for Digital Element 35 8D02 ...Repeated for Digital Element 36 8D18 ...Repeated for Digital Element 37 GE Multilin B90 Low Impedance Bus Differential System B-35...
  • Page 374 ...Repeated for Direct Input/Output 20 94F0 ...Repeated for Direct Input/Output 21 94FC ...Repeated for Direct Input/Output 22 9508 ...Repeated for Direct Input/Output 23 9514 ...Repeated for Direct Input/Output 24 9520 ...Repeated for Direct Input/Output 25 B-36 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 375 ...Repeated for Direct Input/Output 74 9778 ...Repeated for Direct Input/Output 75 9784 ...Repeated for Direct Input/Output 76 9790 ...Repeated for Direct Input/Output 77 979C ...Repeated for Direct Input/Output 78 97A8 ...Repeated for Direct Input/Output 79 GE Multilin B90 Low Impedance Bus Differential System B-37...
  • Page 376 ...Repeated for Non-Volatile Latch 3 A724 ...Repeated for Non-Volatile Latch 4 A730 ...Repeated for Non-Volatile Latch 5 A73C ...Repeated for Non-Volatile Latch 6 A748 ...Repeated for Non-Volatile Latch 7 A754 ...Repeated for Non-Volatile Latch 8 B-38 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 377 0 to 4294967295 F300 AB09 Operand for IEC 61850 XCBR Pos ct1Model 0 to 4 F001 AB0A Operand for IEC 61850 XCBR Pos sboTimeout F001 2 to 60 AB0B ...Repeated for Module 2 GE Multilin B90 Low Impedance Bus Differential System B-39...
  • Page 378 ...Repeated for IEC 61850 GGIO4 analog input 20 AF9C ...Repeated for IEC 61850 GGIO4 analog input 21 AFA3 ...Repeated for IEC 61850 GGIO4 analog input 22 AFAA ...Repeated for IEC 61850 GGIO4 analog input 23 B-40 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 379 0.001 to 100 0.001 F003 10000 B0E6 IEC 61850 MMXU VAr.phsB Deadband 1 0.001 to 100 0.001 F003 10000 B0E8 IEC 61850 MMXU VAr.phsC Deadband 1 0.001 to 100 0.001 F003 10000 GE Multilin B90 Low Impedance Bus Differential System B-41...
  • Page 380 Command to Clear XSWI OpCnt (Operation Counter) 0 to 1 F126 0 (No) B373 ...Repeated for module number 2 B376 ...Repeated for module number 3 B379 ...Repeated for module number 4 B-42 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 381 ...Repeated for Module 6 B9C0 ...Repeated for Module 7 B9E0 ...Repeated for Module 8 BA00 ...Repeated for Module 9 BA20 ...Repeated for Module 10 BA40 ...Repeated for Module 11 BA60 ...Repeated for Module 12 GE Multilin B90 Low Impedance Bus Differential System B-43...
  • Page 382 ...Repeated for Contact Input 42 BC50 ...Repeated for Contact Input 43 BC58 ...Repeated for Contact Input 44 BC60 ...Repeated for Contact Input 45 BC68 ...Repeated for Contact Input 46 BC70 ...Repeated for Contact Input 47 B-44 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 383 0 to 3 F128 1 (33 Vdc) Virtual Inputs (Read/Write Setting) (64 Modules) BE30 Virtual Input 1 Function 0 to 1 F102 0 (Disabled) BE31 Virtual Input 1 Name F205 “Virt Ip 1“ GE Multilin B90 Low Impedance Bus Differential System B-45...
  • Page 384 ...Repeated for Virtual Input 47 C064 ...Repeated for Virtual Input 48 C070 ...Repeated for Virtual Input 49 C07C ...Repeated for Virtual Input 50 C088 ...Repeated for Virtual Input 51 C094 ...Repeated for Virtual Input 52 B-46 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 385 ...Repeated for Virtual Output 34 C240 ...Repeated for Virtual Output 35 C248 ...Repeated for Virtual Output 36 C250 ...Repeated for Virtual Output 37 C258 ...Repeated for Virtual Output 38 C260 ...Repeated for Virtual Output 39 GE Multilin B90 Low Impedance Bus Differential System B-47...
  • Page 386 ...Repeated for Virtual Output 88 C3F0 ...Repeated for Virtual Output 89 C3F8 ...Repeated for Virtual Output 90 C400 ...Repeated for Virtual Output 91 C408 ...Repeated for Virtual Output 92 C410 ...Repeated for Virtual Output 93 B-48 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 387 ...Repeated for Direct Output 25 C64B ...Repeated for Direct Output 26 C64E ...Repeated for Direct Output 27 C651 ...Repeated for Direct Output 28 C654 ...Repeated for Direct Output 29 C657 ...Repeated for Direct Output 30 GE Multilin B90 Low Impedance Bus Differential System B-49...
  • Page 388 ...Repeated for Direct Output 79 C6ED ...Repeated for Direct Output 80 C6F0 ...Repeated for Direct Output 81 C6F3 ...Repeated for Direct Output 82 C6F6 ...Repeated for Direct Output 83 C6F9 ...Repeated for Direct Output 84 B-50 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 389 ...Repeated for Direct Input 11 C8BC ...Repeated for Direct Input 12 C8C0 ...Repeated for Direct Input 13 C8C4 ...Repeated for Direct Input 14 C8C8 ...Repeated for Direct Input 15 C8CC ...Repeated for Direct Input 16 GE Multilin B90 Low Impedance Bus Differential System B-51...
  • Page 390 ...Repeated for Direct Input 65 C994 ...Repeated for Direct Input 66 C998 ...Repeated for Direct Input 67 C99C ...Repeated for Direct Input 68 C9A0 ...Repeated for Direct Input 69 C9A4 ...Repeated for Direct Input 70 B-52 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 391 Remote Device 1 GOOSE Ethernet APPID 0 to 16383 F001 CB22 Remote Device 1 GOOSE Dataset 0 to 16 F184 0 (Fixed) CB24 Undefined 0 to 3 F626 0 (None) CB25 ...Repeated for Device 2 GE Multilin B90 Low Impedance Bus Differential System B-53...
  • Page 392 ...Repeated for Remote Input 14 D02C ...Repeated for Remote Input 15 D036 ...Repeated for Remote Input 16 D040 ...Repeated for Remote Input 17 D04A ...Repeated for Remote Input 18 D054 ...Repeated for Remote Input 19 B-54 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 393 F001 D224 ...Repeated for Remote Output 2 D228 ...Repeated for Remote Output 3 D22C ...Repeated for Remote Output 4 D230 ...Repeated for Remote Output 5 D234 ...Repeated for Remote Output 6 GE Multilin B90 Low Impedance Bus Differential System B-55...
  • Page 394 ...Repeated for Remote Output 20 D2F0 ...Repeated for Remote Output 21 D2F4 ...Repeated for Remote Output 22 D2F8 ...Repeated for Remote Output 23 D2FC ...Repeated for Remote Output 24 D300 ...Repeated for Remote Output 25 B-56 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 395 0 to 2 F001 D34B IEC 61850 GGIO2.CF.SPCSO44.ctlModel Value 0 to 2 F001 D34C IEC 61850 GGIO2.CF.SPCSO45.ctlModel Value 0 to 2 F001 D34D IEC 61850 GGIO2.CF.SPCSO46.ctlModel Value 0 to 2 F001 GE Multilin B90 Low Impedance Bus Differential System B-57...
  • Page 396 ...Repeated for Remote Device 30 D3D8 ...Repeated for Remote Device 31 D3DC ...Repeated for Remote Device 32 Contact Outputs (Read/Write Setting) (64 Modules) D3E0 Contact Output 1 Name F205 “Cont Op 1" B-58 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 397 ...Repeated for Contact Output 43 D665 ...Repeated for Contact Output 44 D674 ...Repeated for Contact Output 45 D683 ...Repeated for Contact Output 46 D692 ...Repeated for Contact Output 47 D6A1 ...Repeated for Contact Output 48 GE Multilin B90 Low Impedance Bus Differential System B-59...
  • Page 398 Template Access F205 (none) Setting File Template (Read Only) ED07 Last Settings Change Date 0 to 4294967295 F050 Settings File Template (Read/Write Setting) ED09 Template Bitmask (750 items) 0 to 65535 F001 B-60 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 399: Data Formats

