Download Print this page

Allen-Bradley 140M Installation Instructions Manual page 4

Jd-frame motor circuit protector

Advertisement

by a color-coded strip for each MCP handle position: red
for ON, white for tripped, and green for OFF. (See Fig.
3-1.)
Handle Position Indicator
Color
ON
TRIP
OFF
(Reset)
International
Symbols
ON
OFF
Electro-Mechanical Trip
Device Adjustment Button
(3 Places)
Figure 3-1 MCP Manual Controls
Table 2-1 Terminal Types ①
Terminal Terminal
Screw
Cat. No. Material
Head
Body
Type
Standard
Terminal
TA250KB Aluminum Socket
Standard
Terminal
T250KB
Stainless
Socket
Steel
① Terminal wire connectors are listed for standard wire
sizes as defined in UL486A and UL486B.
40752-165(1)
Effective March 2008
Red – ON
White – TRIP
Green – OFF (Reset)
Push-To-Trip
Button
AWG
Metric
Wire
Torque
Wire
Wire
Type
Value
Range
Range
lb-in
(N.m.)
4-350
25-185
Cu/AI
275 (31)
MCM
4-350
25-185
Cu
180 (20)
MCM
Table 3-1 MCP Trip Settings
Cam
Motor
NEMA
Setting
Full Load
Starter
Current
Size
Amperes
A
38.5 – 43.4
5
B
43.5 – 48.0
5
C
48.1 – 53.0
5
D
53.1 – 57.6
5
E
57.7 – 62.3
5
F
62.4 – 67.3
5
G
67.4 – 71.9
5
H
72.0 – 76.9
5
I
77.0 – 81.6
5
A
57.7 – 64.6
5
B
64.7 – 71.9
5
C
72.0 – 79.2
5
D
79.3 – 86.5
5
E
86.6 – 93.8
5
F
93.9 – 101.1
5
G
101.2 – 108.4
5
H
108.5 – 115.3
5
I
115.4 – 122.4
5
A
67.4 – 75.3
5
B
75.4 – 83.8
5
C
83.9 – 92.3
5
D
92.4 – 100.7
5
E
100.8 – 109.2
5
F
109.3 – 117.6
5
G
117.7 – 126.1
5
H
126.2 – 134.6
5
I
134.7 – 142.8
5
Page 4
Continuous
MCP
MCP
Amps
Catalog
Trip
Number
Setting
500
565
625
690
9
250
140M-JD8P-C80 750
810
875
935
1000
750
840
935
1030
140M-JD8P-D12 1125
250
1220
1315
1410
1500
875
980
1090
1200
250
1310
140M-JD8P-D14
1420
1530
1640
1750

Advertisement

loading