GE Digital Energy L30 Instruction Manual

Line current differential system, ur series
Table of Contents

Advertisement

Quick Links

GE
Digital Energy
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEDigitalEnergy.com
*1601-9050-Y2*
L30 Line Current Differential
UR Series Instruction Manual
Manual P/N: 1601-9050-Y2 (GEK-113670A)
E83849
LISTED
IND.CONT. EQ.
52TL
System
L30 revision: 7.0x
831776A2.CDR
GE Multilin's Quality Management
System is registered to ISO
9001:2008
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the L30 and is the answer not in the manual?

Questions and answers

Summary of Contents for GE Digital Energy L30

  • Page 1 Digital Energy L30 Line Current Differential System UR Series Instruction Manual L30 revision: 7.0x Manual P/N: 1601-9050-Y2 (GEK-113670A) 831776A2.CDR E83849 GE Digital Energy LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1 System is registered to ISO...
  • Page 2 Copyright © 2012 GE Multilin Inc. All rights reserved. L30 Line Current Differential System UR Series Instruction Manual revision 7.0x. FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista, CyberSentry, HardFiber, Digital Energy, Multilin, and GE Multilin are trademarks or registered trademarks of GE Multilin Inc.
  • Page 3: Table Of Contents

    1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 PC REQUIREMENTS ..................1-5 1.3.2 INSTALLATION....................1-5 1.3.3 CONFIGURING THE L30 FOR SOFTWARE ACCESS........1-6 1.3.4 USING THE QUICK CONNECT FEATURE............1-9 1.3.5 CONNECTING TO THE L30 RELAY ............... 1-15 1.4 UR HARDWARE 1.4.1 MOUNTING AND WIRING................
  • Page 4 5.2 PRODUCT SETUP 5.2.1 SECURITY......................5-8 5.2.2 CYBERSENTRY SECURITY................5-12 5.2.3 DISPLAY PROPERTIES ..................5-18 5.2.4 CLEAR RELAY RECORDS ................5-19 5.2.5 COMMUNICATIONS ..................5-20 5.2.6 MODBUS USER MAP ..................5-44 5.2.7 REAL TIME CLOCK ..................5-44 5.2.8 FAULT REPORTS ....................5-50 L30 Line Current Differential System GE Multilin...
  • Page 5 5.8.7 REMOTE DOUBLE-POINT STATUS INPUTS ..........5-228 5.8.8 REMOTE OUTPUTS..................5-228 5.8.9 DIRECT INPUTS AND OUTPUTS ..............5-229 5.8.10 RESETTING....................5-231 5.8.11 IEC 61850 GOOSE ANALOGS..............5-231 5.8.12 IEC 61850 GOOSE INTEGERS..............5-232 GE Multilin L30 Line Current Differential System...
  • Page 6 7. COMMANDS AND 7.1 COMMANDS TARGETS 7.1.1 COMMANDS MENU ...................7-1 7.1.2 VIRTUAL INPUTS ....................7-1 7.1.3 CLEAR RECORDS .....................7-2 7.1.4 SET DATE AND TIME ..................7-2 7.1.5 RELAY MAINTENANCE ..................7-3 7.1.6 PHASOR MEASUREMENT UNIT ONE-SHOT ..........7-3 L30 Line Current Differential System GE Multilin...
  • Page 7 CURRENT DIFF RESTRAINT 1 ..............10-3 10.2.4 CURRENT DIFF RESTRAINT 2 ..............10-3 10.2.5 CURRENT DIFF BREAK POINT ..............10-3 10.2.6 CT TAP ......................10-4 10.3 CHANNEL ASYMMETRY COMPENSATION USING GPS 10.3.1 DESCRIPTION....................10-6 GE Multilin L30 Line Current Differential System...
  • Page 8 10.3.2 COMPENSATION METHOD 1 .................10-6 10.3.3 COMPENSATION METHOD 2 .................10-7 10.3.4 COMPENSATION METHOD 3 .................10-7 10.4 INSTANTANEOUS ELEMENTS 10.4.1 INSTANTANEOUS ELEMENT ERROR DURING L30 SYNCHRONIZATION .10-9 11. COMMISSIONING 11.1 TESTING 11.1.1 CHANNEL TESTING ..................11-1 11.1.2 CLOCK SYNCHRONIZATION TESTS .............11-2 11.1.3 CURRENT DIFFERENTIAL................11-3...
  • Page 9 COUNTERS .....................E-10 E.2.4 ANALOG INPUTS ....................E-11 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY ..................F-1 F.1.2 CHANGES TO THE L30 MANUAL ..............F-1 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ................. F-7 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY ................F-11 GE Multilin...
  • Page 10 TABLE OF CONTENTS L30 Line Current Differential System GE Multilin...
  • Page 11: Getting Started

    1.1 IMPORTANT PROCEDURES 1 GETTING STARTED 1.1IMPORTANT PROCEDURES Read this chapter to help guide you through the initial setup of your new L30 Line Current Differential System. 1.1.1 CAUTIONS AND WARNINGS Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.
  • Page 12: Ur Overview

    This new generation of equipment is easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Uni- versal Relay (UR) series meets these goals. L30 Line Current Differential System GE Multilin...
  • Page 13: Hardware Architecture

    (dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. GE Multilin L30 Line Current Differential System...
  • Page 14: Software Architecture

    Employing OOD/OOP in the software architecture of the L30 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functional classes.
  • Page 15: Enervista Ur Setup Software

    Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color) • RS232 and/or Ethernet port for communications to the relay The following qualified modems have been tested to be compliant with the L30 and the EnerVista UR Setup software: • US Robotics external 56K FaxModem 5686 •...
  • Page 16: Configuring The L30 For Software Access

    OVERVIEW The user can connect remotely to the L30 through the rear RS485 port or the rear Ethernet port with a computer running the EnerVista UR Setup software. The L30 can also be accessed locally with a laptop computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
  • Page 17 An Ethernet module must be specified at the time of ordering. • To configure the L30 for local access with a laptop through either the front RS232 port or rear Ethernet port, see the Using the Quick Connect Feature section.
  • Page 18 1 GETTING STARTED 10. Click the Read Order Code button to connect to the L30 device and upload the order code. If a communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values.
  • Page 19: Using The Quick Connect Feature

    MODBUS PROTOCOL 11. Click the Read Order Code button to connect to the L30 device and upload the order code. If an communications error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values.
  • Page 20 Now, assign the computer an IP address compatible with the relay’s IP address. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con- nections window. Right-click the Local Area Connection icon and select Properties. 1-10 L30 Line Current Differential System GE Multilin...
  • Page 21 Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. Click the “Use the following IP address” box. Enter an IP address with the first three numbers the same as the IP address of the L30 relay and the last number dif- ferent (in this example, 1.1.1.2).
  • Page 22 Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data: verify the physical connection between the L30 and the laptop computer, and double-check the programmed IP address in the setting, then repeat step 2.
  • Page 23 Click the Quick Connect button to open the Quick Connect dialog box. Select the Ethernet interface and enter the IP address assigned to the L30, then click the Connect button. The EnerV- ista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Con- nect”...
  • Page 24 Set the computer to “Obtain a relay address automatically” as shown. If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been discon- nected from the L30 relay. AUTOMATIC DISCOVERY OF ETHERNET DEVICES The EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on an Ether- net network.
  • Page 25: Connecting To The L30 Relay

    The EnerVista UR Setup software has several quick action buttons to provide instant access to several functions that are often performed when using L30 relays. From the online window, users can select the relay to interrogate from a pull-down window, then click the button for the action they want to perform. The following quick action functions are available: •...
  • Page 26: Ur Hardware

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the L30 rear communications port. The converter terminals (+, –, GND) are connected to the L30 communication module (+, –, COM) terminals. See the CPU communica- tions ports section in chapter 3 for details.
  • Page 27: Using The Relay

    To put the relay in the “Programmed” state, press either of the VALUE keys once and then press ENTER. The face- plate Trouble LED turns off and the In Service LED turns on. GE Multilin L30 Line Current Differential System 1-17...
  • Page 28: Relay Passwords

    See the Changing Settings section in Chapter 4 for complete instructions on setting security-level passwords. 1.5.6 FLEXLOGIC™ CUSTOMIZATION NOTE FlexLogic equation editing is required for setting user-defined logic for customizing the relay operations. See the FlexLogic section in Chapter 5. 1-18 L30 Line Current Differential System GE Multilin...
  • Page 29: Commissioning

    As such, no further functional tests are required. The L30 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the Relay Self-tests section in chapter 7). However, it is recommended that L30 maintenance be scheduled with other system maintenance.
  • Page 30 1.5 USING THE RELAY 1 GETTING STARTED 1-20 L30 Line Current Differential System GE Multilin...
  • Page 31: Product Description

    The L30 is intended to provide complete protection for transmission lines of any voltage level. Both three phase and single phase tripping schemes are available. Models of the L30 are available for application on both two and three terminal lines.
  • Page 32 Non-volatile selector switch Virtual outputs (96) Direct inputs (8 per pilot channel) Open pole detector VT fuse failure Disconnect switches Oscillography DNP 3.0 or IEC 60870-5-104 protocol Setting groups (6) Event recorder Stub bus L30 Line Current Differential System GE Multilin...
  • Page 33: Features

    FlexLogic allowing creation of user-defined distributed protection and control logic. CONTROL: • One and two breaker configuration for breaker-and-a-half and ring bus schemes, pushbutton control from the relay. • Auto-reclosing and synchrochecking. • Breaker arcing current. GE Multilin L30 Line Current Differential System...
  • Page 34: Ordering

    2.1.3 ORDERING a) OVERVIEW The L30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod- ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
  • Page 35 2 PRODUCT DESCRIPTION 2.1 INTRODUCTION Table 2–3: L30 ORDER CODES (HORIZONTAL UNITS) * - F - W/X Full Size Horizontal Mount BASE UNIT Base Unit MOUNT/COATING Horizontal (19” rack) Horizontal (19” rack) with harsh environmental coating FACEPLATE/ DISPLAY English display...
  • Page 36 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION The order codes for the reduced size vertical mount units with traditional CTs and VTs are shown below. Table 2–4: L30 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount BASE UNIT...
  • Page 37 RS422, 2 Channels c) ORDER CODES WITH PROCESS BUS MODULES The order codes for the horizontal mount units with the process bus module are shown below. Table 2–5: L30 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS) * - F - W/X...
  • Page 38 RS422, 2 Channels The order codes for the reduced size vertical mount units with the process bus module are shown below. Table 2–6: L30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount...
  • Page 39 2 PRODUCT DESCRIPTION 2.1 INTRODUCTION Table 2–6: L30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) POWER SUPPLY 125 / 250 V AC/DC power supply 24 to 48 V (DC only) power supply PROCESS BUS MODULE Eight-port digital process bus module...
  • Page 40: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the serial number of your existing unit. Not all replacement modules may be applicable to the L30 relay. Only the modules specified in the order codes are available as replacement modules.
  • Page 41 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels GE Multilin L30 Line Current Differential System 2-11...
  • Page 42: Pilot Channel Relaying

    (DTT) signal to all of the other L30 relays on the protected line. If a slave L30 relay issues a trip from one of its backup functions, it can send a transfer trip signal to its master and other slave relays if such option is designated.
  • Page 43: Channel Monitor

    2.2.2 CHANNEL MONITOR The L30 has logic to detect that the communications channel is deteriorating or has failed completely. This can provide an alarm indication and disable the current differential protection. Note that a failure of the communications from the master to a slave does not prevent the master from performing the current differential algorithm;...
  • Page 44: Loopback Test

    The L30 includes provision for sending and receiving a single-pole direct transfer trip (DTT) signal from current differential protection between the L30 relays at the line terminals using the pilot communications channel. The user may also initiate an additional eight pilot signals with an L30 communications channel to create trip, block, or signaling logic. A FlexLogic operand, an external contact closure, or a signal over the LAN communication channels can be assigned for that logic.
  • Page 45: Functionality

    Current differential protection: The current differential algorithms used in the L30 Line Current Differential System are based on the Fourier transform phaselet approach and an adaptive statistical restraint. The L30 uses per-phase differential at 64 kbps with two phaselets per cycle. A detailed description of the current differential algorithms is found in chapter 8.
  • Page 46: Other Functions

    PFLL Status Frequency Deviation Phase and Frequency Master Locked Loop (PFLL) Clock Phase Deviation PHASELETS TO REMOTE Communications Remote Relay PHASELETS FROM REMOTE Interface Direct Transfer Trip 831732A3.CDR Figure 2–3: L30 BLOCK DIAGRAM 2-16 L30 Line Current Differential System GE Multilin...
  • Page 47: Specifications

    0.00 to 600.00 s in steps of 0.01 < 20 ms at 3  pickup at 60 Hz Operate time: Operate at 1.5  pickup Timing accuracy: ±3% or ±4 ms (whichever is greater) GE Multilin L30 Line Current Differential System 2-17...
  • Page 48 2  CT rating: ±2.5% of reading Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01 Timing accuracy: ±3% of operate time or ±4 ms (whichever is greater) 2-18 L30 Line Current Differential System GE Multilin...
  • Page 49: User-Programmable Elements

    Test sequence 3: all LEDs on, one LED at a time off for 1 s Number of tests: 3, interruptible at any time Duration of full test: approximately 3 minutes GE Multilin L30 Line Current Differential System 2-19...
  • Page 50: Monitoring

    Storage capacity: (NN is dependent on memory) 1-second rate: 01 channel for NN days 16 channels for NN days  60-minute rate: 01 channel for NN days 16 channels for NN days 2-20 L30 Line Current Differential System GE Multilin...
  • Page 51: Metering

    1 sec. at 100 times rated continuous 4xInom; URs equipped with 24 CT inputs have a maximum operating temp. of 50°C Short circuit rating: 150000 RMS symmetrical amperes, 250 V maximum (primary current to external GE Multilin L30 Line Current Differential System 2-21...
  • Page 52: Power Supply

    Make and carry for 0.2 s: 30 A as per ANSI C37.90 Carry continuous: Break (DC inductive, L/R = 40 ms): VOLTAGE CURRENT 24 V 48 V 0.5 A 125 V 0.3 A 250 V 0.2 A 2-22 L30 Line Current Differential System GE Multilin...
  • Page 53 Note: values for 24 V and 48 V are the same due to a required 95% voltage drop across the load impedance. Operate time: < 0.6 ms Internal Limiting Resistor: 100 , 2 W GE Multilin L30 Line Current Differential System 2-23...
  • Page 54: Communications

    –30 dBm 29 dB Singlemode 1550 nm Laser, +5 dBm –30 dBm 35 dB Singlemode These power budgets are calculated from the manu- facturer’s worst-case transmitter power and worst NOTE case receiver sensitivity. 2-24 L30 Line Current Differential System GE Multilin...
  • Page 55: Environmental

    Pollution degree: impaired at temperatures less than – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days). GE Multilin L30 Line Current Differential System 2-25...
  • Page 56: Type Tests

    Safety UL508 e83849 NKCR Safety UL C22.2-14 e83849 NKCR7 Safety UL1053 e83849 NKCR 2.4.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. 2-26 L30 Line Current Differential System GE Multilin...
  • Page 57: Approvals

    To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. GE Multilin L30 Line Current Differential System 2-27...
  • Page 58 2.4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2-28 L30 Line Current Differential System GE Multilin...
  • Page 59: Hardware

    HORIZONTAL UNITS The L30 Line Current Differential System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 60 VERTICAL UNITS The L30 Line Current Differential System is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 61 RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. 11.015” 7.482” 1.329” 13.560” 15.000” 14.025” 4.000” 9.780” 843809A1.CDR Figure 3–4: L30 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin L30 Line Current Differential System...
  • Page 62 3.1 DESCRIPTION 3 HARDWARE Figure 3–5: L30 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For details on side mounting L30 devices with the enhanced front panel, refer to the following documents available online from the GE Multilin website. • GEK-113180: UR-series UR-V side-mounting front panel assembly instructions.
  • Page 63 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: L30 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin L30 Line Current Differential System...
  • Page 64: Module Withdrawal And Insertion

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the L30. L30 Line Current Differential System...
  • Page 65 When the clips have locked into position, the module will be fully inserted. CPU modules have 100Base-FX connectors. These connectors must be individually disconnected from the module before it can be removed from the chassis. NOTE GE Multilin L30 Line Current Differential System...
  • Page 66: Rear Terminal Layout

    (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. Figure 3–11: EXAMPLE OF MODULES IN F AND H SLOTS L30 Line Current Differential System GE Multilin...
  • Page 67: Wiring

    3 HARDWARE 3.2 WIRING 3.2WIRING 3.2.1 TYPICAL WIRING Figure 3–12: TYPICAL WIRING DIAGRAM GE Multilin L30 Line Current Differential System...
  • Page 68: Dielectric Strength

    (see the Self-test errors section in chapter 7) or control power is lost, the relay is de-energize. For high reliability systems, the L30 has a redundant option in which two L30 power supplies are placed in parallel on the bus.
  • Page 69: Ct And Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown below. Twisted-pair cabling on the zero-sequence CT is recommended. GE Multilin L30 Line Current Differential System 3-11...
  • Page 70 NOTE Current inputs Voltage inputs 8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) 842766A3.CDR Figure 3–15: CT/VT MODULE WIRING 3-12 L30 Line Current Differential System GE Multilin...
  • Page 71: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The L30 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bidirectional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 72 Logic operand driving the contact output should be given a reset delay of 10 ms to prevent damage of the output contact (in situations when the element initiating the contact output is bouncing, at val- ues in the region of the pickup value). 3-14 L30 Line Current Differential System GE Multilin...
  • Page 73 ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs GE Multilin L30 Line Current Differential System 3-15...
  • Page 74 ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used 3-16 L30 Line Current Differential System GE Multilin...
  • Page 75 3 HARDWARE 3.2 WIRING Figure 3–17: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) GE Multilin L30 Line Current Differential System 3-17...
  • Page 76 CONTACT IN COMMON SURGE 842763A2.CDR Figure 3–18: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe correct polarity for all contact input and solid state output connec- tions. 3-18 L30 Line Current Differential System GE Multilin...
  • Page 77 There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recom- mend using an external DC supply. NOTE GE Multilin L30 Line Current Differential System 3-19...
  • Page 78 CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–21: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto- burnish functionality using an oscilloscope. NOTE 3-20 L30 Line Current Differential System GE Multilin...
  • Page 79: Transducer Inputs And Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–22: TRANSDUCER INPUT/OUTPUT MODULE WIRING GE Multilin L30 Line Current Differential System 3-21...
  • Page 80: Rs232 Faceplate Port

    3.2.8 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the L30 faceplate for programming with a computer. All that is required to use this interface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
  • Page 81 This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the L30 COM terminal (#3); others function cor- rectly only if the common wire is connected to the L30 COM terminal, but insulated from the shield.
  • Page 82: Irig-B

    Using an amplitude modulated receiver causes errors up to 1 ms in event time-stamping. NOTE Using an amplitude modulated receiver also causes errors of up to 1 ms in metered synchrophasor values. NOTE 3-24 L30 Line Current Differential System GE Multilin...
  • Page 83: Pilot Channel Communications

    RS422, 1 channel RS422, 2 channels, 2 clock inputs RS422, 2 channels All of the fiber modules use ST type connectors. For two-terminal applications, each L30 relay requires at least one com- munications channel. GE Multilin L30 Line Current Differential System...
  • Page 84: Fiber: Led And Eled Transmitters

    The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module. Figure 3–28: LASER FIBER MODULES When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. 3-26 L30 Line Current Differential System GE Multilin...
  • Page 85: Interface

    Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw. GE Multilin L30 Line Current Differential System 3-27...
  • Page 86 For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). 3-28 L30 Line Current Differential System GE Multilin...
  • Page 87 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–33: G.703 DUAL LOOPBACK MODE GE Multilin L30 Line Current Differential System 3-29...
  • Page 88: Rs422 Interface

    (data module 1), connects to the clock inputs of the UR–RS422 interface in the usual fashion. In addition, the send timing outputs of data module 1 is also paralleled to the terminal timing inputs of data module 2. By using this con- 3-30 L30 Line Current Differential System GE Multilin...
  • Page 89 Figure 3–36: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION Data module 1 provides timing to the L30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they vary by manufacturer.
  • Page 90: Rs422 And Fiber Interface

    G.703 and fiber interfaces. When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. Figure 3–39: G.703 AND FIBER INTERFACE CONNECTION 3-32 L30 Line Current Differential System GE Multilin...
  • Page 91: Ieee C37.94 Interface

    For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured. GE Multilin L30 Line Current Differential System 3-33...
  • Page 92 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. Figure 3–40: IEEE C37.94 TIMING SELECTION SWITCH SETTING 3-34 L30 Line Current Differential System GE Multilin...
  • Page 93 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid GE Multilin L30 Line Current Differential System 3-35...
  • Page 94: C37.94Sm Interface