    FlexCurve D Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm; IAC Very Inv Minutes: 0 to 59 in steps of 1 Last bits Seconds (xx:xx:.SS.SSS): 0=00.000s, F104 1=00.001,...,59999=59.999s) ENUMERATION: RESET TYPE 0 = Instantaneous, 1 = Timed GE Multilin B90 Low Impedance Bus Differential System B-61...
  • Page 400 End of Fault Protection 3 Reset End of Fault Protection 4 Selector 1 End of Fault Protection 5 Selector 2 End of Fault Protection 6 Control pushbutton 1 End of Fault Protection 7 B-62 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 401 Digital Element 18 User-Programmable Pushbutton 16 Digital Element 19 Digital Element 20 F126 Digital Element 21 ENUMERATION: NO/YES CHOICE Digital Element 22 0 = No, 1 = Yes Digital Element 23 GE Multilin B90 Low Impedance Bus Differential System B-63...
  • Page 402 FGM Failure Voltage Monitor FGM Error FlexLogic Error Token Maintenance Alert Equipment Mismatch PHY Monitor Process Bus Failure Storage Media Alarm Unit Not Programmed Wrong Transceiver System Exception Power Supply Warning B-64 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 403 Dataset Item 1 Unauthorized Access DNA-31 Dataset Item 2 System Integrity Recovery DNA-32 Dataset Item 3 System Integrity Recovery 06   UserSt-1 System Integrity Recovery 07 UserSt-2 Dataset Item 32 GE Multilin B90 Low Impedance Bus Differential System B-65...
  • Page 404 GooseIn 14 F202 TEXT20: 20-CHARACTER ASCII TEXT GooseIn 15 GooseIn 16 10 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB F203 TEXT16: 16-CHARACTER ASCII TEXT F204 TEXT80: 80-CHARACTER ASCII TEXT B-66 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 405 MMXU2.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind128.q MMXU2.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind128.stVal MMXU2.MX.PhV.phsC.cVal.mag.f MMXU1.MX.TotW.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU1.MX.TotVAr.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU1.MX.TotVA.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU1.MX.TotPF.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU1.MX.Hz.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU1.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f MMXU1.MX.PPV.phsAB.cVal.ang.f MMXU2.MX.A.phsC.cVal.ang.f MMXU1.MX.PPV.phsBC.cVal.mag.f MMXU2.MX.A.neut.cVal.mag.f MMXU1.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.A.neut.cVal.ang.f MMXU1.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.W.phsA.cVal.mag.f MMXU1.MX.PPV.phsCA.cVal.ang.f MMXU2.MX.W.phsB.cVal.mag.f MMXU1.MX.PhV.phsA.cVal.mag.f MMXU2.MX.W.phsC.cVal.mag.f MMXU1.MX.PhV.phsA.cVal.ang.f MMXU2.MX.VAr.phsA.cVal.mag.f GE Multilin B90 Low Impedance Bus Differential System B-67...
  • Page 406 MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU4.MX.TotVAr.mag.f MMXU5.MX.A.phsA.cVal.mag.f MMXU4.MX.TotVA.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU4.MX.TotPF.mag.f MMXU5.MX.A.phsB.cVal.mag.f MMXU4.MX.Hz.mag.f MMXU5.MX.A.phsB.cVal.ang.f MMXU4.MX.PPV.phsAB.cVal.mag.f MMXU5.MX.A.phsC.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.ang.f MMXU5.MX.A.phsC.cVal.ang.f MMXU4.MX.PPV.phsBC.cVal.mag.f MMXU5.MX.A.neut.cVal.mag.f B-68 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 407 GGIO5.ST.UIntIn5.q MMXU6.MX.W.phsA.cVal.mag.f GGIO5.ST.UIntIn5.stVal MMXU6.MX.W.phsB.cVal.mag.f GGIO5.ST.UIntIn6.q MMXU6.MX.W.phsC.cVal.mag.f GGIO5.ST.UIntIn6.stVal MMXU6.MX.VAr.phsA.cVal.mag.f GGIO5.ST.UIntIn7.q MMXU6.MX.VAr.phsB.cVal.mag.f GGIO5.ST.UIntIn7.stVal MMXU6.MX.VAr.phsC.cVal.mag.f GGIO5.ST.UIntIn8.q MMXU6.MX.VA.phsA.cVal.mag.f GGIO5.ST.UIntIn8.stVal MMXU6.MX.VA.phsB.cVal.mag.f GGIO5.ST.UIntIn9.q MMXU6.MX.VA.phsC.cVal.mag.f GGIO5.ST.UIntIn9.stVal MMXU6.MX.PF.phsA.cVal.mag.f GGIO5.ST.UIntIn10.q MMXU6.MX.PF.phsB.cVal.mag.f GGIO5.ST.UIntIn10.stVal MMXU6.MX.PF.phsC.cVal.mag.f GGIO5.ST.UIntIn11.q GGIO4.MX.AnIn1.mag.f GGIO5.ST.UIntIn11.stVal GGIO4.MX.AnIn2.mag.f GGIO5.ST.UIntIn12.q GGIO4.MX.AnIn3.mag.f GGIO5.ST.UIntIn12.stVal GE Multilin B90 Low Impedance Bus Differential System B-69...
