contacts to see whether they are closed. If they are still not closed, dismantle the temperature sensing
disc and then immerse it into warm water to see w
hether the cont acts actuate, if n ot, it can be
preliminarily determine that temperature sensing agent has leaked out, and it must be replaced with a
new thermostat.
4) Motor troubles and other electric faults
a) Motor windings have been burned or short-circuited between turns
ANALYSIS OF TROUBLE
When moto r windin gs have been b urned or sh ort-circuited between turns, the fu se will be blown
repeatedly, and the blowout occurs particularly at the instant when you close the knife switch.
REMEDY
Check the te rminals and the outer casing to see whether they are short-ci rcuited, and measure the
resistance of each phase with an avometer. If short circuit occurs or the resistance of a certain phase
is low, this means that short circuit does exist in the winding s and/or between turns, and insulatio n
layers have been bur ned or deteriora ted. A megameter can b e used in this in spection, too. I f the
insulation resistance is lower than 2M , this means that the insulation layer is already breakdown. If the
motor has been burned, repair it or replaced it with a new one.
b) Fault of control relay
ANALYSIS OF TROUBLE
Overheat, burnout or wear of control relay cont acts may occu r generally. All these will cause poor
contact in electricity.
REMEDY
Dismantle it to repair, or replace it with a new one.
c) Poor electric contactor in thermostat
ANALYSIS OF TROUBLE
Burnout of contactor and leakage of temperature sensing agent may occur generally.
REMEDY
Replace the old with a new one.
d) Check the terminals for loose connection and electric circuits for other abnormal phenomena.
5) Mechanical faults of compressor
a) Seizing of shaft
This pheno menon is ca used mostly by poor lub rication, su ch ad insuf ficient quantity of lubricant ,
clogging in the lubricant oil line, or
in termittent lu bricant oil supply . Dirt and other impurities in the
lubricant oil will increase its viscosity and cause the shaft to be seized. Copper plating may also result
in seizing of shaft.
b) Seizing of piston
This is caused by too small fit clearance between the piston and cylinder or expansion due to heat.
Judgement of seizing shaft and piston After the refrigerator has been powered on, the compressor will
not start and run, but a slight hum sound can be h eard, and several seconds later, thermal protective
relay will actuate and make the con tacts open; this proces s will occur repeatedly, but the compressor
cannot be started.
E. Compressor won't stop
Sometimes, the compressor will run continuously(for several hours or run without end), If the
food
placed in the refrigerator i s not too much, there ma y be the following tw o situations: i) the refrigerator
very low, this means that the control system is proba bly out of order; ii) the control system work s