    For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured. 3-36 L30 Line Current Differential System GE Multilin...
  • Page 95 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. Figure 3–42: C37.94SM TIMING SELECTION SWITCH SETTING GE Multilin L30 Line Current Differential System 3-37...
  • Page 96 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid 3-38 L30 Line Current Differential System GE Multilin...
  • Page 97: Human Interfaces

    ENGAGING A DEVICE The EnerVista UR Setup software can be used in online mode (relay connected) to directly communicate with the L30 relay. Communicating relays are organized and grouped by communication interfaces and into sites. Sites can contain any num- ber of relays selected from the UR-series of relays.
  • Page 98 Site List window are automatically sent to the online communicating device. g) FIRMWARE UPGRADES The firmware of a L30 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
  • Page 99: Enervista Ur Setup Main Window

    Device data view windows, with common tool bar Settings file data view windows, with common tool bar Workspace area with data view tabs Status bar 10. Quick action hot links 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW GE Multilin L30 Line Current Differential System...
  • Page 100: Extended Enervista Ur Setup Features

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. L30 Line Current Differential System GE Multilin...
  • Page 101 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin L30 Line Current Differential System...
  • Page 102 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND L30 Line Current Differential System GE Multilin...
  • Page 103 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin L30 Line Current Differential System...
  • Page 104: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic equation. L30 Line Current Differential System GE Multilin...
  • Page 105 FlexLogic entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin L30 Line Current Differential System...
  • Page 106: Settings File Traceability

    When a settings file is transferred to a L30 device, the date, time, and serial number of the L30 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the L30 actual values at any later date to determine if security has been compromised.
  • Page 107 4.2 EXTENDED ENERVISTA UR SETUP FEATURES The transfer date of a setting file written to a L30 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 108 ONLINE DEVICE TRACEABILITY INFORMATION The L30 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 109: Faceplate Interface

    LED panel 2 LED panel 3 Display Front panel RS232 port Small user-programmable User-programmable Keypad (control) pushbuttons 1 to 7 pushbuttons 1 to 12 827801A7.CDR Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS GE Multilin L30 Line Current Differential System 4-13...
  • Page 110: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. 4-14 L30 Line Current Differential System GE Multilin...
  • Page 111 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every L30, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 112 LEDs on these panels. USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LEDS 842782A1.CDR Figure 4–20: LED PANELS 2 AND 3 (INDEX TEMPLATE) DEFAULT LABELS FOR LED PANEL 2: The default labels are intended to represent: 4-16 L30 Line Current Differential System GE Multilin...
  • Page 113: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational • The L30 settings have been saved to a settings file • The L30 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http:// www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed •...
  • Page 114 Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the L30 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
  • Page 115 4.3 FACEPLATE INTERFACE Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the L30 enhanced front panel and insert the custom labels. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay.
  • Page 116 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the L30 enhanced front panel and insert the custom labels.
  • Page 117 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This attaches the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. GE Multilin L30 Line Current Differential System 4-21...
  • Page 118 FEEDER MANAGEMENT RELAY 842722A1.CDR Place the left side of the customized module back to the front panel frame, then snap back the right side. Put the clear Lexan front cover back into place. 4-22 L30 Line Current Differential System GE Multilin...
  • Page 119: Display

    INTRODUCTION The L30 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, that can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic operand.
  • Page 120: Menus

    Each press of the MENU key advances through the following main heading pages: • Actual values • Settings • Commands • Targets • User displays (when enabled) 4-24 L30 Line Current Differential System GE Multilin...
  • Page 121 Properties. TIME: 1.0 s  To view the remaining settings associated with the Display Properties subheader, DEFAULT MESSAGE repeatedly press the MESSAGE DOWN key. The last message appears as shown. INTENSITY: 25% GE Multilin L30 Line Current Differential System 4-25...
  • Page 122: Changing Settings

    ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length, but user-defined in character. They can be upper case letters, lower case letters, numerals, and a selection of special characters. 4-26 L30 Line Current Differential System GE Multilin...
  • Page 123: Settings

    When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the In Service LED turns on. e) ENTERING INITIAL PASSWORDS The L30 supports password entry from a local or remote connection. GE Multilin L30 Line Current Differential System...
  • Page 124 When an incorrect command or setting password has been entered via the faceplate interface three times within a 3-minute time span, the FlexLogic operand is set to “On” and the L30 does not allow settings or command LOCAL ACCESS DENIED...
  • Page 125 FlexLogic operand is set to “On” and the REMOTE ACCESS DENIED L30 does not allow Settings or Command access via the any external communications interface for the next ten minutes. FlexLogic operand is set to “Off” after the expiration of the ten-minute timeout.
  • Page 126 4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4-30 L30 Line Current Differential System GE Multilin...
  • Page 127: Overview

    See page 5-71.  SYSTEM SETUP   POWER SYSTEM See page 5-72.   SIGNAL SOURCES See page 5-73.   87L POWER SYSTEM See page 5-76.   BREAKERS See page 5-82.  GE Multilin L30 Line Current Differential System...
  • Page 128  DIGITAL ELEMENTS See page 5-204.   DIGITAL COUNTERS See page 5-207.   MONITORING See page 5-209.  ELEMENTS  SETTINGS  CONTACT INPUTS See page 5-220.  INPUTS / OUTPUTS  L30 Line Current Differential System GE Multilin...
  • Page 129 See page 5-239.  FORCE CONTACT See page 5-240.  INPUTS  FORCE CONTACT See page 5-241.  OUTPUTS  CHANNEL TESTS See page 5-242.   PMU See page 5-242.  TEST VALUES GE Multilin L30 Line Current Differential System...
  • Page 130: Introduction To Elements

    RESET DELAY setting: This setting is used to set a time-delay-on-dropout, or off-delay, for the duration between the Operate output state and the return to logic 0 after the input transits outside the defined pickup range. L30 Line Current Differential System GE Multilin...
  • Page 131: Introduction To Ac Sources

    BACKGROUND The L30 may be used on systems with breaker-and-a-half or ring bus configurations. In these applications, each of the two three-phase sets of individual phase currents (one associated with each breaker) can be used as an input to a breaker fail- ure element.
  • Page 132 A summary of CT/VT module configurations is shown below. ITEM MAXIMUM NUMBER CT/VT Module CT Bank (3 phase channels, 1 ground channel) VT Bank (3 phase channels, 1 auxiliary channel) L30 Line Current Differential System GE Multilin...
  • Page 133: Overview

    CTs on each of two breakers is required to measure the winding current flow. GE Multilin L30 Line Current Differential System...
  • Page 134: Product Setup

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the L30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 135: Security Menu

    ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both commands and settings. NOTE If a remote connection is established, local passcodes are not visible. NOTE GE Multilin L30 Line Current Differential System...
  • Page 136  SUPERVISION  TIMEOUTS Range: 2 to 5 in steps of 1 INVALID ATTEMPTS MESSAGE BEFORE LOCKOUT: 3 Range: 5 to 60 minutes in steps of 1 PASSWORD LOCKOUT MESSAGE DURATION: 5 min 5-10 L30 Line Current Differential System GE Multilin...
  • Page 137 INVALID ATTEMPTS BEFORE LOCKOUT The L30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 138: Cybersentry Security

    Log in as outlined (Administrator or Supervisor, then Observer). Users After making any required changes, log off using the Commands > Relay Maintenance > Security menu. logged in through the front panel log out by logging in as None. 5-12 L30 Line Current Differential System GE Multilin...
  • Page 139 Whenever a new role is logged in, the user is prompted with a display to enter a password. 20 alphanumeric characters are acceptable as passwords.The UR device supports five roles. All roles have their corresponding passwords. The Observer role is the only role that does not require a password. GE Multilin L30 Line Current Differential System 5-13...
  • Page 140 PRODUCT SETUP SECURITY SESSION SETTINGS Range: 0 to 99  SESSION SESSION LOCKOUT:  SETTINGS Range: 0 to 9999 minutes SESSION LOCKOUT MESSAGE PERIOD: 3 min The following session settings are available. 5-14 L30 Line Current Differential System GE Multilin...
  • Page 141 Range: Enable, Disable FACTORY SERVICE: MESSAGE MODE: Disable  SELF TESTS See below MESSAGE  Range: Enable, Disable SUPERVISOR ROLE: MESSAGE Disable Range: 1 to 9999 minutes SERIAL INACTIVITY MESSAGE TIMEOUT: 3 GE Multilin L30 Line Current Differential System 5-15...
  • Page 142 Example: If this setting is "Yes" and an attempt is made to change settings or upgrade the firmware, the UR device denies the setting changes and denies upgrading the firmware. If this setting is "No", the UR device accepts setting changes and firmware upgrade. This role is disabled by default. 5-16 L30 Line Current Differential System GE Multilin...
  • Page 143 Settings Lock: If this setting is Enabled then an unauthorized write attempt to a setting for a given role activates this self test.      PATH: SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS FAILED AUTHENTICATE Range: Enabled, Disabled  FAILED FAILED AUTHENTICATE  AUTHENTICATE FUNCTION: Enabled GE Multilin L30 Line Current Differential System 5-17...
  • Page 144: Display Properties

    Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The L30 applies a cut- off value to the magnitudes and angles of the measured currents.
  • Page 145: Clear Relay Records

    CLEAR EVENT RECORDS: MESSAGE Range: FlexLogic operand CLEAR OSCILLOGRAPHY? MESSAGE Range: FlexLogic operand CLEAR DATA LOGGER: MESSAGE Range: FlexLogic operand CLEAR ARC AMPS 1: MESSAGE Range: FlexLogic operand CLEAR ARC AMPS 2: MESSAGE GE Multilin L30 Line Current Differential System 5-19...
  • Page 146: Communications

    Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma- ble pushbuttons to clear specific records are typical applications for these commands. Since the L30 responds to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
  • Page 147 0 ms The L30 is equipped with up to two independent serial communication ports. The faceplate RS232 port is intended for local use and is fixed at 19200 baud and no parity. The rear COM2 port is RS485. The RS485 port has settings for baud rate and parity.
  • Page 148 SCADA is provided through LAN2 and LAN3, to which P2 and respectively P3 are connected and configured to work in redundant mode. In this configuration, P3 uses the IP and MAC address of P2. Figure 5–5: MULTIPLE LANS, WITH REDUNDANCY 5-22 L30 Line Current Differential System GE Multilin...
  • Page 149 Range: Standard IPV4 address format PRT2 SUBNET IP MASK: MESSAGE 0.0.0.0 Range: Standard IPV4 address format PRT2 GWY IP ADDRESS: MESSAGE 0.0.0.0 Range: No, Yes PRT2 REDUNDANCY: MESSAGE Range: Enabled, Disabled PRT2 GOOSE ENABLED: MESSAGE Enabled GE Multilin L30 Line Current Differential System 5-23...
  • Page 150 MODBUS SLAVE ADDRESS grammed. For the RS485 port, each L30 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts resulting in errors will occur.
  • Page 151 DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP OTHER DEFAULT MESSAGE DEADBAND: 30000 Range: 1 to 10080 min. in steps of 1 DNP TIME SYNC IIN MESSAGE PERIOD: 1440 min GE Multilin L30 Line Current Differential System 5-25...
  • Page 152 TIMEOUT: 120 s The L30 supports the Distributed Network Protocol (DNP) version 3.0. The L30 can be used as a DNP slave device con- nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the L30 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the L30 at one time.
  • Page 153 DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the L30 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
  • Page 154 5.2 PRODUCT SETUP 5 SETTINGS master can operate a single point for both trip and close, or raise and lower, operations. The L30 can be configured to sup- port paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED CONTROL setting allows configuration of from 0 to 32 binary output paired controls.
  • Page 155 The L30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The L30 operates as an IEC 61850 server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
  • Page 156 IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In L30 releases previous to 5.0x, this name string was repre- sented by the setting.
  • Page 157 DESTINATION MAC address; the least significant bit of the first byte must be set. In L30 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the L30) and setting the multicast bit.
  • Page 158 The L30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 159 Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. GE Multilin L30 Line Current Differential System 5-33...
  • Page 160 MMXU1 HZ DEADBAND change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency. The L30 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the ...
  • Page 161 IEC61850 GOOSE ANALOG INPUT 1 UNITS The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The L30 must be rebooted (control power removed and re-applied) before these settings take effect.
  • Page 162 DNA and UserSt bit pairs that are included in GSSE messages. To set up a L30 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and “GGIO3.ST.Ind2.stVal”.
  • Page 163 CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta- tus values in the L30. Clients will still be able to connect to the server (L30 relay), but most data values will not be updated.
  • Page 164 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the L30 virtual inputs.
  • Page 165 GGIO4. When this value is NUMBER OF ANALOG POINTS changed, the L30 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly configured number of analog points.
  • Page 166 ITEM 64 attributes supported by the L30. Changes to the dataset will only take effect when the L30 is restarted. It is recommended to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1, GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
  • Page 167 XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1. GE Multilin L30 Line Current Differential System 5-41...
  • Page 168 Explorer or Firefox. This feature is available when the L30 has the Ethernet option installed. The web pages are organized as a series of menus that can be accessed starting at the L30 “Main Menu”. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on.
  • Page 169 5.2 PRODUCT SETUP The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the L30 over a network. The L30 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the L30 contains a list and description of all available files (event records, oscillography, etc.).
  • Page 170: Modbus User Map

    Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchroniz- ing time delivered to the relay. When the L30/L90 channel asymmetry function is used, the relay’s real time clock must be synchronized to an external time source using PTP or IRIG-B, typically from a global positioning system (GPS) receiver.
  • Page 171 Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchroniz- ing time delivered to the relay. When the L30/L90 channel asymmetry function is used, the relay’s real time clock must be synchronized to an external time source using PTP or IRIG-B, typically from a global positioning system (GPS) receiver.
  • Page 172 PP, the associated propagation delay and/or latency may not be compensated for, and the time received at the end-device could be in error by more than 100 µs. 5-46 L30 Line Current Differential System GE Multilin...
  • Page 173 Depending on the characteristics of the device to which the relay is directly linked, VLAN Priority may have no effect. • This setting applies to all of the relay’s PTP capable ports. GE Multilin L30 Line Current Differential System 5-47...
  • Page 174 GPS receiver to provide an accurate time. Both unicast and broadcast SNTP are supported. If SNTP functionality is enabled at the same time as IRIG-B, the IRIG-B signal provides the time value to the L30 clock for as long as a valid signal is present.
  • Page 175 DAYLIGHT SAVINGS TIME (DST) Note that when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and so the DST settings are ignored. GE Multilin L30 Line Current Differential System 5-49...
  • Page 176: Fault Reports

    MESSAGE Z0 ANGLE: 75° The L30 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as the characteristics of the line or feeder, are entered in this menu. The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in the FaultReport.txt file includes:...
  • Page 177 It should be kept in mind that grounding points in vicinity of the installation impact the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.). GE Multilin L30 Line Current Differential System 5-51...
  • Page 178: Oscillography

    64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. When changes are made to the oscillography settings, all existing oscillography records will be CLEARED. NOTE 5-52 L30 Line Current Differential System GE Multilin...
  • Page 179 IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. GE Multilin L30 Line Current Differential System 5-53...
  • Page 180: Data Logger

    436380 s 254460 s 3600000 ms 2727.5 235645200 s 340.9 29455200 s 26182800 s Changing any setting affecting data logger operation will clear any data that is currently in the log. NOTE 5-54 L30 Line Current Differential System GE Multilin...
  • Page 181: User-Programmable Leds

    LED TEST    PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS LED TEST Range: Disabled, Enabled.  LED TEST LED TEST FUNCTION:  Disabled Range: FlexLogic operand LED TEST CONTROL: MESSAGE GE Multilin L30 Line Current Differential System 5-55...
  • Page 182 (one LED on at a time) control input rising edge of the Wait 1 second control input rising edge STAGE 3 of the control (one LED off at a time) input 842011A1.CDR Figure 5–7: LED TEST SEQUENCE 5-56 L30 Line Current Differential System GE Multilin...
  • Page 183 LED column 2: user-programmable LEDs 1 through 12 • LED column 3: user-programmable LEDs 13 through 24 • LED column 4: user-programmable LEDs 25 through 36 • LED column 5: user-programmable LEDs 37 through 48 GE Multilin L30 Line Current Differential System 5-57...
  • Page 184: User-Programmable Self-Tests

    Range: Disabled, Enabled. SFP MODULE FAIL MESSAGE FUNCTION: Disabled All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Most of the minor alarms can be disabled if desired. 5-58 L30 Line Current Differential System GE Multilin...
  • Page 185: Control Pushbuttons

    The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–8: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the L30 is ordered with the twelve user- programmable pushbutton option. STATUS EVENT CAUSE...
  • Page 186 SYSTEM SETUP/ BREAKERS/BREAKER 1/ BREAKER 1 PUSHBUTTON CONTROL Enabled=1 TIMER FLEXLOGIC OPERAND SYSTEM SETUP/ BREAKERS/BREAKER 2/ CONTROL PUSHBTN 1 ON 100 msec BREAKER 2 PUSHBUTTON CONTROL 842010A2.CDR Enabled=1 Figure 5–10: CONTROL PUSHBUTTON LOGIC 5-60 L30 Line Current Differential System GE Multilin...
  • Page 187: User-Programmable Pushbuttons

    FlexLogic equations, protection elements, and control elements. Typical applications include breaker control, autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of password protection. The user-configurable pushbuttons for the enhanced faceplate are shown below. GE Multilin L30 Line Current Differential System 5-61...
  • Page 188 The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push- button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari- ous system disturbances that may cause transient assertion of the operating signals. NOTE 5-62 L30 Line Current Differential System GE Multilin...
  • Page 189 PUSHBTN 1 RESET • PUSHBTN 1 LOCAL: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset. GE Multilin L30 Line Current Differential System 5-63...
  • Page 190 “Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. 5-64 L30 Line Current Differential System GE Multilin...
  • Page 191 Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–13: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) GE Multilin L30 Line Current Differential System 5-65...
  • Page 192: Flex State Parameters

    PATH: SETTINGS PRODUCT SETUP FLEX STATE PARAMETERS Range: FlexLogic operand  FLEX STATE PARAMETER  PARAMETERS Range: FlexLogic operand PARAMETER MESSAGE Range: FlexLogic operand PARAMETER MESSAGE  Range: FlexLogic operand PARAMETER 256: MESSAGE 5-66 L30 Line Current Differential System GE Multilin...
  • Page 193: User-Definable Displays

    INVOKE AND SCROLL play, not at the first user-defined display. The pulses must last for at least 250 ms to take effect. INVOKE AND SCROLL GE Multilin L30 Line Current Differential System 5-67...
  • Page 194 While viewing a user display, press the ENTER key and then select the ‘Yes” option to remove the display from the user display list. Use the MENU key again to exit the user displays menu. 5-68 L30 Line Current Differential System GE Multilin...
  • Page 195: Installation

    "Programmed" state. UNIT NOT PROGRAMMED setting allows the user to uniquely identify a relay. This name will appear on generated reports. RELAY NAME GE Multilin L30 Line Current Differential System 5-69...
  • Page 196: Remote Resources Configuration

    Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the L30 process card and specific Brick. The relay is then configured to measure spe- cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 197: Ac Inputs

    1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). GE Multilin L30 Line Current Differential System 5-71...
  • Page 198: Power System

    ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be con- nected to system phases A, B, and C for correct operation. 5-72 L30 Line Current Differential System GE Multilin...
  • Page 199: Signal Sources

    FREQUENCY TRACKING frequency applications. NOTE The frequency tracking feature functions only when the L30 is in the “Programmed” mode. If the L30 is “Not Pro- grammed”, then metering values are available but can exhibit significant errors. NOTE The nominal system frequency should be selected as 50 Hz or 60 Hz only. The FREQUENCY AND PHASE REFERENCE setting, used as a reference for calculating all angles, must be identical for all terminals.
  • Page 200 An example of the use of sources is shown in the diagram below. A relay could have the following hardware configuration: INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 not applicable 5-74 L30 Line Current Differential System GE Multilin...
  • Page 201 Figure 5–17: EXAMPLE USE OF SOURCES Y LV D HV SRC 1 SRC 2 SRC 3 Phase CT F1+F5 None Ground CT None None Phase VT None None Aux VT None None GE Multilin L30 Line Current Differential System 5-75...
  • Page 202: L Power System