  • Page 408 GGIO3.ST.UIntIn16.stVal GGIO3.MX.AnIn17.mag.f GGIO3.MX.AnIn18.mag.f GGIO3.MX.AnIn19.mag.f GGIO3.MX.AnIn20.mag.f F237 GGIO3.MX.AnIn21.mag.f ENUMERATION: REAL TIME CLOCK MONTH GGIO3.MX.AnIn22.mag.f Value Month GGIO3.MX.AnIn23.mag.f January GGIO3.MX.AnIn24.mag.f February GGIO3.MX.AnIn25.mag.f March GGIO3.MX.AnIn26.mag.f April GGIO3.MX.AnIn27.mag.f GGIO3.MX.AnIn28.mag.f June GGIO3.MX.AnIn29.mag.f July GGIO3.MX.AnIn30.mag.f August GGIO3.MX.AnIn31.mag.f B-70 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 409 T represents bits for the BASE type, and D represents bits for the descriptor. F491 ENUMERATION: ANALOG INPUT MODE 0 = Default Value, 1 = Last Known GE Multilin B90 Low Impedance Bus Differential System B-71...
  • Page 410 Analogs (basically all metering quantities used in protection). F524 ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION F601 ENUMERATION: COM2 PORT USAGE Bitmask Default variation Enumeration COM2 port usage RS485 RRTD GPM-F RRTD and GPM-F B-72 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 411 IEC 61850 report dataset items PIOC12.ST.Op.general None PIOC13.ST.Str.general PDIF1.ST.Str.general PIOC13.ST.Op.general PDIF1.ST.Op.general PIOC14.ST.Str.general PDIF2.ST.Str.general PIOC14.ST.Op.general PDIF2.ST.Op.general PIOC15.ST.Str.general PDIF3.ST.Str.general PIOC15.ST.Op.general PDIF3.ST.Op.general PIOC16.ST.Str.general PDIF4.ST.Str.general PIOC16.ST.Op.general PDIF4.ST.Op.general PIOC17.ST.Str.general PDIS1.ST.Str.general PIOC17.ST.Op.general PDIS1.ST.Op.general PIOC18.ST.Str.general PDIS2.ST.Str.general PIOC18.ST.Op.general PDIS2.ST.Op.general PIOC19.ST.Str.general PDIS3.ST.Str.general PIOC19.ST.Op.general GE Multilin B90 Low Impedance Bus Differential System B-73...
  • Page 412 PIOC65.ST.Str.general PIOC39.ST.Str.general PIOC65.ST.Op.general PIOC39.ST.Op.general PIOC66.ST.Str.general PIOC40.ST.Str.general PIOC66.ST.Op.general PIOC40.ST.Op.general PIOC67.ST.Str.general PIOC41.ST.Str.general PIOC67.ST.Op.general PIOC41.ST.Op.general PIOC68.ST.Str.general PIOC42.ST.Str.general PIOC68.ST.Op.general PIOC42.ST.Op.general PIOC69.ST.Str.general PIOC43.ST.Str.general PIOC69.ST.Op.general PIOC43.ST.Op.general PIOC70.ST.Str.general PIOC44.ST.Str.general PIOC70.ST.Op.general PIOC44.ST.Op.general PIOC71.ST.Str.general PIOC45.ST.Str.general PIOC71.ST.Op.general PIOC45.ST.Op.general PIOC72.ST.Str.general PIOC46.ST.Str.general PIOC72.ST.Op.general B-74 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 413 PTUV6.ST.Str.general PTOC20.ST.Str.general PTUV6.ST.Op.general PTOC20.ST.Op.general PTUV7.ST.Str.general PTOC21.ST.Str.general PTUV7.ST.Op.general PTOC21.ST.Op.general PTUV8.ST.Str.general PTOC22.ST.Str.general PTUV8.ST.Op.general PTOC22.ST.Op.general PTUV9.ST.Str.general PTOC23.ST.Str.general PTUV9.ST.Op.general PTOC23.ST.Op.general PTUV10.ST.Str.general PTOC24.ST.Str.general PTUV10.ST.Op.general PTOC24.ST.Op.general PTUV11.ST.Str.general PTOV1.ST.Str.general PTUV11.ST.Op.general PTOV1.ST.Op.general PTUV12.ST.Str.general PTOV2.ST.Str.general PTUV12.ST.Op.general PTOV2.ST.Op.general PTUV13.ST.Str.general PTOV3.ST.Str.general PTUV13.ST.Op.general GE Multilin B90 Low Impedance Bus Differential System B-75...
