Real Time Alarms - ABB SM1000 User Manual

Inform it videographic recorder
Hide thumbs Also See for SM1000:
Table of Contents

Advertisement

...4 CONFIGURATION

4.8.2 Real Time Alarms

RTA 1
Linearizer
RTA 2
Real Time Alarm 1
Alarm Tag
None
Daily enables
Daily enables
Sunday
Monday
Tuesday
Wednesday
Thursdsay
Friday
Saturday
1st of the month enable
00:00
On time
On time
Every hour
Hours
Minutes
Off
Duration
Off
Log enable
78
RTA 3
RTA 4
Off
Off
0
0
Enter the tag to be used in the Alarm Event log –
see Section 2.7.
Select the day(s) on which the alarm is activated.
Set to 'On' to activate the real-time alarm on the first day of
each month.
Set the time at which the alarm becomes active.
If 'Every hour' is set to 'On', the 'Hours' setting cannot be
adjusted and the alarm is activated at the same time every
hour (determined by the 'Minutes' setting) or on the hour if
'Minutes' is set to 'Off'.
Set the duration for the alarm to remain active.
Set to 'On' to add an entry to the Alarm Event log each time
the real-time alarm becomes active.