     TRANSFORMER Any changes to the L30 power system settings will change the protection system configuration. As such, the 87L protection at all L30 protection system terminals must be temporarily disabled to allow the relays to acknowledge the new settings.
  • Page 203 The effect of charging current compensation is viewed in the METERING  actual values menu. This effect is very dependent on CT and VT accuracy. NOTE 87L DIFFERENTIAL CURRENT GE Multilin L30 Line Current Differential System 5-77...
  • Page 204 LOCAL (TERMINAL 1 and TERMINAL 2) ID NUMBER: In installations using multiplexers or modems for communica- tion, it is desirable to ensure the data used by the relays protecting a given line comes from the correct relays. The L30 performs this check by reading the ID number contained in the messages sent by transmitting relays and comparing this ID to the programmed correct ID numbers by the receiving relays.
  • Page 205 • BLOCK GPS TIME REF: This setting signals to the L30 that the time reference is not valid. The time reference may be not accurate due to problems with the GPS receiver. The user must to be aware of the case when a GPS satellite receiver loses its satellite signal and reverts to its own calibrated crystal oscillator.
  • Page 206 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–19: CHANNEL ASYMMETRY COMPENSATION LOGIC 5-80 L30 Line Current Differential System GE Multilin...
  • Page 207 “None”) if there is no in-zone transformer connected. Only one in-zone transformer is allowed for both two-terminal and three-terminal applications. Enabling in-zone transformer functionality forces the L30 to automatically remove the zero-sequence component from all terminals currents. It also disables ground differential 87LG functional- ity and zero-sequence current removal functionality defined by the setting.
  • Page 208: Breakers

    Range: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled 5-82 L30 Line Current Differential System GE Multilin...
  • Page 209 1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the L30. The follow- ing settings are available for each breaker control element.
  • Page 210 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–21: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the L30 is in “Programmed” mode and not in the local control mode. NOTE 5-84 L30 Line Current Differential System...
  • Page 211 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–22: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2) GE Multilin L30 Line Current Differential System 5-85...
  • Page 212: Disconnect Switches

    For greater security in determination of the switch pole position, both the 52/a and 52/b auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches depends on the number of the CT/VT modules ordered with the L30. •...
  • Page 213 This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the L30 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin...
  • Page 214 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–23: DISCONNECT SWITCH SCHEME LOGIC 5-88 L30 Line Current Differential System GE Multilin...
  • Page 215: Flexcurves™

    1.03 pu. It is recommended to set the two times to a similar value; otherwise, the linear approximation may result in NOTE undesired behavior for the operating quantity that is close to 1.00 pu. GE Multilin L30 Line Current Differential System 5-89...
  • Page 216 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE 5-90 L30 Line Current Differential System GE Multilin...
  • Page 217 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the L30 are displayed in the following graphs. GE Multilin L30 Line Current Differential System...
  • Page 218 842723A1.CDR Figure 5–27: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–28: RECLOSER CURVES GE113, GE120, GE138 AND GE142 5-92 L30 Line Current Differential System GE Multilin...
  • Page 219 Figure 5–29: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–30: RECLOSER CURVES GE131, GE141, GE152, AND GE200 GE Multilin L30 Line Current Differential System 5-93...
  • Page 220 Figure 5–31: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–32: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 5-94 L30 Line Current Differential System GE Multilin...
  • Page 221 Figure 5–33: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–34: RECLOSER CURVES GE119, GE135, AND GE202 GE Multilin L30 Line Current Differential System 5-95...
  • Page 222: Phasor Measurement Unit

    Synchrophasors from different locations within the power system are networked to a central location. The L30 offers PMU features over two communication standards, IEC61850-9-5 and C37.118. The complete Synchropha- sor implementation for Firmware version 7.0 is shown in the figure below.
  • Page 223 Precise time input to the relay from the international time standard, via either IRIG-B or PTP, is vital for correct syn- chrophasor measurement and reporting. For IRIG-B, a DC level shift IRIG-B receiver must be used for the phasor measurement unit to output proper synchrophasor values. NOTE GE Multilin L30 Line Current Differential System 5-97...
  • Page 224 The number of descriptions are equal to the number of bits configured in the 16 bit digital status word. All bitstrings less than or equal to 32 bits in length map into a 32 bit bitstring in an IEC 61850-90-5 dataset. NOTE 5-98 L30 Line Current Differential System GE Multilin...
  • Page 225 From each PMU the user selects the phasor information of interest that is mapped into the selected aggregator datset(s). For version 7.0 only FCDA data is supported. Figure 5–38: DATA SET CREATED FROM USER SELECTED INTERNAL ITEMS GE Multilin L30 Line Current Differential System 5-99...
  • Page 226 CONFIGURATION EXAMPLE: CFG-2 BASED CONFIGURATION (USING IEC61850-90-5) The L30 is expected to send the CFG-2 file (IEEE C37.118 config. file) upon request from the upstream synchrophasor devices (e.g., P30) without stopping R-SV multicasting, see figure below. The primary domain controller (PDC) does not need to use a stop/start data stream command if the UR protocol is set to IEC61850-90-5 prior to requesting the configura- tion via CFG-2 (IEEE C37.118 config.
  • Page 227  UNIT 1  CONFIGURATION  PMU 1 See page 5-105. MESSAGE  CALIBRATION  PMU 1 See page 5-106. MESSAGE  TRIGGERING  PMU 1 See page 5-113. MESSAGE  RECORDING GE Multilin L30 Line Current Differential System 5-101...
  • Page 228 Range: Available FlexLogic operands PMU 1 D-CH-1: MESSAGE Default: Off Range: 16 character ASCII string PMU 1 D-CH-1 MESSAGE Default: DigChannel1 NAME: DigChannel1 Range: Off, On PMU 1 D-CH-1 MESSAGE Default: Off NORMAL STATE: Off 5-102 L30 Line Current Differential System GE Multilin...
  • Page 229 • PMU 1 SIGNAL SOURCE: This setting specifies one of the available L30 signal sources for processing in the PMU. Note that any combination of voltages and currents can be configured as a source. The current channels could be con- figured as sums of physically connected currents.
  • Page 230 5 SETTINGS (50 Hz), the L30 will generate a reporting mismatch message if the selected rate is not set as 10 Hz, 12 Hz, 15 Hz, 20 Hz, 30 Hz, 60 Hz, or 120 Hz (or 10 Hz, 25 Hz, 50 Hz or 100 Hz when the system frequency is 50 Hz) when entered via the keypad or software;...
  • Page 231 VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the true signal. GE Multilin L30 Line Current Differential System 5-105...
  • Page 232 When receiving synchrophasor date at multiple locations, with possibly different reference nodes, it may be more beneficial to allow the central locations to perform the compensation of sequence voltages. This setting applies to PMU data only. The L30 calculates symmetrical voltages independently for protection and control purposes without applying this correction.
  • Page 233 L30 standards. This element requires the frequency is above the minimum measurable value. If the frequency is below this value, such as when the circuit is de-energized, the trigger will drop out.
  • Page 234 PMU 1 VOLT TRIGGER LOW-VOLT: This setting specifies the low threshold for the abnormal voltage trigger, in per- unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The comparator applies a 3% hysteresis. 5-108 L30 Line Current Differential System GE Multilin...
  • Page 235 PMU source. A value of 1 pu is a nominal primary current. The comparator applies a 3% hysteresis. • PMU 1 CURR TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces- sary triggering of the recorder. GE Multilin L30 Line Current Differential System 5-109...
  • Page 236 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator applies a 3% hysteresis. 5-110 L30 Line Current Differential System GE Multilin...
  • Page 237 S > APPARENT PICKUP APPARENT POWER, SB S > APPARENT PICKUP APPARENT POWER, SC S > APPARENT PICKUP 3P APPARENT POWER, S S > 3*(APPARENT PICKUP) 847003A1.CDR Figure 5–45: POWER TRIGGER SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-111...
  • Page 238 PMU 1 df/dt TRIGGER DPO TIME: PMU 1 SIGNAL FLEXLOGIC OPERAND SOURCE: df/dt > RAISE PMU 1 ROCOF TRIGGER ROCOF, df/dt –df/dt > FALL 847000A1.CDR Figure 5–46: RATE OF CHANGE OF FREQUENCY TRIGGER SCHEME LOGIC 5-112 L30 Line Current Differential System GE Multilin...
  • Page 239 When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None will be set to the last protocol saved (i.e., C37.118 or IEC61850-90-5) to any aggregators, as both C37.118 and IEC61850-90-5 simultaineous streaming of both R-SV values is not possible. NOTE GE Multilin L30 Line Current Differential System 5-113...
  • Page 240 AGTR1 PDC CNTRL 3 Phasor data concentrator asserts control bit 3 as received via the network.  as above AGTR1 PDC CNTRL 16 Phasor data concentrator asserts control bit 16, as received via the network. 5-114 L30 Line Current Differential System GE Multilin...
  • Page 241 Default: 4 Range: 0 to 252 MSVCB 1 IP CLASS: MESSAGE Default: 46 Range: 0 to 4095 MSVCB 1 VID: MESSAGE Default: 0 Range: 0 to 16383 MSVCB 1 APPID: MESSAGE Default: 0 GE Multilin L30 Line Current Differential System 5-115...
  • Page 242 MSVCB 1 Security: This setting selects what level of security and authentication is used, see table below, and is in the form of an enumeration as per standard. The range is 1, 2 and 3. Shaded settings in table below are not supported in firmware 7.0. ENUMERATION AUTHENTICATION ENCRYPTION NOTE 5-116 L30 Line Current Differential System GE Multilin...
  • Page 243 NETWORK UDP PORT 1: This setting selects the first UDP port that will be used for network reporting. • NETWORK UDP PORT 2: This setting selects the second UDP port that will be used for network reporting. GE Multilin L30 Line Current Differential System 5-117...
  • Page 244: Introduction To Flexlogic

    Figure 5–48: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the L30 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an ele- ment from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.
  • Page 245 Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–9: L30 FLEXLOGIC OPERAND TYPES OPERAND TYPE STATE...
  • Page 246 Exceeded maximum CRC error threshold on channel 2 87L DIFF CH1 ID FAIL The ID check for a peer L30 on channel 1 has failed 87L DIFF CH2 ID FAIL The ID check for a peer L30 on channel 2 has failed...
  • Page 247 5 SETTINGS 5.5 FLEXLOGIC Table 5–10: L30 FLEXLOGIC OPERANDS (Sheet 2 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: BREAKER 1 OFF CMD Breaker 1 open command initiated Breaker control BREAKER 1 ON CMD Breaker 1 close command initiated BREAKER 1 A BAD ST...
  • Page 248 5.5 FLEXLOGIC 5 SETTINGS Table 5–10: L30 FLEXLOGIC OPERANDS (Sheet 3 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: NEG SEQ OV1 PKP Negative-sequence overvoltage element has picked up Negative-sequence NEG SEQ OV1 DPO Negative-sequence overvoltage element has dropped out...
  • Page 249 5 SETTINGS 5.5 FLEXLOGIC Table 5–10: L30 FLEXLOGIC OPERANDS (Sheet 4 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: PHASE UV1 PKP At least one phase of phase undervoltage 1 has picked up Phase undervoltage PHASE UV1 OP At least one phase of phase undervoltage 1 has operated...
  • Page 250 5.5 FLEXLOGIC 5 SETTINGS Table 5–10: L30 FLEXLOGIC OPERANDS (Sheet 5 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: SWITCH 1 OFF CMD Disconnect switch 1 open command initiated Disconnect switch SWITCH 1 ON CMD Disconnect switch 1 close command initiated SWITCH 1 A BAD ST...
  • Page 251 5 SETTINGS 5.5 FLEXLOGIC Table 5–10: L30 FLEXLOGIC OPERANDS (Sheet 6 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION INPUTS/OUTPUTS: Direct I/P 1-1 On (appears only when an inter-relay communications card is used)   Direct input Direct I/P 1-8 On...
  • Page 252 5.5 FLEXLOGIC 5 SETTINGS Table 5–10: L30 FLEXLOGIC OPERANDS (Sheet 7 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION RESETTING RESET OP Reset command is operated (set by all three operands below). RESET OP (COMMS) Communications source of the reset command.
  • Page 253: Flexlogic Rules

    When making changes to settings, all FlexLogic equations are re-compiled whenever any new setting value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic during testing, for example, it is suggested to power the unit down and then back up. GE Multilin L30 Line Current Differential System 5-127...
  • Page 254: Flexlogic Example

    Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–50: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS 5-128 L30 Line Current Differential System GE Multilin...
  • Page 255 Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." GE Multilin L30 Line Current Differential System 5-129...
  • Page 256 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". 5-130 L30 Line Current Differential System GE Multilin...
  • Page 257 In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) GE Multilin L30 Line Current Differential System 5-131...
  • Page 258: Flexlogic Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". 5-132 L30 Line Current Differential System GE Multilin...
  • Page 259: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. GE Multilin L30 Line Current Differential System 5-133...
  • Page 260 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS 5-134 L30 Line Current Differential System GE Multilin...
  • Page 261 DIRECTION = Under; FLEXELEMENT INPUT MODE = Signed; FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Absolute; FlexElement 1 OpSig 842706A2.CDR Figure 5–58: FLEXELEMENT INPUT MODE SETTING GE Multilin L30 Line Current Differential System 5-135...
  • Page 262 “Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. 5-136 L30 Line Current Differential System GE Multilin...
  • Page 263: Non-Volatile Latches

    Off=0 LATCH 1 ON Dominant LATCH 1 OFF Previous Previous SETTING State State LATCH 1 SET: Off=0 RESET 842005A1.CDR Figure 5–59: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin L30 Line Current Differential System 5-137...
  • Page 264: Overview

      PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) LINE DIFFERENTIAL ELEMENTS  LINE DIFFERENTIAL  CURRENT See page 5-139.  ELEMENTS  DIFFERENTIAL  STUB BUS See page 5-143. MESSAGE  5-138 L30 Line Current Differential System GE Multilin...
  • Page 265 This CURRENT DIFF SIGNAL SOURCE 1 CURRENT DIFF SIGNAL SOURCE 4 source is mandatory and is assigned with the   menu. SYSTEM SETUP SIGNAL SOURCES SOURCE 1 GE Multilin L30 Line Current Differential System 5-139...
  • Page 266 If set to “Per phase”, the L30 performs inrush inhibit individually in each phase. – If set to “2-out-of-3”, the L30 checks second harmonic level in all three phases individually. If any two phases establish an inhibiting condition, then the remaining phase is restrained automatically.
  • Page 267 CURRENT DIFF DTT: This setting enables and disables the sending of a DTT by the current differential element on per single-phase basis to remote devices. To allow the L30 to restart from master-master to master-slave mode (very important on three-terminal applications), must be set to “Enabled”.
  • Page 268 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–60: CURRENT DIFFERENTIAL SCHEME LOGIC 5-142 L30 Line Current Differential System GE Multilin...
  • Page 269 The assigned current element should be mapped to appropriate output contact(s) to trip the stub bus breakers. It should be blocked unless disconnect is open. To prevent 87L tripping from remote L30 relays still protecting the line, the auxiliary contact of line disconnect switch (logic “1” when line switch is open) should be assigned to block the local 87L function by using the setting.
  • Page 270: Phase Current

     PHASE IOC1 See page 5-152. MESSAGE   PHASE IOC2 See page 5-152. MESSAGE   PHASE See page 5–153. MESSAGE  DIRECTIONAL 1  PHASE See page 5–153. MESSAGE  DIRECTIONAL 2 5-144 L30 Line Current Differential System GE Multilin...
  • Page 271 The “Timed” selection can be used where the relay must coordinate with electromechanical relays. GE Multilin L30 Line Current Differential System 5-145...
  • Page 272 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 5-146 L30 Line Current Differential System GE Multilin...
  • Page 273 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 GE Multilin L30 Line Current Differential System 5-147...
  • Page 274 0.197 0.859 0.569 0.419 0.368 0.341 0.325 0.314 0.307 0.301 0.296 1.145 0.759 0.559 0.490 0.455 0.434 0.419 0.409 0.401 0.394 10.0 1.431 0.948 0.699 0.613 0.569 0.542 0.524 0.511 0.501 0.493 5-148 L30 Line Current Differential System GE Multilin...
  • Page 275 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The L30 uses the FlexCurve feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve section in this chapter for additional details. GE Multilin...
  • Page 276 ‘Mvr’ times the setting. If the voltage restraint feature PHASE TOC1 PICKUP is disabled, the pickup level always remains at the setting value. 5-150 L30 Line Current Differential System GE Multilin...
  • Page 277 PHASE TOC1 C DPO Multiplier-Phase C PHASE TOC1 C OP SETTING PHASE TOC1 PKP PHASE TOC1 VOLT RESTRAINT: PHASE TOC1 OP Enabled PHASE TOC1 DPO 827072A4.CDR Figure 5–63: PHASE TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-151...
  • Page 278 PHASE IOC1 PKP SETTING PHASE IOC1 OP PHASE IOC1 BLOCK-B: PHASE IOC1 DPO Off = 0 SETTING 827033A6.VSD PHASE IOC1 BLOCK-C: Off = 0 Figure 5–64: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC 5-152 L30 Line Current Differential System GE Multilin...
  • Page 279 CTs and the line-line voltage from the VTs, based on the 90° or quadrature connection. If there is a requirement to supervise overcurrent elements for flows in opposite directions, such as can happen through a bus-tie breaker, two phase directional elements should be programmed with opposite element characteristic angle (ECA) settings. GE Multilin L30 Line Current Differential System 5-153...
  • Page 280 10 ms must be added to all the instantaneous protection elements under the supervi- sion of the phase directional element. If current reversal is of a concern, a longer delay – in the order of 20 ms – may be needed. 5-154 L30 Line Current Differential System GE Multilin...
  • Page 281: Neutral Current

     NEUTRAL IOC1 See page 5-157. MESSAGE   NEUTRAL IOC2 See page 5-157. MESSAGE   NEUTRAL See page 5–158. MESSAGE  DIRECTIONAL 1  NEUTRAL See page 5–158. MESSAGE  DIRECTIONAL 2 GE Multilin L30 Line Current Differential System 5-155...
  • Page 282 NEUTRAL TOC1 PKP RESET: NEUTRAL TOC1 IN ≥ PICKUP NEUTRAL TOC1 DPO SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A3.VSD Figure 5–67: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC 5-156 L30 Line Current Differential System GE Multilin...
  • Page 283 RESET DELAY : SETTING NEUTRAL IOC1 DPO NEUTRAL IOC1 OP 3( _0 - K _1 ) PICKUP NEUTRAL IOC1 BLOCK: Off=0 SETTING NEUTRAL IOC1 SOURCE: 827035A4.CDR Figure 5–68: NEUTRAL IOC1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-157...
  • Page 284     (EQ 5.19) – The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions. 5-158 L30 Line Current Differential System GE Multilin...
  • Page 285 REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation) The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other protection elements. GE Multilin L30 Line Current Differential System 5-159...
  • Page 286 The polarizing voltage can be programmed to be either the zero-sequence voltage calculated from the phase voltages ("Calculated V0") or supplied externally as an auxiliary voltage ("Measured VX"). 5-160 L30 Line Current Differential System GE Multilin...
  • Page 287 NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique for the “Calculated 3I0” mode of operation. GE Multilin L30 Line Current Differential System 5-161...
  • Page 288: Ground Current

     GROUND TOC1 See page 5-163.    GROUND TOC2 See page 5-163. MESSAGE   GROUND IOC1 See page 5-164. MESSAGE   GROUND IOC2 See page 5-164. MESSAGE  5-162 L30 Line Current Differential System GE Multilin...
  • Page 289 GROUND TOC 1 SETTING GROUND TOC1 PKP RESET: GROUND TOC1 IG ≥ PICKUP GROUND TOC1 DPO SOURCE: GROUND TOC1 OP SETTING GROUND TOC1 BLOCK: 827036A3.VSD Off = 0 Figure 5–71: GROUND TOC1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-163...
  • Page 290 Enabled = 1 SETTING DELAY: GROUND IOC1 GROUND IOC1 RESET SETTING PICKUP: DELAY: GROUND IOC1 SOURCE: IG ≥ PICKUP SETTING GROUND IOC1 BLOCK: 827037A4.VSD Off = 0 Figure 5–72: GROUND IOC1 SCHEME LOGIC 5-164 L30 Line Current Differential System GE Multilin...
  • Page 291: Negative Sequence Current

    < NEG SEQ PICKUP NEG SEQ TOC1 DPO NEG SEQ TOC1 BLOCK: NEG SEQ TOC1 OP Off=0 SETTING NEG SEQ TOC1 SOURCE: Neg Seq 827057A4.CDR Figure 5–73: NEGATIVE SEQUENCE TOC1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-165...
  • Page 292 SETTING NEG SEQ IOC1 DPO NEG SEQ IOC1 OP _2 - K _1 PICKUP NEG SEQ IOC1 BLOCK: Off=0 SETTING NEG SEQ IOC1 SOURCE: 827058A5.CDR Figure 5–74: NEGATIVE SEQUENCE IOC1 SCHEME LOGIC 5-166 L30 Line Current Differential System GE Multilin...
  • Page 293: Breaker Failure