  • Page 414 CSWI12.ST.Loc.stVal RBRF20.ST.OpEx.general CSWI12.ST.Pos.stVal RBRF20.ST.OpIn.general CSWI13.ST.Loc.stVal RBRF21.ST.OpEx.general CSWI13.ST.Pos.stVal RBRF21.ST.OpIn.general CSWI14.ST.Loc.stVal RBRF22.ST.OpEx.general CSWI14.ST.Pos.stVal RBRF22.ST.OpIn.general CSWI15.ST.Loc.stVal RBRF23.ST.OpEx.general CSWI15.ST.Pos.stVal RBRF23.ST.OpIn.general CSWI16.ST.Loc.stVal RBRF24.ST.OpEx.general CSWI16.ST.Pos.stVal RBRF24.ST.OpIn.general CSWI17.ST.Loc.stVal RFLO1.MX.FltDiskm.mag.f CSWI17.ST.Pos.stVal RFLO2.MX.FltDiskm.mag.f CSWI18.ST.Loc.stVal RFLO3.MX.FltDiskm.mag.f CSWI18.ST.Pos.stVal RFLO4.MX.FltDiskm.mag.f CSWI19.ST.Loc.stVal RFLO5.MX.FltDiskm.mag.f CSWI19.ST.Pos.stVal B-76 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 415 GGIO1.ST.Ind69.stVal GGIO1.ST.Ind17.stVal GGIO1.ST.Ind70.stVal GGIO1.ST.Ind18.stVal GGIO1.ST.Ind71.stVal GGIO1.ST.Ind19.stVal GGIO1.ST.Ind72.stVal GGIO1.ST.Ind20.stVal GGIO1.ST.Ind73.stVal GGIO1.ST.Ind21.stVal GGIO1.ST.Ind74.stVal GGIO1.ST.Ind22.stVal GGIO1.ST.Ind75.stVal GGIO1.ST.Ind23.stVal GGIO1.ST.Ind76.stVal GGIO1.ST.Ind24.stVal GGIO1.ST.Ind77.stVal GGIO1.ST.Ind25.stVal GGIO1.ST.Ind78.stVal GGIO1.ST.Ind26.stVal GGIO1.ST.Ind79.stVal GGIO1.ST.Ind27.stVal GGIO1.ST.Ind80.stVal GGIO1.ST.Ind28.stVal GGIO1.ST.Ind81.stVal GGIO1.ST.Ind29.stVal GGIO1.ST.Ind82.stVal GGIO1.ST.Ind30.stVal GGIO1.ST.Ind83.stVal GGIO1.ST.Ind31.stVal GGIO1.ST.Ind84.stVal GE Multilin B90 Low Impedance Bus Differential System B-77...
  • Page 416 MMXU2.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind123.stVal MMXU2.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind124.stVal MMXU2.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind125.stVal MMXU2.MX.PhV.phsA.cVal.ang.f GGIO1.ST.Ind126.stVal MMXU2.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind127.stVal MMXU2.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind128.stVal MMXU2.MX.PhV.phsC.cVal.mag.f MMXU1.MX.TotW.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU1.MX.TotVAr.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU1.MX.TotVA.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU1.MX.TotPF.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU1.MX.Hz.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU1.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f MMXU1.MX.PPV.phsAB.cVal.ang.f MMXU2.MX.A.phsC.cVal.ang.f MMXU1.MX.PPV.phsBC.cVal.mag.f MMXU2.MX.A.neut.cVal.mag.f MMXU1.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.A.neut.cVal.ang.f B-78 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 417 MMXU5.MX.Hz.mag.f MMXU3.MX.W.phsB.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU4.MX.TotVAr.mag.f MMXU5.MX.A.phsA.cVal.mag.f MMXU4.MX.TotVA.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU4.MX.TotPF.mag.f MMXU5.MX.A.phsB.cVal.mag.f GE Multilin B90 Low Impedance Bus Differential System B-79...
  • Page 418 XSWI3.ST.Loc.stVal MMXU6.MX.A.phsC.cVal.mag.f XSWI3.ST.Pos.stVal MMXU6.MX.A.phsC.cVal.ang.f XSWI4.ST.Loc.stVal MMXU6.MX.A.neut.cVal.mag.f XSWI4.ST.Pos.stVal MMXU6.MX.A.neut.cVal.ang.f XSWI5.ST.Loc.stVal MMXU6.MX.W.phsA.cVal.mag.f XSWI5.ST.Pos.stVal MMXU6.MX.W.phsB.cVal.mag.f XSWI6.ST.Loc.stVal MMXU6.MX.W.phsC.cVal.mag.f XSWI6.ST.Pos.stVal MMXU6.MX.VAr.phsA.cVal.mag.f XSWI7.ST.Loc.stVal MMXU6.MX.VAr.phsB.cVal.mag.f XSWI7.ST.Pos.stVal MMXU6.MX.VAr.phsC.cVal.mag.f XSWI8.ST.Loc.stVal MMXU6.MX.VA.phsA.cVal.mag.f XSWI8.ST.Pos.stVal MMXU6.MX.VA.phsB.cVal.mag.f XSWI9.ST.Loc.stVal MMXU6.MX.VA.phsC.cVal.mag.f XSWI9.ST.Pos.stVal MMXU6.MX.PF.phsA.cVal.mag.f XSWI10.ST.Loc.stVal MMXU6.MX.PF.phsB.cVal.mag.f XSWI10.ST.Pos.stVal B-80 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 419 GGIO1.ST.Ind25.q F616 GGIO1.ST.Ind25.stVal ENUMERATION: IEC 61850 GOOSE DATASET ITEMS GGIO1.ST.Ind26.q Enumeration GOOSE dataset items GGIO1.ST.Ind26.stVal None GGIO1.ST.Ind27.q GGIO1.ST.Ind1.q GGIO1.ST.Ind27.stVal GGIO1.ST.Ind1.stVal GGIO1.ST.Ind28.q GGIO1.ST.Ind2.q GGIO1.ST.Ind28.stVal GGIO1.ST.Ind2.stVal GGIO1.ST.Ind29.q GGIO1.ST.Ind3.q GGIO1.ST.Ind29.stVal GGIO1.ST.Ind3.stVal GGIO1.ST.Ind30.q GGIO1.ST.Ind4.q GGIO1.ST.Ind30.stVal GE Multilin B90 Low Impedance Bus Differential System B-81...