    Range: 0.001 to 30.000 pu in steps of 0.001 BF1 N AMP HISET MESSAGE PICKUP: 1.050 pu Range: 0.001 to 30.000 pu in steps of 0.001 BF1 PH AMP LOSET MESSAGE PICKUP: 1.050 pu GE Multilin L30 Line Current Differential System 5-167...
  • Page 294 5-168 L30 Line Current Differential System GE Multilin...
  • Page 295 BREAKER FAILURE TIMER No. 2 (±1/8 cycle) INITIATE (1/8 cycle) BREAKER FAILURE CURRENT DETECTOR PICKUP (1/8 cycle) BREAKER FAILURE OUTPUT RELAY PICKUP (1/4 cycle) FAULT cycles OCCURS 827083A6.CDR Figure 5–75: BREAKER FAILURE MAIN PATH SEQUENCE GE Multilin L30 Line Current Differential System 5-169...
  • Page 296 In microprocessor relays this time is not significant. In L30 relays, which use a Fourier transform, the calculated current magnitude will ramp-down to zero one power frequency cycle after the current is interrupted, and this lag should be included in the overall margin duration, as it occurs after current interruption.
  • Page 297 Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be given via output operand BKR FAIL 1 TRIP OP GE Multilin L30 Line Current Differential System 5-171...
  • Page 298 5.6 GROUPED ELEMENTS 5 SETTINGS SINGLE-POLE BREAKER FAILURE, INITIATE Figure 5–77: SINGLE-POLE BREAKER FAILURE, TIMERS 5-172 L30 Line Current Differential System GE Multilin...
  • Page 299 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–78: THREE-POLE BREAKER FAILURE, INITIATE GE Multilin L30 Line Current Differential System 5-173...
  • Page 300 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–79: THREE-POLE BREAKER FAILURE, TIMERS 5-174 L30 Line Current Differential System GE Multilin...
  • Page 301: Voltage Elements

    ------------------ –   pickup where: T = operating time D = undervoltage delay setting (D = 0.00 operates instantaneously) V = secondary voltage applied to the relay = pickup level pickup GE Multilin L30 Line Current Differential System 5-175...
  • Page 302 The minimum voltage setting selects the operating voltage below which the element is blocked (a setting of “0” will allow a dead source to be considered a fault condition). 5-176 L30 Line Current Differential System GE Multilin...
  • Page 303 The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as cal- culated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below. GE Multilin L30 Line Current Differential System 5-177...
  • Page 304 There are three negative-sequence overvoltage elements available. The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed phase sequence of voltage, or a non-symmetrical system voltage condition. 5-178 L30 Line Current Differential System GE Multilin...
  • Page 305 AUX UV1 EVENTS: MESSAGE Disabled The L30 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt- age conditions of the auxiliary voltage. The selects the voltage level at which the time undervoltage ele- AUX UV1 PICKUP ment starts timing.
  • Page 306 AUX OV1 EVENTS: MESSAGE Disabled The L30 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM ...
  • Page 307 Off=0 DELAY : FLEXLOGIC OPERANDS < Vx Pickup AUX OV1 OP SETTING AUX OV1 DPO AUX OV1 SIGNAL AUX OV1 PKP SOURCE: AUXILIARY VOLT (Vx) 827836A2.CDR Figure 5–85: AUXILIARY OVERVOLTAGE SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-181...
  • Page 308: Supervising Elements

    DD CONTROL LOGIC: This setting is used to prevent operation of I_0 and I_2 logic of disturbance detector during conditions such as single breaker pole being open which leads to unbalanced load current in single-pole tripping schemes. Breaker auxiliary contact can be used for such scheme. 5-182 L30 Line Current Differential System GE Multilin...
  • Page 309 OR LOWER) IN 0.02 pu SETTING FLEXLOGIC OPERAND STEPS USING THE HIGHEST VALUE OF 50DD SV DD LOGIC I_0 AND I_2. SEAL-IN: Off=0 SETTING DD NON-CURRENT SUPV: Off=0 827044A6.CDR Figure 5–86: DISTURBANCE DETECTOR SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-183...
  • Page 310: Overview

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-184 L30 Line Current Differential System GE Multilin...
  • Page 311 TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–88: TRIP BUS LOGIC GE Multilin L30 Line Current Differential System 5-185...
  • Page 312: Setting Groups

    The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 5-186 L30 Line Current Differential System GE Multilin...
  • Page 313: Selector Switch

    SELECTOR 1 3BIT ACK: MESSAGE Range: Restore, Synchronize, Sync/Restore SELECTOR 1 POWER-UP MESSAGE MODE: Restore Range: Self-reset, Latched, Disabled SELECTOR 1 TARGETS: MESSAGE Self-reset Range: Disabled, Enabled SELECTOR 1 EVENTS: MESSAGE Disabled GE Multilin L30 Line Current Differential System 5-187...
  • Page 314 SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con- trol word pre-selects the position using the following encoding convention: POSITION rest 5-188 L30 Line Current Differential System GE Multilin...
  • Page 315 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. GE Multilin L30 Line Current Differential System 5-189...
  • Page 316 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–90: TIME-OUT MODE 5-190 L30 Line Current Differential System GE Multilin...
  • Page 317 Make the following changes to selector switch element in the    SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 GE Multilin L30 Line Current Differential System 5-191...
  • Page 318 SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–92: SELECTOR SWITCH LOGIC 5-192 L30 Line Current Differential System GE Multilin...
  • Page 319: Underfrequency

    ≤ 0 < f PICKUP UNDERFREQ 1 OP UNDERFREQ 1 ACTUAL VALUES MIN VOLT / AMP: UNDERFREQ 1 SOURCE: ≥ Level Minimum VOLT / AMP Frequency 827079A8.CDR Figure 5–93: UNDERFREQUENCY SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-193...
  • Page 320: Synchrocheck

    F. This time can be calculated by: ------------------------------- - (EQ 5.22) 360 ----------------- -  F 2   where: = phase angle difference in degrees; F = frequency difference in Hz. 5-194 L30 Line Current Differential System GE Multilin...
  • Page 321 COMBINATION SOURCE Y SOURCE Z Phase VTs and Phase VTs and Phase Phase Auxiliary VT Auxiliary VT Phase VTs and Phase VT Phase Phase Auxiliary VT Phase VT Phase VT Phase Phase GE Multilin L30 Line Current Differential System 5-195...
  • Page 322 The relay will use the phase channel of a three-phase set of voltages if pro- grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. 5-196 L30 Line Current Differential System GE Multilin...
  • Page 323 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–94: SYNCHROCHECK SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-197...
  • Page 324: Autoreclose

    4.000 s Range: FlexLogic™ operand AR1 ADD DELAY 1: MESSAGE Range: 0.00 to 655.35 s in steps of 0.01 AR1 DELAY 1: MESSAGE 0.000 s Range: FlexLogic™ operand AR1 ADD DELAY 2: MESSAGE 5-198 L30 Line Current Differential System GE Multilin...
  • Page 325 Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs: • The maximum shot number was reached. • A ‘Block’ input is in effect (for instance; Breaker Failure, bus differential protection operated, etc.). L30 Line Current Differential System 5-199 l t i l i n...
  • Page 326 ‘reclose-in-progress’ state. If all condi- tions allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. This timer must be set to a delay less than the reset timer. NOTE 5-200 L30 Line Current Differential System GE Multilin...
  • Page 327 5 SETTINGS 5.7 CONTROL ELEMENTS To sheet 2 Figure 5–95: AUTORECLOSURE SCHEME LOGIC (Sheet 1 of 2) GE Multilin L30 Line Current Differential System 5-201...
  • Page 328 5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–96: AUTORECLOSURE SCHEME LOGIC (Sheet 2 of 2) 5-202 L30 Line Current Differential System GE Multilin...
  • Page 329 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–97: SINGLE SHOT AUTORECLOSING SEQUENCE - PERMANENT FAULT GE Multilin L30 Line Current Differential System 5-203...
  • Page 330: Digital Elements

    Some versions of the digital input modules include an active voltage monitor circuit connected across form-A contacts. The voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for form-A). 5-204 L30 Line Current Differential System GE Multilin...
  • Page 331 The settings to use digital element 1 to monitor the breaker trip circuit are indicated below (EnerVista UR Setup example shown): The PICKUP DELAY setting should be greater than the operating time of the breaker to avoid nuisance alarms. NOTE GE Multilin L30 Line Current Differential System 5-205...
  • Page 332 “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). Figure 5–100: TRIP CIRCUIT EXAMPLE 2 The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and solid-state contact with voltage monitoring. NOTE 5-206 L30 Line Current Differential System GE Multilin...
  • Page 333: Digital Counters

    –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic operand for blocking the counting operation. All counter operands are blocked. GE Multilin L30 Line Current Differential System 5-207...
  • Page 334 COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–101: DIGITAL COUNTER SCHEME LOGIC 5-208 L30 Line Current Differential System GE Multilin...
  • Page 335: Monitoring Elements

    1000 kA2-cyc Range: FlexLogic™ operand BKR 1 ARC AMP BLOCK: MESSAGE Range: Self-reset, Latched, Disabled BKR 1 ARC AMP MESSAGE TARGET: Self-reset Range: Disabled, Enabled BKR 1 ARC AMP MESSAGE EVENTS: Disabled GE Multilin L30 Line Current Differential System 5-209...
  • Page 336 BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. Breaker Contacts Initiate Extinguished Part Total Area = Breaker Arcing Current (kA·cycle) Programmable 100 ms Start Delay Start Stop Integration Integration Figure 5–102: ARCING CURRENT MEASUREMENT 5-210 L30 Line Current Differential System GE Multilin...
  • Page 337 BKR 1 ARCING AMP C Φ 827071A3.CDR BKR 1 OPERATING TIME A Φ BKR 1 OPERATING TIME B Φ BKR 1 OPERATING TIME C Φ BKR 1 OPERATING TIME Figure 5–103: BREAKER ARCING CURRENT SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-211...
  • Page 338 CT FAIL 3I0 INPUT 2 PICKUP: This setting selects the 3I_0 pickup value for input 2 (different CT input) of the relay. • CT FAIL 3V0 INPUT: This setting selects the voltage source. 5-212 L30 Line Current Differential System GE Multilin...
  • Page 339 An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized; positive- sequence voltage and current are both below threshold levels. The function setting enables and disables the fuse failure feature for each source. GE Multilin L30 Line Current Differential System 5-213...
  • Page 340 20 c cles Enabled = 1 SOURCE FLEX-A ALOG 3V_0(3rd Harmonic) SRC1 3V0 3rd Harmonic Note 3V_0 is the sample summation 827093AN.CDR of Va, Vb, and Vc. Figure 5–105: VT FUSE FAIL SCHEME LOGIC 5-214 L30 Line Current Differential System GE Multilin...
  • Page 341 • BROKEN CONDUCTOR 1 PKP DELAY: This setting specifies the pickup time delay for this function to operate after assertion of the broken conductor pickup FlexLogic operand. GE Multilin L30 Line Current Differential System 5-215...
  • Page 342 5 cycles is less than 10% of the base current. If this current is greater or equal than 10% than the base current, then the hot curve characteristic is applied. 5-216 L30 Line Current Differential System GE Multilin...
  • Page 343    ---------------------------- -  (EQ 5.25)     – In the above equation, • τ = thermal protection trip time constant. • is a minimum reset time setting GE Multilin L30 Line Current Differential System 5-217...
  • Page 344 IEC255-8 cold curve or hot curve equations. op(In) • is the reset time calculated at index n as per the reset time equation. rst(In) • is the measured overload RMS current at index n. 5-218 L30 Line Current Differential System GE Multilin...
  • Page 345 30 minutes Busbar 60 minutes 20 minutes Underground cable 20 to 60 minutes 60 minutes The logic for the thermal overload protection element is shown below. Figure 5–108: THERMAL OVERLOAD PROTECTION SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-219...
  • Page 346: Contact Inputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the L30 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 347 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. GE Multilin L30 Line Current Differential System 5-221...
  • Page 348: Virtual Inputs

    “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) SETTING Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–110: VIRTUAL INPUTS SCHEME LOGIC 5-222 L30 Line Current Differential System GE Multilin...
  • Page 349: Contact Outputs

    The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the L30 using the FlexLogic operand to seal-in the contact output as follows: CONT OP 1 ION “Cont Op 1"...
  • Page 350 5 SETTINGS The L30 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop- ulates the setting menu accordingly.
  • Page 351: Virtual Outputs

    Logic equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings would be programmed as follows: GE Multilin L30 Line Current Differential System 5-225...
  • Page 352: Remote Devices

    32 “DNA” bit pairs that represent the state of two pre-defined events and 30 user-defined events. All remaining bit pairs are “UserSt” bit pairs, which are status bits representing user-definable events. The L30 implementation provides 32 of the 96 available UserSt bit pairs.
  • Page 353: Remote Inputs

    5.8 INPUTS AND OUTPUTS c) LOCAL DEVICES: DEVICE ID FOR TRANSMITTING GSSE MESSAGES In a L30 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the ...
  • Page 354: Remote Double-Point Status Inputs

    The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted. Table 5–25: IEC 61850 DNA ASSIGNMENTS IEC 61850 DEFINITION FLEXLOGIC OPERAND Test IEC 61850 TEST MODE ConfRev IEC 61850 CONF REV 5-228 L30 Line Current Differential System GE Multilin...
  • Page 355: Direct Inputs And Outputs

    DIRECT INPUT 1-2 MESSAGE DEFAULT: Off  Range: Off, On DIRECT INPUT 1-8 MESSAGE DEFAULT: Off Range: Off, On DIRECT INPUT 2-1 MESSAGE DEFAULT: Off Range: Off, On DIRECT INPUT 2-2 MESSAGE DEFAULT: Off GE Multilin L30 Line Current Differential System 5-229...
  • Page 356 L90 communication channel (same for 1-2...1-8) (87L is Enabled) SETTING DIRECT OUTPUT 1-1: FLEXLOGIC OPERAND (same for 1-2...1-8) Fail DIRECT I/P 1-1 Off (Flexlogic Operand) (same for 1-2...1-8) 831024A1.CDR Figure 5–111: DIRECT INPUTS/OUTPUTS LOGIC 5-230 L30 Line Current Differential System GE Multilin...
  • Page 357: Resetting

    GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log values in other L30 features, such as FlexElements. The base factor is applied to the GOOSE analog input FlexAn- alog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
  • Page 358: Iec 61850 Goose Integers

    = maximum primary RMS value of all the sources related to the +IN and –IN inputs BASE (Max Delta Volts) The GOOSE analog input FlexAnalog values are available for use in other L30 functions that use FlexAnalog values. 5.8.12 IEC 61850 GOOSE INTEGERS ...
  • Page 359: Dcma Inputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT H1 MIN VALUE DCMA INPUT H1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin L30 Line Current Differential System 5-233...
  • Page 360: Rtd Inputs

    1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-234 L30 Line Current Differential System GE Multilin...
  • Page 361 168.47 280.77 233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 GE Multilin L30 Line Current Differential System 5-235...
  • Page 362: Dcma Outputs

    – MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. DRIVING SIGNAL MIN VAL MAX VAL 842739A1.CDR Figure 5–112: DCMA OUTPUT CHARACTERISTIC 5-236 L30 Line Current Differential System GE Multilin...
  • Page 363 The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow- ing for 50% overload. The phase current with the 50% overload margin is: GE Multilin L30 Line Current Differential System 5-237...
  • Page 364 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-238 L30 Line Current Differential System GE Multilin...
  • Page 365: Test Mode

    TEST MODE FORCING: MESSAGE The L30 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
  • Page 366: Force Contact Inputs

    Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a L30 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
  • Page 367: Force Contact Outputs

    PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin L30 Line Current Differential System 5-241...
  • Page 368: Channel Tests

    Range: 0.000 to 9.999 kA in steps of 0.001 PMU 1 IA TEST MESSAGE MAGNITUDE: 1.000 kA Range: –180.00 to 180.00° in steps of 0.05 PMU 1 IA TEST MESSAGE ANGLE: –10.00° 5-242 L30 Line Current Differential System GE Multilin...
  • Page 369 In test mode, the following actions take place: a. The Data Invalid / Test Mode bit (bit 15 in the STAT word) is set. b. The Sim bit in all output datasets is set. GE Multilin L30 Line Current Differential System 5-243...
  • Page 370 5.10 TESTING 5 SETTINGS 5-244 L30 Line Current Differential System GE Multilin...
  • Page 371: Actual Values Main Menu

     COMM STATUS See page 6-10.  REMAINING CONNECT  ACTUAL VALUES  87L DIFFERENTIAL See page 6-14.  METERING  CURRENT  SOURCE SRC 1 See page 6-15.   SOURCE SRC 2  GE Multilin L30 Line Current Differential System...
  • Page 372: Fault Reports

     PMU RECORDS See page 6-23.   MAINTENANCE See page 6-24.   ACTUAL VALUES  MODEL INFORMATION See page 6-25.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-25.  L30 Line Current Differential System GE Multilin...
  • Page 373: Contact Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin L30 Line Current Differential System...
  • Page 374: Remote Double-Point Status Inputs

    Range: On, Off, VOff, VOn, IOn, IOff  CONTACT OUTPUTS Cont Op 1  Range: On, Off, VOff, VOn, IOn, IOff Cont Op 2 MESSAGE  Range: On, Off, VOff, VOn, IOn, IOff Cont Op xx MESSAGE L30 Line Current Differential System GE Multilin...
  • Page 375: Virtual Outputs

    The present state of the programmed remote devices is shown here. The message indicates ALL REMOTE DEVICES ONLINE whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required remote device is not online. GE Multilin L30 Line Current Differential System...
  • Page 376: Channel Tests

    Range: n/a, FAIL, OK VALIDITY OF CHANNEL MESSAGE CONFIGURATION: n/a Range: n/a, FAIL, OK PFLL MESSAGE STATUS: n/a The status information for two channels is shown here. A brief description of each actual value is below: L30 Line Current Differential System GE Multilin...
  • Page 377: Digital Counters

      PATH: ACTUAL VALUES STATUS SELECTOR SWITCHES Range: Current Position / 7  SELECTOR SWITCHES SELECTOR SWITCH 1  POSITION: 0/7 Range: Current Position / 7 SELECTOR SWITCH 2 MESSAGE POSITION: 0/7 GE Multilin L30 Line Current Differential System...
  • Page 378: Flex States

    UINT INPUT 16 MESSAGE The L30 Line Current Differential System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap- ter 2 for additional details.
  • Page 379: Real Time Clock Synchronizing

    PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-B time. The value 999,999,999 indicates that the difference is not being measured due to one or both of the time sig- nals being absent or disabled. GE Multilin L30 Line Current Differential System...
  • Page 380: Remaining Connection Status

    Range: 0 to 4 MODBUS TCP (max 4) MESSAGE Range: 0 to 2 DNP (max 2) MESSAGE Range: 0 to 2 IEC-104 (max 2) MESSAGE Range: 0 to 4 PMU TCP (max 4) MESSAGE 6-10 L30 Line Current Differential System GE Multilin...
  • Page 381: Metering Conventions

    WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS GE Multilin L30 Line Current Differential System 6-11...
  • Page 382 -- - V   -- - V   -- - V   -- - V   -- - V   The above equations apply to currents as well. 6-12 L30 Line Current Differential System GE Multilin...
  • Page 383 The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a relative matter. It is important to remember that the L30 displays are always referenced as specified under SETTINGS ...
  • Page 384: Differential Current

    The metered current values are displayed for all line terminals in fundamental phasor form. All angles are shown with respect to the reference common for all L30 devices; that is, frequency, source currents, and voltages. The metered pri- mary differential and restraint currents are displayed for the local relay.
  • Page 385: Sources

    0.000 0.0° SRC 1 PHASOR Ic: MESSAGE 0.000 0.0° SRC 1 PHASOR In: MESSAGE 0.000 0.0° SRC 1 ZERO SEQ I0: MESSAGE 0.000 0.0° SRC 1 POS SEQ I1: MESSAGE 0.000 0.0° GE Multilin L30 Line Current Differential System 6-15...
  • Page 386 RMS Vca: MESSAGE 0.00 SRC 1 PHASOR Vab: MESSAGE 0.000 0.0° SRC 1 PHASOR Vbc: MESSAGE 0.000 0.0° SRC 1 PHASOR Vca: MESSAGE 0.000 0.0° SRC 1 ZERO SEQ V0: MESSAGE 0.000 0.0° 6-16 L30 Line Current Differential System GE Multilin...
  • Page 387 APPARENT PWR MESSAGE 3: 0.000 SRC 1 APPARENT PWR MESSAGE a: 0.000 SRC 1 APPARENT PWR MESSAGE b: 0.000 SRC 1 APPARENT PWR MESSAGE c: 0.000 SRC 1 POWER FACTOR MESSAGE 3: 1.000 GE Multilin L30 Line Current Differential System 6-17...
  • Page 388: Synchrocheck

    TRACKING FREQUENCY adjusted at all terminals. If currents are below 0.125 pu, then the is used. NOMINAL FREQUENCY 6-18 L30 Line Current Differential System GE Multilin...
  • Page 389: Flexelements™

    MESSAGE 0.000 The L30 Line Current Differential System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap- ter 2 for additional details.
  • Page 390: Phasor Measurement Unit

    COUNTER: 0 The above actual values are displayed without the corresponding time stamp as they become available per the recording rate setting. Also, the recording post-filtering setting is applied to these values. 6-20 L30 Line Current Differential System GE Multilin...
  • Page 391: Transducer Inputs And Outputs

    RTD INPUT xx  -50 °C Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value. GE Multilin L30 Line Current Differential System 6-21...
  • Page 392: Fault Reports

    If all 1024 event records have been filled, the oldest record will be removed as a new record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the event trigger. Refer to the menu for clearing event records.  COMMANDS CLEAR RECORDS 6-22 L30 Line Current Differential System GE Multilin...
  • Page 393: Oscillography

     RECORDING The number of triggers applicable to the phasor measurement unit recorder is indicated by the value. NUMBER OF TRIGGERS The status of the phasor measurement unit recorder is indicated as follows: GE Multilin L30 Line Current Differential System 6-23...
  • Page 394: Breaker Maintenance

    BKR 1 ARCING AMP  menu for clearing breaker arcing current records. The COMMANDS CLEAR RECORDS BREAKER OPERATING TIME defined as the slowest operating time of breaker poles that were initiated to open. 6-24 L30 Line Current Differential System GE Multilin...
  • Page 395: Model Information

    MESSAGE Date and time when the boot program was built. 2004/09/15 16:41:32 The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. GE Multilin L30 Line Current Differential System 6-25...
  • Page 396 6.5 PRODUCT INFORMATION 6 ACTUAL VALUES 6-26 L30 Line Current Differential System GE Multilin...
  • Page 397: Virtual Inputs

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin L30 Line Current Differential System...
  • Page 398: Clear Records

    The complete date, as a minimum, must be entered to allow execution of this command. The new time (if entered) and date will take effect at the moment the ENTER key is clicked. The timescale of the entered time should be local time, including daylight time where and when applicable. L30 Line Current Differential System GE Multilin...
  • Page 399: Relay Maintenance

    Various self-checking diagnostics are performed in the background while the L30 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the L30 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.
  • Page 400 PMU and not to the absolute UTC time. Therefore a simple IRIG-B genera- tor could be used instead. Also, the test set does not have to support GPS synchronization. Any stable signal source can L30 Line Current Differential System GE Multilin...
  • Page 401: Security

    Operator Logoff: Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session. • Clear Security Data: Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the operands associated with the self-tests. GE Multilin L30 Line Current Differential System...
  • Page 402: Targets Menu

    The critical fail relay on the power supply module is de-energized. • All other output relays are de-energized and are prevented from further operation. • The faceplate In Service LED indicator is turned off. • event is recorded. RELAY OUT OF SERVICE L30 Line Current Differential System GE Multilin...
  • Page 403 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the L30 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
  • Page 404 • What to do: Verify that all the items in the GOOSE data set are supported by the L30. The EnerVista UR Setup soft- ware will list the valid items. An IEC61850 client will also show which nodes are available for the L30.
  • Page 405 How often the test is performed: Upon initiation of a contact output state change. • What to do: Verify the state of the output contact and contact the factory if the problem persists. GE Multilin L30 Line Current Differential System...
  • Page 406 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the L30 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 407 Brick. Where multiple UR-series devices have self-test errors, look for common causes. GE Multilin L30 Line Current Differential System 7-11...
  • Page 408 Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended, however the output may still be non-functional. 7-12 L30 Line Current Differential System GE Multilin...
  • Page 409: Enabling The Security Management System

    To add user accounts: Select the Security > User Management menu item to open the user management window. Enter a username in the User field. The username must be 4 to 20 characters in length. GE Multilin L30 Line Current Differential System...
  • Page 410: Modifying User Privileges

    The EnerVista security management system must be enabled To modify user privileges: Select the Security > User Management menu item to open the user management window. Locate the username in the User field. L30 Line Current Differential System GE Multilin...
  • Page 411 The user is not granted write access to functions that are not checked, even if the Update Info field is checked. Admin The user is an EnerVista UR Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights. Click OK to save the changes. GE Multilin L30 Line Current Differential System...
  • Page 412 (Administrator, Engineer, Supervisor, Observer, Operator) as login names and the associated passwords are stored on the UR device. As such, when using the local accounts, access is not user-attributable. L30 Line Current Differential System GE Multilin...
  • Page 413 > Product Setup > Security, accessible from the top-level menu. NOTE No password or security information are displayed in plain text by the EnerVista software or UR device, nor are they ever transmitted without cryptographic protection. GE Multilin L30 Line Current Differential System...
  • Page 414 This setting must following (Shared) Secret meet the CyberSentry password password requirements. section for requirements RADIUS Authentication method used by RADIUS EAP-TTLS EAP-TTLS EAP-TTLS Administrator Authentication server. Currently fixed to EAP-TTLS. Method L30 Line Current Differential System GE Multilin...
  • Page 415 Change Text The specified role protected. All RADIUS users are password- following following Me1# and Administrator, protected. password password except for section for section for Supervisor, where requirements requireme it is only itself GE Multilin L30 Line Current Differential System...
  • Page 416 |--------------- Supervisory see table notes see table notes |--------------- Display Properties Clear relay records |--------------- (settings) |--------------- Communications |--------------- Modbus user map |--------------- Real Time Clock |--------------- Oscillography |--------------- Data Logger |--------------- Demand L30 Line Current Differential System GE Multilin...
  • Page 417 |--------------- Analogs IEC61850 GOOSE |--------------- Integers |------------ Transducer I/O |------------ Testing |------------ Front Panel Labels Designer |------------ Protection Summary Commands |------------ Virtual Inputs |------------ Clear Records |------------ Set date and time User Displays GE Multilin L30 Line Current Differential System...
  • Page 418 Remote user IDs must reside on an external RADIUS server, and must be provided with the requisite user role (see the fol- lowing example). Users are specified in the RADIUS server configuration file for users. Roles are specified in the RADIUS server dictionary. Example: In the file ‘users’: exampleusername User-Password == "examplepassword" 8-10 L30 Line Current Differential System GE Multilin...
  • Page 419: L30 Design

    The second major technical consideration is the restraint characteristic, which is the decision boundary between situations that are declared to be a fault and those that are not. The L30 uses an innovative adaptive decision process based on an on-line computation of the sources of measurement error. In this adaptive approach, the restraint region is an ellipse with variable major axis, minor axis, and orientation.
  • Page 420: Removal Of Decaying Offset

    Since the sampling clocks are synchronized, the time stamp is simply a sequence number. L30 Line Current Differential System GE Multilin...
  • Page 421: Disturbance Detection

    CT saturation is detected (see CT Saturation Detection for details); is an adaptive restraint term (see Online Estimate Of Measurement Error for details) LOC_ADA_A The squared restraining current is calculated as a sum of squared local and all remote restraints: GE Multilin L30 Line Current Differential System...
  • Page 422: Ground Differential Element

    The line ground differential function allows sensitive ground protection for single-line to-ground faults, allowing the phase differential element to be set higher (above load) to provide protection for multi-phase faults. The L30 ground differential function calculates ground differential current from all terminal phase currents. The maximum phase current is used for the restraint.
  • Page 423: Clock Synchronization

    In all cases, an estimate of phase error is computed and used to automatically adapt the restraint region to compensate. Frequency tracking is provided that will accommodate any fre- quency shift normally encountered in power systems. GE Multilin L30 Line Current Differential System...
  • Page 424: Frequency Tracking And Phase Locking

    GPS (Global Positioning System) to compensate for the channel delay asymmetry. This feature requires a GPS receiver to provide a GPS clock signal to the L30. With this option there are two clocks as each terminal: a local sampling clock and a local GPS clock.
  • Page 425: Frequency Detection

    Current measurements can generally provide the most accurate information, but are not always available and may contain large errors during faults or switching transients. Time stamped messages are GE Multilin L30 Line Current Differential System...
  • Page 426 256 to the round trip and add 128 to the phase angle. Also, if the above equations are computed using integer values of time stamps, a conversion to phase angle in radians is required by multiplying by  / 32. L30 Line Current Differential System GE Multilin...
  • Page 427 ( T1 T2 T2 T1 ) i -3, i-2, i -1, δ θ Calculate 1, 1. Speed up Slow down 831729A2.CDR Figure 9–2: ROUND TRIP DELAY AND CLOCK OFFSET COMPUTATION FROM TIME STAMPS GE Multilin L30 Line Current Differential System...
  • Page 428: Phase Locking Filter

    T = the time between execution of the filter algorithm repeat = time constant for the primary phase locked loop phase = time constant for the frequency locked loop frequency 9-10 L30 Line Current Differential System GE Multilin...
  • Page 429: Matching Phaselets

    A 6 Mhz clock with a 16-bit hardware counter is adequate, provided the method is used for achieving the 32-bit resolu- tion that is described in this document. • An 8-bit time stamp is adequate provided time stamp messages are exchanged once per cycle. • A 4-bit message sequence number is adequate. GE Multilin L30 Line Current Differential System 9-11...
  • Page 430: Online Estimate Of Measurement Errors

    1_A k   1_ADA_A 1_MAG_A Another source of the measurement errors is clock synchronization error, resulting in a clock uncertainty term. The L30 algorithm accounts for two terms of synchronization error corresponding to: • Raw clock deviation computed from time stamps. There are several effects that cause it to not track exactly. First, the ping-pong algorithm inherently produces slightly different estimates of clock deviation at each terminal.
  • Page 431: Ct Saturation Detection

    For short transmission lines the charging current is a small factor and can therefore be treated as an unknown error. In this application the L30 can be deployed with- out voltage sensors and the line charging current is included as a constant term in the total variance, increasing the differ- ential restraint current.
  • Page 432: Differential Element Characteristics

    The L30 incorporates an adaptive differential algorithm based on the traditional percent differential principle. In the tradi- tional percent differential scheme, the operating parameter is based on the phasor sum of currents in the zone and the restraint parameter is based on the scalar (or average scalar) sum of the currents in the protected zone - when the operat- ing parameter divided by the restraint parameter is above the slope setting, the relay will operate.
  • Page 433: Relay Synchronization

    9.1 OVERVIEW The major difference between the L30 differential scheme and a percent differential scheme is the use of an estimate of errors in the input currents to increase the restraint parameter during faults, permitting the use of more sensitive settings than those used in the traditional scheme.
  • Page 434: Description

    9.2OPERATING CONDITION CHARACTERISTICS 9.2.1 DESCRIPTION Characteristics of differential elements can be shown in the complex plane. The operating characteristics of the L30 are fundamentally dependant on the relative ratios of the local and remote current phasor magnitudes and the angles of as shown in the Restraint Characteristics figure.
  • Page 435 9 THEORY OF OPERATION 9.2 OPERATING CONDITION CHARACTERISTICS Figure 9–7: RESTRAINT CHARACTERISTICS GE Multilin L30 Line Current Differential System 9-17...
  • Page 436: Trip Decision Example

    Current differential section of chapter 5. The following figure shows how the L30 settings affect the restraint characteristics. The local and remote currents are 180° apart, which represents an external fault. The breakpoint between the two slopes indicates the point where the restraint area is becoming wider to override uncertainties from CT saturation, fault noise, harmonics, etc.
  • Page 437 9 THEORY OF OPERATION 9.2 OPERATING CONDITION CHARACTERISTICS loc pu OPERATE RESTRAINT BP=8, P=2, S1=30%, S2=50% BP=4, P=1, S1=30%, S2=50% BP=4, P=1, S1=20%, S2=40% OPERATE rem pu 831725A1.CDR Figure 9–8: SETTINGS IMPACT ON RESTRAINT CHARACTERISTIC GE Multilin L30 Line Current Differential System 9-19...
  • Page 438: Description

    Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before applying the two equations above (the superscripts denote phases, the subscripts denote stations). For AG faults:  (EQ 9.43) 9-20 L30 Line Current Differential System GE Multilin...
  • Page 439 -- - V (EQ 9.50) SYS0   Z -- - V SYS0 where Z is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu. SYS0 GE Multilin L30 Line Current Differential System 9-21...
  • Page 440 FAULT FAULT LOCATION 3I_0 LOCATOR 1 FAULT# RECLOSE SHOT VA or VAB VB or VBC VC or VCA Vn or V_0 SHOT # FROM 827094A5.CDR AUTO RECLOSURE Figure 9–10: FAULT LOCATOR SCHEME 9-22 L30 Line Current Differential System GE Multilin...
  • Page 441: Introduction

    CTs. Ideally, CTs selected for line current differential protection should be based on the criteria described below. If the available CTs do not meet the described criteria, the L30 will still provide good security for CT saturation for external faults.
  • Page 442: Calculation Example 2

      0.008   ---------------------------------- - 4.71 0.75 0.52 291.89 V (< 300 V, which is OK) (EQ 10.9) ratio of 300:1 The CT will provide acceptable performance in this application. 10-2 L30 Line Current Differential System GE Multilin...
  • Page 443: Introduction

    Program the setting below the current level where CT saturation and spurious transient differential currents can be expected. The first approach gives comparatively more security and less sensitivity; the second approach provides less security for more sensitivity. GE Multilin L30 Line Current Differential System 10-3...
  • Page 444: Ct Tap

    For relay 1, channel 1 communicates to relay 2 and channel 2 communicates to relay 3 • For relay 2, channel 1 communicates to relay 1 and channel 2 communicates to relay 3 10-4 L30 Line Current Differential System GE Multilin...
  • Page 445 This satisfies the equality condition indicated earlier. During on-load tests, the differential current at all terminals should be the same and generally equal to the charging current if the tap and CT ratio settings are chosen correctly. GE Multilin L30 Line Current Differential System 10-5...
  • Page 446: Description

    If GPS is enabled at all terminals and the GPS signal is present, the L30 compensates for the channel asymmetry. On the loss of the GPS signal, the L30 stores the last measured value of the channel asymmetry per channel and compensates for the asymmetry until the GPS clock is available.
  • Page 447: Compensation Method 2

    Create FlexLogic™ similar to that shown below to switch the 87L element to Settings Group 2 (with most sensitive set- tings) if the L30 has a valid GPS time reference. If a GPS or 87L communications failure occurs, the L30 will switch back to Settings Group 1 with less sensitive settings.
  • Page 448 Set the 87L element with different differential settings for Settings Groups 1 and 2 as shown below Enable GPS compensation when the GPS signal is valid and switch to Settings Group 2 (with more sensitive settings) as shown below. 10-8 L30 Line Current Differential System GE Multilin...
  • Page 449: Instantaneous Element Error During L30 Synchronization

    10.4.1 INSTANTANEOUS ELEMENT ERROR DURING L30 SYNCHRONIZATION As explained in the Theory of Operation chapter, two or three L30 relays are synchronized to each other and to system fre- quency to provide digital differential protection and accurate measurements for other protection and control functions.
  • Page 450 10.4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10-10 L30 Line Current Differential System GE Multilin...
  • Page 451: Channel Testing

    G.703, and RS422. The speed is 64 Kbaud in a transparent synchronous mode with automatic synchronous character detection and CRC insertion. The Local Loopback Channel Test verifies the L30 communication modules are working properly. The Remote Loopback –4 Channel Test verifies the communication link between the relays meets requirements (BER less than 10 ).
  • Page 452: Clock Synchronization Tests

    “OK” ACTUAL VALUES STATUS CHANNEL TESTS CHANNEL 1(2) STATUS:    “n/a” ACTUAL VALUES STATUS CHANNEL TESTS REMOTE LOOPBACK STATUS:    “OK” ACTUAL VALUES STATUS CHANNEL TESTS PFLL STATUS: 11-2 L30 Line Current Differential System GE Multilin...
  • Page 453: Current Differential

    Download the UR Test software from the GE Multilin website (http://www.GEindustrial.com/multilin) or contact GE Multilin for information about the UR current differential test program which allows the user to simulate different operating conditions for verifying correct responses of the relays during commissioning activities. NOTE GE Multilin L30 Line Current Differential System 11-3...
  • Page 454: Local-Remote Relay Tests

    These phasors and differential currents can be monitored at the ACTUAL VAL-   menu where all current magnitudes and angles can be observed and con- METERING 87L DIFFERENTIAL CURRENT clusions of proper relay interconnections can be made. 11-4 L30 Line Current Differential System GE Multilin...
  • Page 455: A.1.1 Flexanalog Items

    SRC 2 Ib RMS Amps Source 2 phase B current RMS 6212 SRC 2 Ic RMS Amps Source 2 phase C current RMS 6214 SRC 2 In RMS Amps Source 2 neutral current RMS GE Multilin L30 Line Current Differential System...
  • Page 456 SRC 1 V_2 Mag Volts Source 1 negative-sequence voltage magnitude 6699 SRC 1 V_2 Angle Degrees Source 1 negative-sequence voltage angle 6720 SRC 2 Vag RMS Volts Source 2 phase AG voltage RMS L30 Line Current Differential System GE Multilin...
  • Page 457 Source 2 phase A real power 7204 SRC 2 Pb Watts Source 2 phase B real power 7206 SRC 2 Pc Watts Source 2 phase C real power 7208 SRC 2 Q Vars Source 2 three-phase reactive power GE Multilin L30 Line Current Differential System...
  • Page 458 Synchrocheck 2 delta frequency 9223 Synchchk 2 Delta Phs Degrees Synchrocheck 2 delta phase 9224 Synchchk 3 Delta V Volts Synchrocheck 3 delta voltage 9226 Synchchk 3 Delta F Synchrocheck 3 delta frequency L30 Line Current Differential System GE Multilin...
  • Page 459 Remote 1 IG angle 9409 Terminal 2 IG Mag Amps Remote 2 IG magnitude 9411 Terminal 2 IG Angle Amps Remote 2 IG angle 9421 87L Harm2 Iad Mag Amps Current differential second harmonic Iad magnitude GE Multilin L30 Line Current Differential System...
  • Page 460 10 actual value 13524 DCMA Inputs 11 Value dcmA input 11 actual value 13526 DCMA Inputs 12 Value dcmA input 12 actual value 13528 DCMA Inputs 13 Value dcmA input 13 actual value L30 Line Current Differential System GE Multilin...
  • Page 461 RTD input 33 actual value 13585 RTD Inputs 34 Value RTD input 34 actual value 13586 RTD Inputs 35 Value RTD input 35 actual value 13587 RTD Inputs 36 Value RTD input 36 actual value GE Multilin L30 Line Current Differential System...
  • Page 462 45594 GOOSE Analog In 6 IEC 61850 GOOSE analog input 6 45596 GOOSE Analog In 7 IEC 61850 GOOSE analog input 7 45598 GOOSE Analog In 8 IEC 61850 GOOSE analog input 8 L30 Line Current Differential System GE Multilin...
  • Page 463: A.1.2 Flexinteger Items

    IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 GE Multilin L30 Line Current Differential System...
  • Page 464 A.1 PARAMETER LISTS APPENDIX A A-10 L30 Line Current Differential System GE Multilin...
  • Page 465: B.1.1 Introduction

    Broadcast mode is only recognized when associated with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored. GE Multilin L30 Line Current Differential System...
  • Page 466: B.1.4 Crc-16 Algorithm

    No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC L30 Line Current Differential System GE Multilin...
  • Page 467: B.2.1 Supported Function Codes

    125. See the Modbus memory map table for exact details on the data registers. Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The L30 interpretation allows either function code to be used for reading one or more consecutive data registers.
  • Page 468: B.2.3 Execute Operation (Function Code 05H)

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high L30 Line Current Differential System GE Multilin...
  • Page 469: B.2.5 Store Multiple Settings (Function Code 10H)

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte GE Multilin L30 Line Current Differential System...
  • Page 470: B.3.1 Obtaining Relay Files Via Modbus

    Familiarity with the data logger feature is required to understand this description. Refer to the Data Logger section of Chap- ter 5 for details. To read the entire data logger in binary COMTRADE format, read the following files. L30 Line Current Differential System GE Multilin...
  • Page 471: B.3.2 Modbus Password Operation