  • Page 420 GGIO1.ST.Ind76.q GGIO1.ST.Ind50.q GGIO1.ST.Ind76.stVal GGIO1.ST.Ind50.stVal GGIO1.ST.Ind77.q GGIO1.ST.Ind51.q GGIO1.ST.Ind77.stVal GGIO1.ST.Ind51.stVal GGIO1.ST.Ind78.q GGIO1.ST.Ind52.q GGIO1.ST.Ind78.stVal GGIO1.ST.Ind52.stVal GGIO1.ST.Ind79.q GGIO1.ST.Ind53.q GGIO1.ST.Ind79.stVal GGIO1.ST.Ind53.stVal GGIO1.ST.Ind80.q GGIO1.ST.Ind54.q GGIO1.ST.Ind80.stVal GGIO1.ST.Ind54.stVal GGIO1.ST.Ind81.q GGIO1.ST.Ind55.q GGIO1.ST.Ind81.stVal GGIO1.ST.Ind55.stVal GGIO1.ST.Ind82.q GGIO1.ST.Ind56.q GGIO1.ST.Ind82.stVal GGIO1.ST.Ind56.stVal GGIO1.ST.Ind83.q GGIO1.ST.Ind57.q GGIO1.ST.Ind83.stVal B-82 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 421 MMXU1.MX.TotW.mag.f GGIO1.ST.Ind103.q MMXU1.MX.TotVAr.mag.f GGIO1.ST.Ind103.stVal MMXU1.MX.TotVA.mag.f GGIO1.ST.Ind104.q MMXU1.MX.TotPF.mag.f GGIO1.ST.Ind104.stVal MMXU1.MX.Hz.mag.f GGIO1.ST.Ind105.q MMXU1.MX.PPV.phsAB.cVal.mag.f GGIO1.ST.Ind105.stVal MMXU1.MX.PPV.phsAB.cVal.ang.f GGIO1.ST.Ind106.q MMXU1.MX.PPV.phsBC.cVal.mag.f GGIO1.ST.Ind106.stVal MMXU1.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind107.q MMXU1.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind107.stVal MMXU1.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind108.q MMXU1.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind108.stVal MMXU1.MX.PhV.phsA.cVal.ang.f GGIO1.ST.Ind109.q MMXU1.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind109.stVal MMXU1.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind110.q MMXU1.MX.PhV.phsC.cVal.mag.f GE Multilin B90 Low Impedance Bus Differential System B-83...
  • Page 422 MMXU3.MX.VA.phsB.cVal.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU2.MX.A.phsC.cVal.ang.f MMXU4.MX.TotVAr.mag.f MMXU2.MX.A.neut.cVal.mag.f MMXU4.MX.TotVA.mag.f MMXU2.MX.A.neut.cVal.ang.f MMXU4.MX.TotPF.mag.f MMXU2.MX.W.phsA.cVal.mag.f MMXU4.MX.Hz.mag.f MMXU2.MX.W.phsB.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.W.phsC.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.ang.f MMXU2.MX.VAr.phsA.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.mag.f MMXU2.MX.VAr.phsB.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.VAr.phsC.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.VA.phsA.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.ang.f B-84 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 423 MMXU6.MX.W.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU6.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU6.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU6.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU6.MX.VA.phsA.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU6.MX.VA.phsB.cVal.mag.f MMXU5.MX.A.phsA.cVal.mag.f MMXU6.MX.VA.phsC.cVal.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU6.MX.PF.phsA.cVal.mag.f MMXU5.MX.A.phsB.cVal.mag.f MMXU6.MX.PF.phsB.cVal.mag.f MMXU5.MX.A.phsB.cVal.ang.f MMXU6.MX.PF.phsC.cVal.mag.f MMXU5.MX.A.phsC.cVal.mag.f GGIO4.MX.AnIn1.mag.f MMXU5.MX.A.phsC.cVal.ang.f GGIO4.MX.AnIn2.mag.f MMXU5.MX.A.neut.cVal.mag.f GGIO4.MX.AnIn3.mag.f MMXU5.MX.A.neut.cVal.ang.f GGIO4.MX.AnIn4.mag.f MMXU5.MX.W.phsA.cVal.mag.f GGIO4.MX.AnIn5.mag.f MMXU5.MX.W.phsB.cVal.mag.f GGIO4.MX.AnIn6.mag.f GE Multilin B90 Low Impedance Bus Differential System B-85...