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the L30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 472 Command or setting password security access is restricted to the particular port or particular TCP/IP connection on which the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the passwords must be re-entered after disconnecting and re-connecting on TCP/IP. L30 Line Current Differential System GE Multilin...
  • Page 473: B.4.1 Modbus Memory Map

    0414 Virtual Input 21 State 0 to 1 F108 0 (Off) 0415 Virtual Input 22 State 0 to 1 F108 0 (Off) 0416 Virtual Input 23 State 0 to 1 F108 0 (Off) GE Multilin L30 Line Current Differential System...
  • Page 474 ...Repeated for Digital Counter 3 0818 ...Repeated for Digital Counter 4 0820 ...Repeated for Digital Counter 5 0828 ...Repeated for Digital Counter 6 0830 ...Repeated for Digital Counter 7 0838 ...Repeated for Digital Counter 8 B-10 L30 Line Current Differential System GE Multilin...
  • Page 475 Field latching output close driver states 0 to 65535 F500 160B Field latching output physical states 0 to 65535 F500 160C Field unit online/offline states 0 to 65535 F500 160D Undefined 0 to 65535 F500 GE Multilin L30 Line Current Differential System B-11...
  • Page 476 Source 1 Negative Sequence Current Magnitude 0 to 999999.999 0.001 F060 1821 Source 1 Negative Sequence Current Angle -359.9 to 0 degrees F002 1822 Source 1 Differential Ground Current Magnitude 0 to 999999.999 0.001 F060 B-12 L30 Line Current Differential System GE Multilin...
  • Page 477 Source 1 Three Phase Reactive Power -1000000000000 to 0.001 F060 1000000000000 1C0A Source 1 Phase A Reactive Power -1000000000000 to 0.001 F060 1000000000000 1C0C Source 1 Phase B Reactive Power -1000000000000 to 0.001 F060 1000000000000 GE Multilin L30 Line Current Differential System B-13...
  • Page 478 0 to 1 F126 0 (No) 2227 Breaker 4 Arcing Current Clear Command 0 to 1 F126 0 (No) 2228 Breaker 5 Arcing Current Clear Command 0 to 1 F126 0 (No) B-14 L30 Line Current Differential System GE Multilin...
  • Page 479 0 to 7 F244 6 (H1a) 2461 Field Raw Data Freeze 0 to 1 F102 0 (Disabled) 87L Current differential actual values (Read Only) 2480 Local IA Magnitude 0 to 999999.999 0.001 F060 GE Multilin L30 Line Current Differential System B-15...
  • Page 480 PMU 1 Phase B Voltage Angle -359.9 to 0 ° F002 2546 PMU 1 Phase C Voltage Magnitude 0 to 999999.999 0.001 F060 2548 PMU 1 Phase C Voltage Angle -359.9 to 0 ° F002 B-16 L30 Line Current Differential System GE Multilin...
  • Page 481 IEC 61850 GGIO5 configuration (read/write setting registers) (16 modules) 26B0 IEC 61850 GGIO5 uinteger input 1 operand F612 26B1 IEC 61850 GGIO5 uinteger input 2 operand F612 26B2 IEC 61850 GGIO5 uinteger input 3 operand F612 GE Multilin L30 Line Current Differential System B-17...
  • Page 482 Fault Report Actuals (Read Only Non-Volatile) (15 modules) 3030 Fault Report 1 Time 0 to 4294967295 F050 3032 Fault Report 2 Time 0 to 4294967295 F050 3034 Fault Report 3 Time 0 to 4294967295 F050 B-18 L30 Line Current Differential System GE Multilin...
  • Page 483 Reserved for password settings of future roles (63 items) 0 to 65535 F001 3328 Security status indicator 0 to 65535 F618 Security (Read/Write Setting) 3329 Session Lockout 0 to 99 F001 332A Session Lockout Period 0 to 9999 F001 GE Multilin L30 Line Current Differential System B-19...
  • Page 484 DCMA Inputs 20 Value -9999999 to 9999999 F004 34E8 DCMA Inputs 21 Value -9999999 to 9999999 F004 34EA DCMA Inputs 22 Value -9999999 to 9999999 F004 34EC DCMA Inputs 23 Value -9999999 to 9999999 F004 B-20 L30 Line Current Differential System GE Multilin...
  • Page 485 -32768 to 32767 °C F002 Ohm Input Values (Read Only) (2 modules) Þ 3520 Ohm Inputs 1 Value 0 to 65535 F001 Þ 3521 Ohm Inputs 2 Value 0 to 65535 F001 GE Multilin L30 Line Current Differential System B-21...
  • Page 486 0 to 7 F244 7 (H1b) 387D Field Unit 6 Process Card Port 0 to 7 F244 5 (H2b) 387E Field Unit 7 Process Card Port 0 to 7 F244 3 (H3b) B-22 L30 Line Current Differential System GE Multilin...
  • Page 487 ...Repeated for Field Contact Input 21 39E7 ...Repeated for Field Contact Input 22 39F2 ...Repeated for Field Contact Input 23 39FD ...Repeated for Field Contact Input 24 3A08 ...Repeated for Field Contact Input 25 GE Multilin L30 Line Current Differential System B-23...
  • Page 488 F300 3DD1 Field Latching Output 1 Events 0 to 1 F102 1 (Enabled) 3DD2 Field Latching Output 1 Reserved (2 items) 0 to 1 F001 3DD4 ...Repeated for Fielding Latching Output 2 B-24 L30 Line Current Differential System GE Multilin...
  • Page 489 ...Repeated for Field Unit Transducer 3 3F6D ...Repeated for Field Unit Transducer 4 3F7C ...Repeated for Field Unit Transducer 5 3F8B ...Repeated for Field Unit Transducer 6 3F9A ...Repeated for Field Unit Transducer 7 GE Multilin L30 Line Current Differential System B-25...
  • Page 490 Channel 1 Number of Lost Packets 0 to 65535 F001 405C Channel 1 Remote Loopback Status 0 to 2 F134 2 (n/a) 405D Channel 1 Status 0 to 2 F134 1 (OK) B-26 L30 Line Current Differential System GE Multilin...
  • Page 491 DNP current scale factor 0 to 8 F194 2 (1) 40AF DNP voltage scale factor 0 to 8 F194 2 (1) 40B0 DNP power scale factor 0 to 8 F194 2 (1) GE Multilin L30 Line Current Differential System B-27...
  • Page 492 DNP object 30 default variation 1 to 5 F001 4147 DNP object 32 default variation 0 to 5 F525 0 (1) Communications Actuals (Read Only) 4160 Modbus Available TCP/IP Connections 0 to 4 F001 B-28 L30 Line Current Differential System GE Multilin...
  • Page 493 F300 42C2 User LED type (latched or self-resetting) 0 to 1 F127 1 (Self-Reset) 42C3 ...Repeated for User-Programmable LED 2 42C6 ...Repeated for User-Programmable LED 3 42C9 ...Repeated for User-Programmable LED 4 GE Multilin L30 Line Current Differential System B-29...
  • Page 494 0 to 1 F102 1 (Enabled) 4444 User Programmable Primary Ethernet Fail Function 0 to 1 F102 0 (Disabled) 4445 User Programmable Secondary Ethernet Fail Function 0 to 1 F102 0 (Disabled) B-30 L30 Line Current Differential System GE Multilin...
  • Page 495 Breaker 1 name F206 “Bkr 1" 47D4 Breaker 1 mode 0 to 1 F157 0 (3-Pole) 47D5 Breaker 1 open 0 to 4294967295 F300 47D7 Breaker 1 close 0 to 4294967295 F300 GE Multilin L30 Line Current Differential System B-31...
  • Page 496 Raw Field Data AC3 Angle 0 to 0.01 degree F002 4E09 Raw Field Data AC4 Mag 0 to 0.001 0.001 F003 4E0B Raw Field Data AC4 Angle 0 to 0.01 degree F002 B-32 L30 Line Current Differential System GE Multilin...
  • Page 497 ...Repeated for RTD Input 10 54C8 ...Repeated for RTD Input 11 54DC ...Repeated for RTD Input 12 54F0 ...Repeated for RTD Input 13 5404 ...Repeated for RTD Input 14 5518 ...Repeated for RTD Input 15 GE Multilin L30 Line Current Differential System B-33...
  • Page 498 ...Repeated for FlexLogic Timer 12 5860 ...Repeated for FlexLogic Timer 13 5868 ...Repeated for FlexLogic Timer 14 5870 ...Repeated for FlexLogic Timer 15 5878 ...Repeated for FlexLogic Timer 16 5880 ...Repeated for FlexLogic Timer 17 B-34 L30 Line Current Differential System GE Multilin...
  • Page 499 ...Repeated for Phase Instantaneous Overcurrent 8 5A98 ...Repeated for Phase Instantaneous Overcurrent 9 5AAB ...Repeated for Phase Instantaneous Overcurrent 10 5ABE ...Repeated for Phase Instantaneous Overcurrent 11 5AD1 ...Repeated for Phase Instantaneous Overcurrent 12 GE Multilin L30 Line Current Differential System B-35...
  • Page 500 0 to 1 F001 5D11 ...Repeated for Ground Time Overcurrent 2 5D22 ...Repeated for Ground Time Overcurrent 3 5D33 ...Repeated for Ground Time Overcurrent 4 5D44 ...Repeated for Ground Time Overcurrent 5 B-36 L30 Line Current Differential System GE Multilin...
  • Page 501 0 to 1 F102 0 (Disabled) Setting Groups (Read/Write Setting) 5F70 Setting Group for Modbus Comms (0 means group 1) 0 to 5 F001 5F71 Setting Groups Block 0 to 4294967295 F300 GE Multilin L30 Line Current Differential System B-37...
  • Page 502 6000 6217 Autoreclose 1 Incomplete Sequence Time 0 to 655.35 0.01 F001 6218 Autoreclose 1 Events 0 to 1 F102 0 (Disabled) 6219 Autoreclose 1 Reduce Max 1 0 to 4294967295 F300 B-38 L30 Line Current Differential System GE Multilin...
  • Page 503 0 (Definite Time) 7004 Phase Undervoltage 1 Delay 0 to 600 0.01 F001 7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 0.001 F001 7006 Phase Undervoltage 1 Block 0 to 4294967295 F300 GE Multilin L30 Line Current Differential System B-39...
  • Page 504 0 to 1 F196 0 (Calculated 3I0) 723E Neutral Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 723F Neutral Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 0.001 F001 B-40 L30 Line Current Differential System GE Multilin...
  • Page 505 0 to 65535 F001 7808 ...Repeated for Ohm Inputs 2 Phasor Measurement Unit Recorder Config Counter Command (Read/Write Command) (4 modules) 781A PMU 1 Recorder Clear Config Counter 0 to 1 F126 0 (No) GE Multilin L30 Line Current Differential System B-41...
  • Page 506 7916 PMU TCP port number 1 to 65535 F001 4712 7917 PMU UDP port number 1 1 to 65535 F001 4713 7918 PMU UDP port number 2 1 to 65535 F001 4714 B-42 L30 Line Current Differential System GE Multilin...
  • Page 507 Underfreqency 1 Reserved (5 items) 0 to 1 F001 7A8F ...Repeated for Underfrequency 2 7A9E ...Repeated for Underfrequency 3 7AAD ...Repeated for Underfrequency 4 7ABC ...Repeated for Underfrequency 5 7ACB ...Repeated for Underfrequency 6 GE Multilin L30 Line Current Differential System B-43...
  • Page 508 F001 7FA5 Auxiliary Overvoltage 1 Block 0 to 4294967295 F300 7FA7 Auxiliary Overvoltage 1 Target 0 to 2 F109 0 (Self-reset) 7FA8 Auxiliary Overvoltage 1 Events 0 to 1 F102 0 (Disabled) B-44 L30 Line Current Differential System GE Multilin...
  • Page 509 0 to 4294967295 F300 862D ...Repeated for Breaker Failure 2 865A ...Repeated for Breaker Failure 3 8687 ...Repeated for Breaker Failure 4 86B4 ...Repeated for Breaker Failure 5 86E1 ...Repeated for Breaker Failure 6 GE Multilin L30 Line Current Differential System B-45...
  • Page 510 ...Repeated for Digital Element 37 8D2E ...Repeated for Digital Element 38 8D44 ...Repeated for Digital Element 39 8D5A ...Repeated for Digital Element 40 8D70 ...Repeated for Digital Element 41 8D86 ...Repeated for Digital Element 42 B-46 L30 Line Current Differential System GE Multilin...
  • Page 511 Fault Report 1 Z0 Magnitude 0.01 to 650 ohms 0.01 F001 9206 Fault Report 1 Z0 Angle 25 to 90 degrees F001 9207 Fault Report 1 Line Length Units 0 to 1 F147 0 (km) GE Multilin L30 Line Current Differential System B-47...
  • Page 512 ...Repeated for IEC61850 GOOSE UInteger 5 98AF ...Repeated for IEC61850 GOOSE UInteger 6 98B2 ...Repeated for IEC61850 GOOSE UInteger 7 98B5 ...Repeated for IEC61850 GOOSE UInteger 8 98B8 ...Repeated for IEC61850 GOOSE UInteger 9 B-48 L30 Line Current Differential System GE Multilin...
  • Page 513 Digital Counter 1 Units F206 (none) A30A Digital Counter 1 Block 0 to 4294967295 F300 A30C Digital Counter 1 Up 0 to 4294967295 F300 A30E Digital Counter 1 Down 0 to 4294967295 F300 GE Multilin L30 Line Current Differential System B-49...
  • Page 514 ...Repeated for IEC 61850 GOOSE analog input 5 AA23 ...Repeated for IEC 61850 GOOSE analog input 6 AA2A ...Repeated for IEC 61850 GOOSE analog input 7 AA31 ...Repeated for IEC 61850 GOOSE analog input 8 B-50 L30 Line Current Differential System GE Multilin...
  • Page 515 0 to 65534 F206 (none) IEC 61850 GGIO4 general analog configuration settings (read/write) AF00 Number of analog points in GGIO4 4 to 32 F001 AF01 GOOSE analog scan period 100 to 5000 F001 1000 GE Multilin L30 Line Current Differential System B-51...
  • Page 516 TCP Port Number for the IEC 61850 / MMS Protocol 0 to 65535 F001 B06D IEC 61850 Logical Device Name F213 “IECName” B07D IEC 61850 Logical Device Instance F213 “LDInst” B08D IEC 61850 LPHD Location F204 “Location” B-52 L30 Line Current Differential System GE Multilin...
  • Page 517 ...Repeated for Received Analog 8 B220 ...Repeated for Received Analog 9 B222 ...Repeated for Received Analog 10 B224 ...Repeated for Received Analog 11 B226 ...Repeated for Received Analog 12 B228 ...Repeated for Received Analog 13 GE Multilin L30 Line Current Differential System B-53...
  • Page 518 0 to 197 F233 0 (None) (32 items) B920 ...Repeated for Module 2 B940 ...Repeated for Module 3 B960 ...Repeated for Module 4 B980 ...Repeated for Module 5 B9A0 ...Repeated for Module 6 B-54 L30 Line Current Differential System GE Multilin...
  • Page 519 ...Repeated for Contact Input 36 BC20 ...Repeated for Contact Input 37 BC28 ...Repeated for Contact Input 38 BC30 ...Repeated for Contact Input 39 BC38 ...Repeated for Contact Input 40 BC40 ...Repeated for Contact Input 41 GE Multilin L30 Line Current Differential System B-55...
  • Page 520 ...Repeated for Contact Input 90 BDD0 ...Repeated for Contact Input 91 BDD8 ...Repeated for Contact Input 92 BDE0 ...Repeated for Contact Input 93 BDE8 ...Repeated for Contact Input 94 BDF0 ...Repeated for Contact Input 95 B-56 L30 Line Current Differential System GE Multilin...
  • Page 521 ...Repeated for Virtual Input 41 C01C ...Repeated for Virtual Input 42 C028 ...Repeated for Virtual Input 43 C034 ...Repeated for Virtual Input 44 C040 ...Repeated for Virtual Input 45 C04C ...Repeated for Virtual Input 46 GE Multilin L30 Line Current Differential System B-57...
  • Page 522 ...Repeated for Virtual Output 28 C210 ...Repeated for Virtual Output 29 C218 ...Repeated for Virtual Output 30 C220 ...Repeated for Virtual Output 31 C228 ...Repeated for Virtual Output 32 C230 ...Repeated for Virtual Output 33 B-58 L30 Line Current Differential System GE Multilin...
  • Page 523 ...Repeated for Virtual Output 82 C3C0 ...Repeated for Virtual Output 83 C3C8 ...Repeated for Virtual Output 84 C3D0 ...Repeated for Virtual Output 85 C3D8 ...Repeated for Virtual Output 86 C3E0 ...Repeated for Virtual Output 87 GE Multilin L30 Line Current Differential System B-59...
  • Page 524 0 to 2 F144 0 (Disabled) C800 Force Contact Output x State (64 items) 0 to 3 F131 0 (Disabled) 87L Channel Tests (Read/Write) C840 Local Loopback Function 0 to 1 F126 0 (No) B-60 L30 Line Current Differential System GE Multilin...
  • Page 525 ...Repeated for Remote Input 2 CFB4 ...Repeated for Remote Input 3 CFBE ...Repeated for Remote Input 4 CFC8 ...Repeated for Remote Input 5 CFD2 ...Repeated for Remote Input 6 CFDC ...Repeated for Remote Input 7 GE Multilin L30 Line Current Differential System B-61...
  • Page 526 ...Repeated for Remote Input 56 D1D0 ...Repeated for Remote Input 57 D1DA ...Repeated for Remote Input 58 D1E4 ...Repeated for Remote Input 59 D1EE ...Repeated for Remote Input 60 D1F8 ...Repeated for Remote Input 61 B-62 L30 Line Current Differential System GE Multilin...
  • Page 527 ...Repeated for Remote Output 8 D2C0 ...Repeated for Remote Output 9 D2C4 ...Repeated for Remote Output 10 D2C8 ...Repeated for Remote Output 11 D2CC ...Repeated for Remote Output 12 D2D0 ...Repeated for Remote Output 13 GE Multilin L30 Line Current Differential System B-63...
  • Page 528 IEC 61850 GGIO2.CF.SPCSO31.ctlModel Value 0 to 2 F001 D33F IEC 61850 GGIO2.CF.SPCSO32.ctlModel Value 0 to 2 F001 D340 IEC 61850 GGIO2.CF.SPCSO33.ctlModel Value 0 to 2 F001 D341 IEC 61850 GGIO2.CF.SPCSO34.ctlModel Value 0 to 2 F001 B-64 L30 Line Current Differential System GE Multilin...
  • Page 529 ...Repeated for Remote Device 17 D3C4 ...Repeated for Remote Device 18 D3C8 ...Repeated for Remote Device 19 D3CC ...Repeated for Remote Device 20 D3D0 ...Repeated for Remote Device 21 D3D4 ...Repeated for Remote Device 22 GE Multilin L30 Line Current Differential System B-65...
  • Page 530 ...Repeated for Contact Output 12 DD44 ...Repeated for Contact Output 13 DD53 ...Repeated for Contact Output 14 DD62 ...Repeated for Contact Output 15 DD71 ...Repeated for Contact Output 16 DD80 ...Repeated for Contact Output 17 B-66 L30 Line Current Differential System GE Multilin...
  • Page 531 Inputs 1 Units F206 “mA” E05E dcmA Inputs 1 Range 0 to 6 F173 6 (4 to 20 mA) E05F dcmA Inputs 1 Minimum Value -9999.999 to 9999.999 0.001 F004 4000 GE Multilin L30 Line Current Differential System B-67...
  • Page 532 Phasor Measurement Unit Control Block (Read/Write Setting) (4 modules) E650 PMU Aggregator 1 Control Block SvEna 0 to 4294967295 F300 E652 PMU Aggregator 1 Control Block Client Control 0 to 4294967295 F300 B-68 L30 Line Current Differential System GE Multilin...
  • Page 533 Last settings change date 0 to 4294967295 F050 ED09 Template bitmask (750 items) 0 to 65535 F001 Phasor Measurement Unit Records (Read Only) EFFF PMU Recording Number of Triggers 0 to 65535 samples F001 GE Multilin L30 Line Current Differential System B-69...
  • Page 534: B.4.2 Data Formats