  • Page 424 PIOC3.ST.Str.general GGIO5.ST.UIntIn7.q PIOC3.ST.Op.general GGIO5.ST.UIntIn7.stVal PIOC4.ST.Str.general GGIO5.ST.UIntIn8.q PIOC4.ST.Op.general GGIO5.ST.UIntIn8.stVal PIOC5.ST.Str.general GGIO5.ST.UIntIn9.q PIOC5.ST.Op.general GGIO5.ST.UIntIn9.stVal PIOC6.ST.Str.general GGIO5.ST.UIntIn10.q PIOC6.ST.Op.general GGIO5.ST.UIntIn10.stVal PIOC7.ST.Str.general GGIO5.ST.UIntIn11.q PIOC7.ST.Op.general GGIO5.ST.UIntIn11.stVal PIOC8.ST.Str.general GGIO5.ST.UIntIn12.q PIOC8.ST.Op.general GGIO5.ST.UIntIn12.stVal PIOC9.ST.Str.general GGIO5.ST.UIntIn13.q PIOC9.ST.Op.general GGIO5.ST.UIntIn13.stVal PIOC10.ST.Str.general GGIO5.ST.UIntIn14.q PIOC10.ST.Op.general B-86 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 425 PIOC56.ST.Str.general PIOC30.ST.Str.general PIOC56.ST.Op.general PIOC30.ST.Op.general PIOC57.ST.Str.general PIOC31.ST.Str.general PIOC57.ST.Op.general PIOC31.ST.Op.general PIOC58.ST.Str.general PIOC32.ST.Str.general PIOC58.ST.Op.general PIOC32.ST.Op.general PIOC59.ST.Str.general PIOC33.ST.Str.general PIOC59.ST.Op.general PIOC33.ST.Op.general PIOC60.ST.Str.general PIOC34.ST.Str.general PIOC60.ST.Op.general PIOC34.ST.Op.general PIOC61.ST.Str.general PIOC35.ST.Str.general PIOC61.ST.Op.general PIOC35.ST.Op.general PIOC62.ST.Str.general PIOC36.ST.Str.general PIOC62.ST.Op.general PIOC36.ST.Op.general PIOC63.ST.Str.general PIOC37.ST.Str.general PIOC63.ST.Op.general GE Multilin B90 Low Impedance Bus Differential System B-87...
  • Page 426 PTRC3.ST.Tr.general PTOC11.ST.Str.general PTRC3.ST.Op.general PTOC11.ST.Op.general PTRC4.ST.Tr.general PTOC12.ST.Str.general PTRC4.ST.Op.general PTOC12.ST.Op.general PTRC5.ST.Tr.general PTOC13.ST.Str.general PTRC5.ST.Op.general PTOC13.ST.Op.general PTRC6.ST.Tr.general PTOC14.ST.Str.general PTRC6.ST.Op.general PTOC14.ST.Op.general PTUV1.ST.Str.general PTOC15.ST.Str.general PTUV1.ST.Op.general PTOC15.ST.Op.general PTUV2.ST.Str.general PTOC16.ST.Str.general PTUV2.ST.Op.general PTOC16.ST.Op.general PTUV3.ST.Str.general PTOC17.ST.Str.general PTUV3.ST.Op.general PTOC17.ST.Op.general PTUV4.ST.Str.general PTOC18.ST.Str.general PTUV4.ST.Op.general B-88 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 427 CSWI3.ST.Loc.stVal RBRF11.ST.OpEx.general CSWI3.ST.Pos.stVal RBRF11.ST.OpIn.general CSWI4.ST.Loc.stVal RBRF12.ST.OpEx.general CSWI4.ST.Pos.stVal RBRF12.ST.OpIn.general CSWI5.ST.Loc.stVal RBRF13.ST.OpEx.general CSWI5.ST.Pos.stVal RBRF13.ST.OpIn.general CSWI6.ST.Loc.stVal RBRF14.ST.OpEx.general CSWI6.ST.Pos.stVal RBRF14.ST.OpIn.general CSWI7.ST.Loc.stVal RBRF15.ST.OpEx.general CSWI7.ST.Pos.stVal RBRF15.ST.OpIn.general CSWI8.ST.Loc.stVal RBRF16.ST.OpEx.general CSWI8.ST.Pos.stVal RBRF16.ST.OpIn.general CSWI9.ST.Loc.stVal RBRF17.ST.OpEx.general CSWI9.ST.Pos.stVal RBRF17.ST.OpIn.general CSWI10.ST.Loc.stVal RBRF18.ST.OpEx.general CSWI10.ST.Pos.stVal GE Multilin B90 Low Impedance Bus Differential System B-89...
  • Page 428 XCBR2.ST.Pos.stVal CSWI30.ST.Pos.stVal 1001 XCBR3.ST.Loc.stVal XSWI1.ST.Loc.stVal 1002 XCBR3.ST.Pos.stVal XSWI1.ST.Pos.stVal 1003 XCBR4.ST.Loc.stVal XSWI2.ST.Loc.stVal 1004 XCBR4.ST.Pos.stVal XSWI2.ST.Pos.stVal 1005 XCBR5.ST.Loc.stVal XSWI3.ST.Loc.stVal 1006 XCBR5.ST.Pos.stVal XSWI3.ST.Pos.stVal 1007 XCBR6.ST.Loc.stVal XSWI4.ST.Loc.stVal 1008 XCBR6.ST.Pos.stVal XSWI4.ST.Pos.stVal XSWI5.ST.Loc.stVal XSWI5.ST.Pos.stVal XSWI6.ST.Loc.stVal XSWI6.ST.Pos.stVal XSWI7.ST.Loc.stVal B-90 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 429 Item F631 ENUMERATION: VIRTUAL INPUTS FOR IEC 103 None Port 1 PTP Clock Enumeration Item Port 2 PTP Clock Port 3 PTP Clock Virtual Input 1 IRIG-B Virtual Input 2 SNTP GE Multilin B90 Low Impedance Bus Differential System B-91...
  • Page 430 B.4 MEMORY MAPPING APPENDIX B Enumeration Item Virtual Input 3   Virtual Input 64 B-92 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 431: Iec 61850

    LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract ser- vices in IEC 61850-8-1. The B90 relay supports IEC 61850 server services over TCP/IP. The TCP/IP profile requires the B90 to have an IP address to establish communications. These addresses are located in the ...
  • Page 432: Server Data Organization

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the B90 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
  • Page 433: Mmxn: Analog Measured Values

    C.2.6 MMXN: ANALOG MEASURED VALUES A limited number of measured analog values are available through the MMXN logical nodes. Each MMXN logical node provides data from a B90 current and voltage terminal. There is one MMXN available for each configurable terminal (programmed in the ...
  • Page 434 IEC 61850 control model. • XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct control with normal security is the only supported IEC 61850 control model. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 435: Server Features And Configuration

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the B90. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.
  • Page 436: Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the B90 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the B90. This frees up the con- nection to be used by other clients.
  • Page 437: Generic Substation Event Services: Gsse And Goose

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the B90 will use the source Ether- net MAC address as the destination, with the multicast bit set.
  • Page 438 The B90 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 439 REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic equations or other settings. The B90 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 440: Ethernet Mac Address For Gsse/Goose

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the B90 is configured to use an automated multicast MAC scheme. If the B90 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
  • Page 441: Iec 61850 Implementation Via Enervista Ur Setup

    The B90 can be configured for IEC 61850 via the EnerVista UR Setup software as follows. An ICD file is generated for the B90 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 442: Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the B90 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
  • Page 443: About Icd Files

    (which also includes SSD, CID and SCD files). The ICD file describes the capabilities of an IED and consists of four major sections: • Header • Communication • IEDs • DataTypeTemplates GE Multilin B90 Low Impedance Bus Differential System C-13...
  • Page 444 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. C-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 445 Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure C–4: ICD FILE STRUCTURE, IED NODE GE Multilin B90 Low Impedance Bus Differential System C-15...
  • Page 446 Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure C–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE C-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 447: Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline B90 settings file is typically much quicker than create an ICD file directly from the relay.
  • Page 448 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE C-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 449 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. GE Multilin B90 Low Impedance Bus Differential System C-19...
  • Page 450: Importing An Scd File With Enervista Ur Setup

    Figure C–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the B90 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
  • Page 451 File to Device item. The software will prompt for the target device. Select the target device from the list provided and click Send. The new settings will be updated to the selected device. GE Multilin B90 Low Impedance Bus Differential System C-21...
  • Page 452: Acsi Conformance

    Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion C-22 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 453: Acsi Services Conformance Statement

    UR FAMILY PUBLISHER SERVER (CLAUSE 7) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 8) Associate Abort Release LOGICAL DEVICE (CLAUSE 9) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 10) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 11) GetDataValues SetDataValues GetDataDirectory GetDataDefinition GE Multilin B90 Low Impedance Bus Differential System C-23...
  • Page 454 LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 18, ANNEX C) GOOSE-CONTROL-BLOCK (CLAUSE 18) SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK (ANNEX C) SendGSSEMessage GetReference GetGSSEElementNumber GetGsCBValues C-24 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 455 (SendGOOSEMessage or SendGSSEMessage) NOTE c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) GE Multilin B90 Low Impedance Bus Differential System C-25...
  • Page 456: Logical Nodes

    GGIO: Generic process I/O GLOG: Generic log GSAL: Generic security application I: LOGICAL NODES FOR INTERFACING AND ARCHIVING IARC: Archiving IHMI: Human machine interface ISAF: Safety alarm function ITCI: Telecontrol interface ITMI: Telemonitoring interface C-26 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 457 PSCH: Protection scheme PSDE: Sensitive directional earth fault PTEF: Transient earth fault PTOC: Time overcurrent PTOF: Overfrequency PTOV: Overvoltage PTRC: Protection trip conditioning PTTR: Thermal overload PTUC: Undercurrent PTUF: Underfrequency PTUV: Undervoltage GE Multilin B90 Low Impedance Bus Differential System C-27...
  • Page 458 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TANG: Angle TAXD: Axial displacement TCTR: Current transformer TDST: Distance TFLW: Liquid flow TFRQ: Frequency TGSN: Generic sensor THUM: Humidity TLVL: Media level TMGF: Magnetic field TMVM: Movement sensor C-28 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 459 ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRES: Resistor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZSCR: Semi-conductor controlled rectifier ZSMC: Synchronous machine ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component GE Multilin B90 Low Impedance Bus Differential System C-29...
  • Page 460 C.7 LOGICAL NODES APPENDIX C C-30 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 461: Iec 60870-5-103

    Xt = (8191/Xmax) * X - 4096 a = 2 * 4096/Xmax b = -4096 To calculate Xmax, one needs to know the rated value for the specific type of measurand. Xmax = 2.4 * Xrated GE Multilin B90 Low Impedance Bus Differential System...
  • Page 462: Interoperability Document

    Status indications in monitor direction INF Semantics  <16> Auto-recloser active  <17> Teleprotection active  <18> Protection active  <19> LED reset  <20> Monitor direction blocked  <21> Test mode B90 Low Impedance Bus Differential System GE Multilin...
  • Page 463  <68> General trip  <69> Trip L  <70> Trip L  <71> Trip L  <72> Trip I>> (back-up operation)  <73> Fault location X in ohms  <74> Fault forward/line GE Multilin B90 Low Impedance Bus Differential System...
  • Page 464  <243> Read directory of a single entry  <244> Read value or attribute of a single entry  <245> End of general interrogation of generic data  <249> Write entry with confirmation  <250> Write entry with execution B90 Low Impedance Bus Differential System GE Multilin...
  • Page 465  Generic services  Private data Miscellaneous MEASURAND MAX MVAL = TIMES RATED VALUE Current L   Current L   Current L   Voltage L   Voltage L   GE Multilin B90 Low Impedance Bus Differential System...
  • Page 466 D.1 IEC 60870-5-103 APPENDIX D MEASURAND MAX MVAL = TIMES RATED VALUE Voltage L   Active power P   Reactive power Q   Frequency f   Voltage L   B90 Low Impedance Bus Differential System GE Multilin...
  • Page 467: Interoperability Document

    Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin B90 Low Impedance Bus Differential System...
  • Page 468  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 469  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 470 •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 471 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 472 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure B90 Low Impedance Bus Differential System GE Multilin...
  • Page 473  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin B90 Low Impedance Bus Differential System...
  • Page 474 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs B90 Low Impedance Bus Differential System GE Multilin...
  • Page 475: Iec 60870-5-104 Points

    E.1.2 IEC 60870-5-104 POINTS The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. See the Communications section of chapter 5 for details. IEC104 POINT LISTS GE Multilin B90 Low Impedance Bus Differential System...
  • Page 476 E.1 IEC 60870-5-104 APPENDIX E E-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 477: Dnp Communications

    Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin B90 Low Impedance Bus Differential System...
  • Page 478 FlexLogic. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 479  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin B90 Low Impedance Bus Differential System...
  • Page 480: F.1.2 Implementation Table

    17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B90 is not restarted, but the DNP process is restarted. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 481 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B90 is not restarted, but the DNP process is restarted. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 482 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B90 is not restarted, but the DNP process is restarted. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 483 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B90 is not restarted, but the DNP process is restarted. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 484: Dnp Point Lists

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 485: Binary And Control Relay Output

    Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 486: Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 F-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 487: Radius Server

    For example, the file can look like the following: $INCLUDE ../shareéfreeradius/dictionary $INCLUDE dictionary.ge For the first start, run the RADIUS server in debug mode to ensure that there are no compiling errors. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 488: Radius Server Configuration

    (for example user name Tester and password "testpw"). Check that the RADIUS server log file shows the access with an "Access-Accept" entry. Recall that If you tried another third-party tool and it did not work, you can use the FreeRADIUS software from freera- dius.net. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 489: Miscellaneous

    13-0126 1601-0115-AA1 7.2x 1 August 2013 13-0401 1601-0115-AA2 7.2x 31 December 2014 14-1732 H.1.2 CHANGES TO THE B90 MANUAL Table H–2: MAJOR UPDATES FOR B90 MANUAL REVISION AA2 PAGE PAGE CHANGE DESCRIPTION (AA1) (AA2) Update General revision throughout document Update...
  • Page 490 Revised section 1.3.1 on system requirements, including addition of support for Windows 7 and Windows Server 2008 Delete Deleted references and figures relating to multiple B90 units because only one B90 unit is allowed per system Update Updated several specifications...
  • Page 491 APPENDIX H H.1 CHANGE NOTES Table H–7: MAJOR UPDATES FOR B90 MANUAL REVISION Y1 PAGE PAGE CHANGE DESCRIPTION (X2) (Y1) Delete Deleted content pertaining to Ethernet switch Title Title Update Changed part numbers. Updated address and contact information. Update Updated address and contact information...
  • Page 492: Abbreviations

    FD ....Fault Detector MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A ... MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set MVA_B ... MegaVolt-Ampere (phase B) FLA....Full Load Current B90 Low Impedance Bus Differential System GE Multilin...
  • Page 493 ....With Option RST ....Reset WRT....With Respect To RSTR ..... Restrained RTD....Resistance Temperature Detector X .....Reactance RTU....Remote Terminal Unit XDUCER..Transducer RX (Rx) ..Receive, Receiver XFMR....Transformer s ..... second Z......Impedance, Zone GE Multilin B90 Low Impedance Bus Differential System...
  • Page 494: H.3.1 Ge Multilin Warranty

    APPENDIX H H.3WARRANTY H.3.1 GE MULTILIN WARRANTY If the B90 system is ordered as part of an engineered solution, the warranty is void if the relay logic is changed. NOTE For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years.
  • Page 495 Modbus registers ............B-25 actual values ..............6-3 settings ............. 5-114, 5-116 FlexLogic operands ............5-103 specifications ..............2-12 Modbus registers ........B-14, B-16, B-58 theory of operation ............8-1 settings ............... 5-151 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 496 ............... 5-141 definite time curve ............5-132 DIGITAL OUTPUTS I²t curves ..............5-132 see entry for CONTACT OUTPUTS IAC curves ..............5-131 DIMENSIONS ..............3-1 IEC curves ..............5-130 IEEE curves ..............5-128 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 497 IEEE C37.94 COMMUNICATIONS ....3-34, 3-36, 3-39 FLEXLOGIC TIMERS IEEE CURVES ............... 5-128 Modbus registers ............B-24 IN SERVICE INDICATOR ........... 1-19, 7-6 settings ............... 5-112 INCOMPATIBLE HARDWARE ERROR ........ 7-6 FORCE CONTACT INPUTS ..........5-164 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 498 LINK POWER BUDGET ............ 2-17 settings ................ 5-112 LOCAL SETTING AUTHORIZATION ........4-2 specifications ..............2-13 LOGIC GATES ............... 5-106 LOGS, SYSTEM ............... 5-20 LOST PASSWORD ............. 5-5 ONE SHOTS ..............5-106 OPERATING TEMPERATURE ...........2-17 OPERATING TIMES ............2-12 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 499 RFI, CONDUCTED ............2-18 description ..............3-10 RMS CURRENT ............... 2-14 low range ..............2-15 RS232 removal to replace battery ..........10-3 configuration ..............1-9 specifications ..............2-15 specifications ..............2-16 wiring ................3-21 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 500 ............... 7-4 Modbus registers ..........B-19, B-23 SYSLOG ................5-20 settings ..............5-78, 5-80 SYSTEM FREQUENCY ............ 5-90 specifications ..............2-13 SYSTEM LOGS ..............5-20 SYSTEM REQUIREMENTS ..........1-5 SYSTEM SETUP .............. 5-89 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 501 VIRTUAL INPUTS RS422 interface ............. 3-31 actual values ..............6-3 WIRING DIAGRAM ............. 3-5 commands ..............7-1 FlexLogic operands ............. 5-104 logic ................5-150 Modbus registers ............ B-9, B-45 settings ............... 5-150 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 502 INDEX viii B90 Low Impedance Bus Differential System GE Multilin...

Table of Contents