    0 = 1 & 3 Pole, 1 = 1 Pole, 2 = 3 Pole-A, 3 = 3 Pole-B Positive values indicate lagging power factor; negative values indicate leading. F083 ENUMERATION: SELECTOR MODES 0 = Time-Out, 1 = Acknowledge B-70 L30 Line Current Differential System GE Multilin...
  • Page 535 ENUMERATION: NEUTRAL OVERVOLTAGE CURVES ENUMERATION: LOGIC INPUT 0 = Definite Time, 1 = FlexCurve A, 2 = FlexCurve B, 0 = Disabled, 1 = Input 1, 2 = Input 2 3 = FlexCurve C GE Multilin L30 Line Current Differential System B-71...
  • Page 536 Negative Sequence Time Overcurrent 2 Negative Sequence Overvoltage Auxiliary Undervoltage 1 F123 ENUMERATION: CT SECONDARY Phase Undervoltage 1 Phase Undervoltage 2 0 = 1 A, 1 = 5 A Auxiliary Overvoltage 1 B-72 L30 Line Current Differential System GE Multilin...
  • Page 537 Digital Element 41 Non-volatile Latch 13 Digital Element 42 Non-volatile Latch 14 Digital Element 43 Non-volatile Latch 15 Digital Element 44 Non-volatile Latch 16 Digital Element 45 Digital Counter 1 Digital Element 46 GE Multilin L30 Line Current Differential System B-73...
  • Page 538 Thermal overload protection 2 RTD Input 34 1014 Broken conductor detection 1 RTD Input 35 1015 Broken conductor detection 2 RTD Input 36 RTD Input 37 RTD Input 38 RTD Input 39 B-74 L30 Line Current Differential System GE Multilin...
  • Page 539 0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles Maintenance Alert 3 = 3 x 64 cycles, 4 = 1 x 128 cycles Any Minor Error Any Major Error Maintenance Alert GE Multilin L30 Line Current Differential System B-75...
  • Page 540 Temperature Warning On Temperature Warning Off F144 Unauthorized Access ENUMERATION: FORCED CONTACT INPUT STATE System Integrity Recovery 0 = Disabled, 1 = Open, 2 = Closed System Integrity Recovery 06 System Integrity Recovery 07 B-76 L30 Line Current Differential System GE Multilin...
  • Page 541 0 = Normal, 1 = Symmetry 1, 2 = Symmetry 2, 3 = Delay 1 4 = Delay 2 F159 ENUMERATION: BREAKER AUX CONTACT KEYING 0 = 52a, 1 = 52b, 2 = None GE Multilin L30 Line Current Differential System B-77...
  • Page 542 4 to 20 mA 64 samples/cycle F174 ENUMERATION: TRANSDUCER RTD INPUT TYPE 0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel, 2 = 100 Ohm Nickel, 3 = 10 Ohm Copper B-78 L30 Line Current Differential System GE Multilin...
  • Page 543 User-programmable key 10 F205 Value Up User-programmable key 11 TEXT12: 12-CHARACTER ASCII TEXT Value Down User-programmable key 12 Message Up User-programmable key 13 F206 Message Down User-programmable key 14 TEXT6: 6-CHARACTER ASCII TEXT GE Multilin L30 Line Current Differential System B-79...
  • Page 544 MMXU1.MX.VAr.phsB.cVal.mag.f MMXU1.MX.VAr.phsC.cVal.mag.f MMXU1.MX.VA.phsA.cVal.mag.f F229 ENUMERATION: SETTINGS CONTROL CHANGE METHOD MMXU1.MX.VA.phsB.cVal.mag.f MMXU1.MX.VA.phsC.cVal.mag.f 0 = None, 1 = Keypad, 2 = Front Port, 3 = COM1, 4 = COM2, 5 = Ethernet MMXU1.MX.PF.phsA.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f B-80 L30 Line Current Differential System GE Multilin...
  • Page 545 MMXU2.MX.PF.phsC.cVal.mag.f MMXU4.MX.PhV.phsC.cVal.mag.f MMXU3.MX.TotW.mag.f MMXU4.MX.PhV.phsC.cVal.ang.f MMXU3.MX.TotVAr.mag.f MMXU4.MX.A.phsA.cVal.mag.f MMXU3.MX.TotVA.mag.f MMXU4.MX.A.phsA.cVal.ang.f MMXU3.MX.TotPF.mag.f MMXU4.MX.A.phsB.cVal.mag.f MMXU3.MX.Hz.mag.f MMXU4.MX.A.phsB.cVal.ang.f MMXU3.MX.PPV.phsAB.cVal.mag.f MMXU4.MX.A.phsC.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.ang.f MMXU4.MX.A.phsC.cVal.ang.f MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.A.neut.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.A.neut.cVal.ang.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.W.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f GE Multilin L30 Line Current Differential System B-81...
  • Page 546 MMXU5.MX.VA.phsA.cVal.mag.f GGIO4.MX.AnIn11.mag.f MMXU5.MX.VA.phsB.cVal.mag.f GGIO4.MX.AnIn12.mag.f MMXU5.MX.VA.phsC.cVal.mag.f GGIO4.MX.AnIn13.mag.f MMXU5.MX.PF.phsA.cVal.mag.f GGIO4.MX.AnIn14.mag.f MMXU5.MX.PF.phsB.cVal.mag.f GGIO4.MX.AnIn15.mag.f MMXU5.MX.PF.phsC.cVal.mag.f GGIO4.MX.AnIn16.mag.f MMXU6.MX.TotW.mag.f GGIO4.MX.AnIn17.mag.f MMXU6.MX.TotVAr.mag.f GGIO4.MX.AnIn18.mag.f MMXU6.MX.TotVA.mag.f GGIO4.MX.AnIn19.mag.f MMXU6.MX.TotPF.mag.f GGIO4.MX.AnIn20.mag.f MMXU6.MX.Hz.mag.f GGIO4.MX.AnIn21.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f GGIO4.MX.AnIn22.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f GGIO4.MX.AnIn23.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f GGIO4.MX.AnIn24.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f GGIO4.MX.AnIn25.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f GGIO4.MX.AnIn26.mag.f B-82 L30 Line Current Differential System GE Multilin...
  • Page 547 ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS GGIO3.ST.UIntIn3.stVal FOR RECEPTION GGIO3.ST.UIntIn4.q value GOOSE dataset item GGIO3.ST.UIntIn4.stVal None GGIO3.ST.UIntIn5.q GGIO3.ST.Ind1.q GGIO3.ST.UIntIn5.stVal GGIO3.ST.Ind1.stVal GGIO3.ST.UIntIn6.q GGIO3.ST.Ind2.q GGIO3.ST.UIntIn6.stVal GGIO3.ST.Ind2.stVal GGIO3.ST.UIntIn7.q   GGIO3.ST.UIntIn7.stVal GGIO1.ST.Ind64q GGIO3.ST.UIntIn8.q GGIO1.ST.Ind64.stVal GGIO3.ST.UIntIn8.stVal GGIO3.MX.AnIn1.mag.f GGIO3.ST.UIntIn9.q GE Multilin L30 Line Current Differential System B-83...
  • Page 548 ENUMERATION: PROCESS CARD DSP CONFIGURATION September October value instance November December F238 ENUMERATION: REAL TIME CLOCK DAY value Sunday Monday Tuesday Wednesday F260 Thursday ENUMERATION: DATA LOGGER MODE Friday 0 = Continuous, 1 = Trigger Saturday B-84 L30 Line Current Differential System GE Multilin...
  • Page 549 IDs. The operate bit for element ID [44] NOR (2 to 16 inputs) X is bit [X mod 16] in register [X/16]. [46] NAND (2 to 16 inputs) [48] TIMER (1 to 32) GE Multilin L30 Line Current Differential System B-85...
  • Page 550 ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION Channel 2 CRC Fail bitmask default variation F511 BITFIELD: 3-PHASE SIMPLE ELEMENT STATE 0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate C B-86 L30 Line Current Differential System GE Multilin...
  • Page 551 210° lag 240° lag 270° lag 300° lag 330° lag F561 ENUMERATION: 87L INRUSH INHIBIT MODE Enumeration Inrush inhibit mode Disabled Per phase Two out of three Average GE Multilin L30 Line Current Differential System B-87...
  • Page 552 PIOC7.ST.Str.general UR_UINT16: FLEXINTEGER PARAMETER PIOC7.ST.Op.general This 16-bit value corresponds to the Modbus address of the PIOC8.ST.Str.general selected FlexInteger paramter. Only certain values may be used as FlexIntegers. PIOC8.ST.Op.general PIOC9.ST.Str.general PIOC9.ST.Op.general PIOC10.ST.Str.general PIOC10.ST.Op.general B-88 L30 Line Current Differential System GE Multilin...
  • Page 553 PIOC29.ST.Op.general PIOC56.ST.Str.general PIOC30.ST.Str.general PIOC56.ST.Op.general PIOC30.ST.Op.general PIOC57.ST.Str.general PIOC31.ST.Str.general PIOC57.ST.Op.general PIOC31.ST.Op.general PIOC58.ST.Str.general PIOC32.ST.Str.general PIOC58.ST.Op.general PIOC32.ST.Op.general PIOC59.ST.Str.general PIOC33.ST.Str.general PIOC59.ST.Op.general PIOC33.ST.Op.general PIOC60.ST.Str.general PIOC34.ST.Str.general PIOC60.ST.Op.general PIOC34.ST.Op.general PIOC61.ST.Str.general PIOC35.ST.Str.general PIOC61.ST.Op.general PIOC35.ST.Op.general PIOC62.ST.Str.general PIOC36.ST.Str.general PIOC62.ST.Op.general PIOC36.ST.Op.general PIOC63.ST.Str.general PIOC37.ST.Str.general PIOC63.ST.Op.general GE Multilin L30 Line Current Differential System B-89...
  • Page 554 PTOC10.ST.Op.general PTRC3.ST.Tr.general PTOC11.ST.Str.general PTRC3.ST.Op.general PTOC11.ST.Op.general PTRC4.ST.Tr.general PTOC12.ST.Str.general PTRC4.ST.Op.general PTOC12.ST.Op.general PTRC5.ST.Tr.general PTOC13.ST.Str.general PTRC5.ST.Op.general PTOC13.ST.Op.general PTRC6.ST.Tr.general PTOC14.ST.Str.general PTRC6.ST.Op.general PTOC14.ST.Op.general PTUV1.ST.Str.general PTOC15.ST.Str.general PTUV1.ST.Op.general PTOC15.ST.Op.general PTUV2.ST.Str.general PTOC16.ST.Str.general PTUV2.ST.Op.general PTOC16.ST.Op.general PTUV3.ST.Str.general PTOC17.ST.Str.general PTUV3.ST.Op.general PTOC17.ST.Op.general PTUV4.ST.Str.general PTOC18.ST.Str.general PTUV4.ST.Op.general B-90 L30 Line Current Differential System GE Multilin...
  • Page 555 RBRF10.ST.OpIn.general CSWI3.ST.Loc.stVal RBRF11.ST.OpEx.general CSWI3.ST.Pos.stVal RBRF11.ST.OpIn.general CSWI4.ST.Loc.stVal RBRF12.ST.OpEx.general CSWI4.ST.Pos.stVal RBRF12.ST.OpIn.general CSWI5.ST.Loc.stVal RBRF13.ST.OpEx.general CSWI5.ST.Pos.stVal RBRF13.ST.OpIn.general CSWI6.ST.Loc.stVal RBRF14.ST.OpEx.general CSWI6.ST.Pos.stVal RBRF14.ST.OpIn.general CSWI7.ST.Loc.stVal RBRF15.ST.OpEx.general CSWI7.ST.Pos.stVal RBRF15.ST.OpIn.general CSWI8.ST.Loc.stVal RBRF16.ST.OpEx.general CSWI8.ST.Pos.stVal RBRF16.ST.OpIn.general CSWI9.ST.Loc.stVal RBRF17.ST.OpEx.general CSWI9.ST.Pos.stVal RBRF17.ST.OpIn.general CSWI10.ST.Loc.stVal RBRF18.ST.OpEx.general CSWI10.ST.Pos.stVal GE Multilin L30 Line Current Differential System B-91...
  • Page 556 CSWI29.ST.Pos.stVal GGIO1.ST.Ind51.stVal CSWI30.ST.Loc.stVal GGIO1.ST.Ind52.stVal CSWI30.ST.Pos.stVal GGIO1.ST.Ind53.stVal GGIO1.ST.Ind1.stVal GGIO1.ST.Ind54.stVal GGIO1.ST.Ind2.stVal GGIO1.ST.Ind55.stVal GGIO1.ST.Ind3.stVal GGIO1.ST.Ind56.stVal GGIO1.ST.Ind4.stVal GGIO1.ST.Ind57.stVal GGIO1.ST.Ind5.stVal GGIO1.ST.Ind58.stVal GGIO1.ST.Ind6.stVal GGIO1.ST.Ind59.stVal GGIO1.ST.Ind7.stVal GGIO1.ST.Ind60.stVal GGIO1.ST.Ind8.stVal GGIO1.ST.Ind61.stVal GGIO1.ST.Ind9.stVal GGIO1.ST.Ind62.stVal GGIO1.ST.Ind10.stVal GGIO1.ST.Ind63.stVal GGIO1.ST.Ind11.stVal GGIO1.ST.Ind64.stVal GGIO1.ST.Ind12.stVal GGIO1.ST.Ind65.stVal GGIO1.ST.Ind13.stVal GGIO1.ST.Ind66.stVal B-92 L30 Line Current Differential System GE Multilin...
  • Page 557 GGIO1.ST.Ind104.stVal MMXU1.MX.VAr.phsA.cVal.mag.f GGIO1.ST.Ind105.stVal MMXU1.MX.VAr.phsB.cVal.mag.f GGIO1.ST.Ind106.stVal MMXU1.MX.VAr.phsC.cVal.mag.f GGIO1.ST.Ind107.stVal MMXU1.MX.VA.phsA.cVal.mag.f GGIO1.ST.Ind108.stVal MMXU1.MX.VA.phsB.cVal.mag.f GGIO1.ST.Ind109.stVal MMXU1.MX.VA.phsC.cVal.mag.f GGIO1.ST.Ind110.stVal MMXU1.MX.PF.phsA.cVal.mag.f GGIO1.ST.Ind111.stVal MMXU1.MX.PF.phsB.cVal.mag.f GGIO1.ST.Ind112.stVal MMXU1.MX.PF.phsC.cVal.mag.f GGIO1.ST.Ind113.stVal MMXU2.MX.TotW.mag.f GGIO1.ST.Ind114.stVal MMXU2.MX.TotVAr.mag.f GGIO1.ST.Ind115.stVal MMXU2.MX.TotVA.mag.f GGIO1.ST.Ind116.stVal MMXU2.MX.TotPF.mag.f GGIO1.ST.Ind117.stVal MMXU2.MX.Hz.mag.f GGIO1.ST.Ind118.stVal MMXU2.MX.PPV.phsAB.cVal.mag.f GGIO1.ST.Ind119.stVal MMXU2.MX.PPV.phsAB.cVal.ang.f GE Multilin L30 Line Current Differential System B-93...
  • Page 558 MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.A.neut.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.A.neut.cVal.ang.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.W.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU3.MX.A.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU3.MX.A.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f B-94 L30 Line Current Differential System GE Multilin...
  • Page 559 MMXU6.MX.TotVA.mag.f GGIO4.MX.AnIn19.mag.f MMXU6.MX.TotPF.mag.f GGIO4.MX.AnIn20.mag.f MMXU6.MX.Hz.mag.f GGIO4.MX.AnIn21.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f GGIO4.MX.AnIn22.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f GGIO4.MX.AnIn23.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f GGIO4.MX.AnIn24.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f GGIO4.MX.AnIn25.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f GGIO4.MX.AnIn26.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f GGIO4.MX.AnIn27.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f GGIO4.MX.AnIn28.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f GGIO4.MX.AnIn29.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f GGIO4.MX.AnIn30.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f GGIO4.MX.AnIn31.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f GGIO4.MX.AnIn32.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f XSWI1.ST.Loc.stVal MMXU6.MX.A.phsA.cVal.mag.f XSWI1.ST.Pos.stVal GE Multilin L30 Line Current Differential System B-95...
  • Page 560 GGIO1.ST.Ind14.q XSWI20.ST.Pos.stVal GGIO1.ST.Ind14.stVal XSWI21.ST.Loc.stVal GGIO1.ST.Ind15.q XSWI21.ST.Pos.stVal GGIO1.ST.Ind15.stVal XSWI22.ST.Loc.stVal GGIO1.ST.Ind16.q XSWI22.ST.Pos.stVal GGIO1.ST.Ind16.stVal XSWI23.ST.Loc.stVal GGIO1.ST.Ind17.q XSWI23.ST.Pos.stVal GGIO1.ST.Ind17.stVal XSWI24.ST.Loc.stVal GGIO1.ST.Ind18.q XSWI24.ST.Pos.stVal GGIO1.ST.Ind18.stVal XCBR1.ST.Loc.stVal GGIO1.ST.Ind19.q XCBR1.ST.Pos.stVal GGIO1.ST.Ind19.stVal XCBR2.ST.Loc.stVal GGIO1.ST.Ind20.q XCBR2.ST.Pos.stVal GGIO1.ST.Ind20.stVal XCBR3.ST.Loc.stVal GGIO1.ST.Ind21.q XCBR3.ST.Pos.stVal GGIO1.ST.Ind21.stVal XCBR4.ST.Loc.stVal B-96 L30 Line Current Differential System GE Multilin...
  • Page 561 GGIO1.ST.Ind40.stVal GGIO1.ST.Ind67.q GGIO1.ST.Ind41.q GGIO1.ST.Ind67.stVal GGIO1.ST.Ind41.stVal GGIO1.ST.Ind68.q GGIO1.ST.Ind42.q GGIO1.ST.Ind68.stVal GGIO1.ST.Ind42.stVal GGIO1.ST.Ind69.q GGIO1.ST.Ind43.q GGIO1.ST.Ind69.stVal GGIO1.ST.Ind43.stVal GGIO1.ST.Ind70.q GGIO1.ST.Ind44.q GGIO1.ST.Ind70.stVal GGIO1.ST.Ind44.stVal GGIO1.ST.Ind71.q GGIO1.ST.Ind45.q GGIO1.ST.Ind71.stVal GGIO1.ST.Ind45.stVal GGIO1.ST.Ind72.q GGIO1.ST.Ind46.q GGIO1.ST.Ind72.stVal GGIO1.ST.Ind46.stVal GGIO1.ST.Ind73.q GGIO1.ST.Ind47.q GGIO1.ST.Ind73.stVal GGIO1.ST.Ind47.stVal GGIO1.ST.Ind74.q GGIO1.ST.Ind48.q GGIO1.ST.Ind74.stVal GE Multilin L30 Line Current Differential System B-97...
  • Page 562 GGIO1.ST.Ind93.stVal GGIO1.ST.Ind120.q GGIO1.ST.Ind94.q GGIO1.ST.Ind120.stVal GGIO1.ST.Ind94.stVal GGIO1.ST.Ind121.q GGIO1.ST.Ind95.q GGIO1.ST.Ind121.stVal GGIO1.ST.Ind95.stVal GGIO1.ST.Ind122.q GGIO1.ST.Ind96.q GGIO1.ST.Ind122.stVal GGIO1.ST.Ind96.stVal GGIO1.ST.Ind123.q GGIO1.ST.Ind97.q GGIO1.ST.Ind123.stVal GGIO1.ST.Ind97.stVal GGIO1.ST.Ind124.q GGIO1.ST.Ind98.q GGIO1.ST.Ind124.stVal GGIO1.ST.Ind98.stVal GGIO1.ST.Ind125.q GGIO1.ST.Ind99.q GGIO1.ST.Ind125.stVal GGIO1.ST.Ind99.stVal GGIO1.ST.Ind126.q GGIO1.ST.Ind100.q GGIO1.ST.Ind126.stVal GGIO1.ST.Ind100.stVal GGIO1.ST.Ind127.q GGIO1.ST.Ind101.q GGIO1.ST.Ind127.stVal B-98 L30 Line Current Differential System GE Multilin...
  • Page 563 MMXU1.MX.PF.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU1.MX.PF.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU2.MX.TotW.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU2.MX.TotVAr.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU2.MX.TotVA.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU2.MX.TotPF.mag.f MMXU3.MX.A.phsB.cVal.mag.f MMXU2.MX.Hz.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU2.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU2.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.A.phsC.cVal.ang.f MMXU2.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU2.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.A.neut.cVal.ang.f MMXU2.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU2.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.W.phsB.cVal.mag.f MMXU2.MX.PhV.phsA.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU2.MX.PhV.phsA.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU2.MX.PhV.phsB.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f GE Multilin L30 Line Current Differential System B-99...
  • Page 564 MMXU4.MX.VAr.phsC.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU6.MX.A.phsA.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU6.MX.A.phsA.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU6.MX.A.phsB.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU6.MX.A.phsB.cVal.ang.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU6.MX.A.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU6.MX.A.phsC.cVal.ang.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU6.MX.A.neut.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU6.MX.A.neut.cVal.ang.f B-100 L30 Line Current Differential System GE Multilin...
  • Page 565 GGIO4.MX.AnIn26.mag.f PDIS4.ST.Str.general GGIO4.MX.AnIn27.mag.f PDIS4.ST.Op.general GGIO4.MX.AnIn28.mag.f PDIS5.ST.Str.general GGIO4.MX.AnIn29.mag.f PDIS5.ST.Op.general GGIO4.MX.AnIn30.mag.f PDIS6.ST.Str.general GGIO4.MX.AnIn31.mag.f PDIS6.ST.Op.general GGIO4.MX.AnIn32.mag.f PDIS7.ST.Str.general GGIO5.ST.UIntIn1.q PDIS7.ST.Op.general GGIO5.ST.UIntIn1.stVal PDIS8.ST.Str.general GGIO5.ST.UIntIn2.q PDIS8.ST.Op.general GGIO5.ST.UIntIn2.stVal PDIS9.ST.Str.general GGIO5.ST.UIntIn3.q PDIS9.ST.Op.general GGIO5.ST.UIntIn3.stVal PDIS10.ST.Str.general GGIO5.ST.UIntIn4.q PDIS10.ST.Op.general GGIO5.ST.UIntIn4.stVal PIOC1.ST.Str.general GGIO5.ST.UIntIn5.q PIOC1.ST.Op.general GE Multilin L30 Line Current Differential System B-101...
  • Page 566 PIOC20.ST.Op.general PIOC47.ST.Str.general PIOC21.ST.Str.general PIOC47.ST.Op.general PIOC21.ST.Op.general PIOC48.ST.Str.general PIOC22.ST.Str.general PIOC48.ST.Op.general PIOC22.ST.Op.general PIOC49.ST.Str.general PIOC23.ST.Str.general PIOC49.ST.Op.general PIOC23.ST.Op.general PIOC50.ST.Str.general PIOC24.ST.Str.general PIOC50.ST.Op.general PIOC24.ST.Op.general PIOC51.ST.Str.general PIOC25.ST.Str.general PIOC51.ST.Op.general PIOC25.ST.Op.general PIOC52.ST.Str.general PIOC26.ST.Str.general PIOC52.ST.Op.general PIOC26.ST.Op.general PIOC53.ST.Str.general PIOC27.ST.Str.general PIOC53.ST.Op.general PIOC27.ST.Op.general PIOC54.ST.Str.general PIOC28.ST.Str.general PIOC54.ST.Op.general B-102 L30 Line Current Differential System GE Multilin...
  • Page 567 PTOC1.ST.Op.general PTOV4.ST.Str.general PTOC2.ST.Str.general PTOV4.ST.Op.general PTOC2.ST.Op.general PTOV5.ST.Str.general PTOC3.ST.Str.general PTOV5.ST.Op.general PTOC3.ST.Op.general PTOV6.ST.Str.general PTOC4.ST.Str.general PTOV6.ST.Op.general PTOC4.ST.Op.general PTOV7.ST.Str.general PTOC5.ST.Str.general PTOV7.ST.Op.general PTOC5.ST.Op.general PTOV8.ST.Str.general PTOC6.ST.Str.general PTOV8.ST.Op.general PTOC6.ST.Op.general PTOV9.ST.Str.general PTOC7.ST.Str.general PTOV9.ST.Op.general PTOC7.ST.Op.general PTOV10.ST.Str.general PTOC8.ST.Str.general PTOV10.ST.Op.general PTOC8.ST.Op.general PTRC1.ST.Tr.general PTOC9.ST.Str.general PTRC1.ST.Op.general GE Multilin L30 Line Current Differential System B-103...
  • Page 568 RBRF1.ST.OpIn.general RPSB1.ST.Op.general RBRF2.ST.OpEx.general RPSB1.ST.BlkZn.stVal RBRF2.ST.OpIn.general RREC1.ST.Op.general RBRF3.ST.OpEx.general RREC1.ST.AutoRecSt.stVal RBRF3.ST.OpIn.general RREC2.ST.Op.general RBRF4.ST.OpEx.general RREC2.ST.AutoRecSt.stVal RBRF4.ST.OpIn.general RREC3.ST.Op.general RBRF5.ST.OpEx.general RREC3.ST.AutoRecSt.stVal RBRF5.ST.OpIn.general RREC4.ST.Op.general RBRF6.ST.OpEx.general RREC4.ST.AutoRecSt.stVal RBRF6.ST.OpIn.general RREC5.ST.Op.general RBRF7.ST.OpEx.general RREC5.ST.AutoRecSt.stVal RBRF7.ST.OpIn.general RREC6.ST.Op.general RBRF8.ST.OpEx.general RREC6.ST.AutoRecSt.stVal RBRF8.ST.OpIn.general CSWI1.ST.Loc.stVal RBRF9.ST.OpEx.general CSWI1.ST.Pos.stVal B-104 L30 Line Current Differential System GE Multilin...
  • Page 569 CSWI20.ST.Pos.stVal XSWI17.ST.Loc.stVal CSWI21.ST.Loc.stVal XSWI17.ST.Pos.stVal CSWI21.ST.Pos.stVal XSWI18.ST.Loc.stVal CSWI22.ST.Loc.stVal XSWI18.ST.Pos.stVal CSWI22.ST.Pos.stVal XSWI19.ST.Loc.stVal CSWI23.ST.Loc.stVal XSWI19.ST.Pos.stVal CSWI23.ST.Pos.stVal XSWI20.ST.Loc.stVal CSWI24.ST.Loc.stVal XSWI20.ST.Pos.stVal CSWI24.ST.Pos.stVal XSWI21.ST.Loc.stVal CSWI25.ST.Loc.stVal XSWI21.ST.Pos.stVal CSWI25.ST.Pos.stVal XSWI22.ST.Loc.stVal CSWI26.ST.Loc.stVal XSWI22.ST.Pos.stVal CSWI26.ST.Pos.stVal XSWI23.ST.Loc.stVal CSWI27.ST.Loc.stVal XSWI23.ST.Pos.stVal CSWI27.ST.Pos.stVal XSWI24.ST.Loc.stVal CSWI28.ST.Loc.stVal XSWI24.ST.Pos.stVal GE Multilin L30 Line Current Differential System B-105...
  • Page 570 Synchronized (No PDelay) Enumeration Role None F626 Administrator ENUMERATION: NETWORK PORT FOR REMOTE DEVICE Supervisor Engineer Enumeration Item Operator None Observer Network Port 1 Factory Service Network Port 2 Network Port 3 B-106 L30 Line Current Differential System GE Multilin...
  • Page 571: C.1.1 Introduction

    The L30 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks. The TP4/CLNP profile requires the L30 to have a network address or Network Service Access Point (NSAP) to establish a communication link. The TCP/IP profile requires the L30 to have an IP address to establish communications. These addresses are located in the ...
  • Page 572: C.2.1 Overview

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the L30 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
  • Page 573: C.2.6 Mmxu: Analog Measured Values

    A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a L30 current and voltage source. There is one MMXU available for each con- figurable source (programmed in the ...
  • Page 574 The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the L30 protection elements, these flags take their values from the pickup and operate FlexLogic operands for the corresponding element.
  • Page 575: C.3.1 Buffered/Unbuffered Reporting

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the L30. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.
  • Page 576: C.3.6 Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the L30 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the L30. This frees up the con- nection to be used by other clients.
  • Page 577: C.4.1 Overview

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the L30 will use the source Ether- net MAC address as the destination, with the multicast bit set.
  • Page 578 The L30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 579 REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic equations or other settings. The L30 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 580: C.4.5 Ethernet Mac Address For Gsse/Goose

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the L30 is configured to use an automated multicast MAC scheme. If the L30 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
  • Page 581: C.5.1 Overview

    The L30 can be configured for IEC 61850 via the EnerVista UR Setup software as follows. An ICD file is generated for the L30 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 582: C.5.2 Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the L30 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
  • Page 583: C.5.3 About Icd Files

    (which also includes SSD, CID and SCD files). The ICD file describes the capabilities of an IED and consists of four major sections: • Header • Communication • IEDs • DataTypeTemplates GE Multilin L30 Line Current Differential System C-13...
  • Page 584 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. C-14 L30 Line Current Differential System GE Multilin...
  • Page 585 Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure 0–4: ICD FILE STRUCTURE, IED NODE GE Multilin L30 Line Current Differential System C-15...
  • Page 586 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure 0–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE C-16 L30 Line Current Differential System GE Multilin...
  • Page 587: C.5.4 Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline L30 settings file is typically much quicker than create an ICD file directly from the relay.
  • Page 588 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure 0–7: SCD FILE STRUCTURE, SUBSTATION NODE C-18 L30 Line Current Differential System GE Multilin...
  • Page 589 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. GE Multilin L30 Line Current Differential System C-19...
  • Page 590: C.5.6 Importing An Scd File With Enervista Ur Setup

    Figure 0–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the L30 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
  • Page 591 File to Device item. The software will prompt for the target device. Select the target device from the list provided and click Send. The new settings will be updated to the selected device. GE Multilin L30 Line Current Differential System C-21...
  • Page 592: C.6.1 Acsi Basic Conformance Statement

    REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion C-22 L30 Line Current Differential System GE Multilin...
  • Page 593: C.6.3 Acsi Services Conformance Statement

    UR FAMILY PUBLISHER SERVER (CLAUSE 7) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 8) Associate Abort Release LOGICAL DEVICE (CLAUSE 9) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 10) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 11) GetDataValues SetDataValues GetDataDirectory GetDataDefinition GE Multilin L30 Line Current Differential System C-23...
  • Page 594 LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 18, ANNEX C) GOOSE-CONTROL-BLOCK (CLAUSE 18) SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK (ANNEX C) SendGSSEMessage GetReference GetGSSEElementNumber GetGsCBValues C-24 L30 Line Current Differential System GE Multilin...
  • Page 595 (SendGOOSEMessage or SendGSSEMessage) NOTE c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) GE Multilin L30 Line Current Differential System C-25...
  • Page 596: C.7.1 Logical Nodes Table

    GGIO: Generic process I/O GLOG: Generic log GSAL: Generic security application I: LOGICAL NODES FOR INTERFACING AND ARCHIVING IARC: Archiving IHMI: Human machine interface ISAF: Safety alarm function ITCI: Telecontrol interface ITMI: Telemonitoring interface C-26 L30 Line Current Differential System GE Multilin...
  • Page 597 PSCH: Protection scheme PSDE: Sensitive directional earth fault PTEF: Transient earth fault PTOC: Time overcurrent PTOF: Overfrequency PTOV: Overvoltage PTRC: Protection trip conditioning PTTR: Thermal overload PTUC: Undercurrent PTUF: Underfrequency PTUV: Undervoltage GE Multilin L30 Line Current Differential System C-27...
  • Page 598 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TANG: Angle TAXD: Axial displacement TCTR: Current transformer TDST: Distance TFLW: Liquid flow TFRQ: Frequency TGSN: Generic sensor THUM: Humidity TLVL: Media level TMGF: Magnetic field TMVM: Movement sensor C-28 L30 Line Current Differential System GE Multilin...
  • Page 599 ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRES: Resistor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZSCR: Semi-conductor controlled rectifier ZSMC: Synchronous machine ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component GE Multilin L30 Line Current Differential System C-29...
  • Page 600 C.7 LOGICAL NODES APPENDIX C C-30 L30 Line Current Differential System GE Multilin...
  • Page 601: D.1.1 Interoperability Document

    Balanced Transmision Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin L30 Line Current Differential System...
  • Page 602  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 L30 Line Current Differential System GE Multilin...
  • Page 603  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin L30 Line Current Differential System...
  • Page 604 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 L30 Line Current Differential System GE Multilin...
  • Page 605 M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin L30 Line Current Differential System...
  • Page 606 F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure L30 Line Current Differential System GE Multilin...
  • Page 607  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin L30 Line Current Differential System...
  • Page 608 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs L30 Line Current Differential System GE Multilin...
  • Page 609: D.1.2 Point List

    The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin L30 Line Current Differential System...
  • Page 610 D.1 IEC 60870-5-104 APPENDIX D D-10 L30 Line Current Differential System GE Multilin...
  • Page 611: E.1.1 Dnp V3.00 Device Profile

    Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin L30 Line Current Differential System...
  • Page 612 FlexLogic. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. L30 Line Current Differential System GE Multilin...
  • Page 613  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin L30 Line Current Differential System...
  • Page 614: E.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. L30 Line Current Differential System GE Multilin...
  • Page 615 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. GE Multilin L30 Line Current Differential System...
  • Page 616 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. L30 Line Current Differential System GE Multilin...
  • Page 617 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. GE Multilin L30 Line Current Differential System...
  • Page 618: E.2.1 Binary Input Points

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 L30 Line Current Differential System GE Multilin...
  • Page 619: E.2.2 Binary And Control Relay Output

    Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin L30 Line Current Differential System...
  • Page 620: E.2.3 Counters

    Events Since Last Clear A counter freeze command has no meaning for counters 8 and 9. L30 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.
  • Page 621: E.2.4 Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin L30 Line Current Differential System E-11...
  • Page 622 E.2 DNP POINT LISTS APPENDIX E E-12 L30 Line Current Differential System GE Multilin...
  • Page 623: F.1.1 Revision History

    Minor changes throughout document Delete Deleted CPU options U and V Update Updated Figure 1-1 Rear Nameplate Update Updated Figure 3-10 Rear Terminal View Table F–3: MAJOR UPDATES FOR L30 MANUAL REVISION Y1 (Sheet 1 of 3) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1)
  • Page 624 F.1 CHANGE NOTES APPENDIX F Table F–3: MAJOR UPDATES FOR L30 MANUAL REVISION Y1 (Sheet 2 of 3) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1) 5-37 Delete Deleted Local Time Offset, Daylight Savings Time, DST (start/stop for month/day/hour) from Real Time Clock menu...
  • Page 625 APPENDIX F F.1 CHANGE NOTES Table F–3: MAJOR UPDATES FOR L30 MANUAL REVISION Y1 (Sheet 3 of 3) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1) Added to Minor self-test error message **Bad PTP Signal** Added new section for CyberSentry software option with overview and security menu subsections Added Flexanalog item PTP–IRIG-B Delta to Table A-1: Flexanalog Data Items...
  • Page 626 F.1 CHANGE NOTES APPENDIX F Table F–4: MAJOR UPDATES FOR L30 MANUAL REVISION X2 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (X1) (X2) Update Added IEC codes to headings Update Added 50 to range for PMU 1 Rate diagram in section 5.4b Basic Configuration...
  • Page 627 APPENDIX F F.1 CHANGE NOTES Table F–7: MAJOR UPDATES FOR L30 MANUAL REVISION V2 PAGE PAGE CHANGE DESCRIPTION (V1) (V2) Title Title Update Manual part number to 1601-9050-V2 Update Updated ORDERING section 3-23 3-23 Update Updated RS485 PORTS section Table F–8: MAJOR UPDATES FOR L30 MANUAL REVISION V1...
  • Page 628 F.1 CHANGE NOTES APPENDIX F Table F–10: MAJOR UPDATES FOR L30 MANUAL REVISION U1 PAGE PAGE CHANGE DESCRIPTION (T1) (U1) Title Title Update Manual part number to 1601-9050-U1 2-17 2-17 Update Updated PROTECTION ELEMENTS section for changes to line current differential and...
  • Page 629: F.2.1 Standard Abbreviations

    .EVT ....Filename extension for event recorder files EXT ....Extension, External F ..... Field FAIL....Failure FD ....Fault Detector FDH....Fault Detector high-set FDL ....Fault Detector low-set FLA....Full Load Current FO ....Fiber Optic GE Multilin L30 Line Current Differential System...
  • Page 630 MTR ....Motor MVA....MegaVolt-Ampere (total 3-phase) MVA_A ... MegaVolt-Ampere (phase A) MVA_B ... MegaVolt-Ampere (phase B) MVA_C ... MegaVolt-Ampere (phase C) MVAR ..... MegaVar (total 3-phase) MVAR_A..MegaVar (phase A) MVAR_B..MegaVar (phase B) L30 Line Current Differential System GE Multilin...
  • Page 631 RX (Rx) ..Receive, Receiver s ..... second S..... Sensitive SAT ....CT Saturation SBO....Select Before Operate SCADA... Supervisory Control and Data Acquisition SEC....Secondary SEL ....Select / Selector / Selection SENS ..... Sensitive GE Multilin L30 Line Current Differential System...
  • Page 632 VTLOS ... Voltage Transformer Loss Of Signal WDG ....Winding WH ....Watt-hour w/ opt....With Option WRT ....With Respect To X..... Reactance XDUCER ..Transducer XFMR ..... Transformer Z ..... Impedance, Zone F-10 L30 Line Current Differential System GE Multilin...
  • Page 633: F.3.1 Ge Multilin Warranty

    GE Multilin is not liable for special, indirect or consequential damages or for loss of profit or for expenses sustained as a result of a relay malfunction, incorrect application or adjustment. For complete text of Warranty (including limitations and disclaimers), refer to GE Multilin Standard Conditions of Sale. GE Multilin L30 Line Current Differential System F-11...
  • Page 634 F.3 WARRANTY APPENDIX F F-12 L30 Line Current Differential System GE Multilin...
  • Page 635 Modbus registers ............B-60 settings ............... 5-179 procedures ..............11-1 specifications ..............2-18 settings ............... 5-242 AUXILIARY VOLTAGE CHANNEL ........3-12 CHANNELS AUXILIARY VOLTAGE METERING ........6-17 banks ..............5-71, 5-72 number of ..............5-76 GE Multilin L30 Line Current Differential System...
  • Page 636 ..............6-7 current ............2-15, 2-17, 5-139 settings ............... 5-207 current metering .............6-14 CRC-16 ALGORITHM ............B-2 element characteristics ...........9-14 CRITICAL FAILURE RELAY ........2-23, 3-10 line elements ............... 5-138 CSA APPROVAL .............. 2-27 L30 Line Current Differential System GE Multilin...
  • Page 637 Modbus ................B-7 settings ................. 5-25 Modbus registers ..........B-18, B-29 DTT .................2-14, 11-4 settings ................. 5-50 DUPLEX, HALF ..............B-1 FAULT REPORTS Modbus registers ............B-47 FAULT TYPE ..............9-20 FAX NUMBERS ..............1-1 GE Multilin L30 Line Current Differential System...
  • Page 638 IEC CURVES ..............5-147 tracking ................9-6 IED ................... 1-2 FREQUENCY METERING IED SETUP ............... 1-5 actual values ..............6-18 IEEE C37.94 COMMUNICATIONS ....3-33, 3-34, 3-37 Modbus registers ............B-14 IEEE CURVES ..............5-146 L30 Line Current Differential System GE Multilin...
  • Page 639 FlexLogic operands ............5-121 LOGIC GATES ............... 5-127 logic ................5-166 LOOP FILTER BLOCK DIAGRAM ........9-10 Modbus registers ............B-39 LOOPBACK ............2-14, 5-242 settings ............... 5-166 LOST PASSWORD ........... 5-9, 5-10 GE Multilin L30 Line Current Differential System...
  • Page 640 ................5-152 settings ................. 5-52 Modbus registers ............B-35 specifications..............2-20 specifications ..............2-17 via COMTRADE .............. B-6 PHASE LOCKING ............9-6, 9-10 via EnerVista software ............. 4-2 PHASE MEASUREMENT UNIT see entry for SYNCHROPHASOR OUTPUTS L30 Line Current Differential System GE Multilin...
  • Page 641 ............... 5-190, 5-191 RELAY MAINTENANCE ............. 7-3 Self-test errors ..............7-11 RELAY NAME ..............5-69 SELF-TESTS RELAY NOT PROGRAMMED ........... 1-17 description .............. 2-16, 7-6 RELAY SYNCHRONIZATION ..........9-15 error messages ..............7-8 GE Multilin L30 Line Current Differential System...
  • Page 642 ..............2-19 TRIP DECISION EXAMPLE ..........9-18 SYNCHRONIZATION RELAY ..........9-15 TRIP LEDs ...............5-57 SYNCHROPHASORS TROUBLE INDICATOR ..........1-17, 7-6 actual values ..............6-20 TYPICAL WIRING DIAGRAM ..........3-9 clearing PMU records ............7-2 viii L30 Line Current Differential System GE Multilin...
  • Page 643 WEBSITE ................1-1 USER-PROGRAMMABLE SELF TESTS WIRING DIAGRAM ............. 3-9 Modbus registers ............B-30 settings ................. 5-58 USERST-1 BIT PAIR ............5-229 ZERO SEQUENCE CORE BALANCE ........ 3-12 ZERO-SEQUENCE CURRENT REMOVAL ......5-78 GE Multilin L30 Line Current Differential System...
  • Page 644 INDEX L30 Line Current Differential System GE Multilin...

Table of Contents