West Control Solutions ProVU4 User Manual

Graphical controller with optional profiling & recording
Table of Contents

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for West Control Solutions ProVU4

  • Page 2 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual ProVU4 Graphical Controller with optional Profiling & Recording User Guide Part Number: 59407-3 Price: £13.00 $20.00 €18.00...
  • Page 4 THIS SYMBOL MEANS THE EQUIPMENT IS PROTECTED THROUGHOUT BY DOUBLE INSULATION. Products covered by this manual are suitable for Indoor use, Installation Category II, Pollution category 2 environments. This user guide covers all versions of the West ProVU4 controller. 59407, Issue 3 – May 2011 Page iii...
  • Page 5 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Warranty and Returns Statement These products are sold by West Instruments under the warranties set forth in the following paragraphs. Such warranties are extended only with respect to a purchase of these products,...
  • Page 6: Issue 3 – May 2011

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual How to use this manual This manual is structured to give easy access to the information required for all aspects of the installation and use and of the Graphical Controller. The main sections are shown here, followed by a full table of contents.
  • Page 7: Table Of Contents

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Contents Page Number: Warranty and Returns Statement ....................iv Introduction .......................... 14 Installation ..........................15 Unpacking ............................15 Installation ............................15 Panel-Mounting ........................... 15 Cleaning .............................. 16 Field Upgrade Options ......................17 Options Modules and Functions ......................
  • Page 8 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Messages and Error Indications ..................40 Start-up Errors ............................. 40 Input Problems ............................ 40 USB Data Transfer Problems ....................... 41 Getting Help ............................41 Configuration and Use ......................42 Operation Mode ........................... 42 Base, Trend &...
  • Page 9 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual USB Memory Stick Folders & Files ....................66 The Data Recorder Option ....................67 Introduction ............................67 Changes To Operation Mode ....................... 67 The Profiler Option ....................... 68 Profile Components ..........................68 Profile Starting & Standard Segments ....................69 Loops Segments..........................
  • Page 10 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Profile Setup Via Modbus........................115 Instrument Data ..........................130 Calibration ........................... 131 Calibration Reminder ......................... 131 Equipment Required For Checking or Calibrating The Universal Input ..........131 Calibration Check ..........................131 Recalibration Procedure ........................132 Appendix 1 –...
  • Page 11 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Custom Display Mode ........................141 Cycle Time ............................141 Data Recorder ........................... 141 Deadband ............................141 Derivative Action..........................141 Deviation Alarm Value ........................142 Digital Input ............................142 Direct Acting Control .......................... 142 Display Configuration .........................
  • Page 12 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual On-Off Control ........................... 149 On-Off Differential (On-Off Hysteresis) ....................149 Operation Mode ..........................150 Output Configuration .......................... 150 Overlap/Deadband..........................150 PD Control ............................152 PI Control ............................152 PID Control ............................152 PLC ..............................
  • Page 13 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Secondary Proportional Band ......................159 Self-Tune............................160 Sensor Break Pre-Set Power ......................160 Serial Communications Configuration ....................161 Serial Communications Option ......................161 Setpoint ............................. 161 Setpoint Upper Limit .......................... 161 Setpoint Lower Limit .......................... 161 Setpoint Ramp Editing ........................
  • Page 14 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Auxiliary Inputs ..........................176 Digital Inputs ............................177 Output Specifications ......................... 178 Communications ..........................180 Display .............................. 181 Control Loop ............................181 Data Recorder Option ........................181 Profiler Option............................ 182 Alarms ............................... 182 Conditions For Use ..........................
  • Page 15: Introduction

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 1 Introduction This product is a DIN size (96 x 96mm front) microprocessor based graphical process controller, featuring a 160 x 80 pixel, monochrome LCD with a dual colour (red/green) backlight. It can control process variables from a variety of sources such as temperature, pressure, flow and level.
  • Page 16: Installation

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 2 Installation Unpacking 1. Remove the product from its packing. Retain the packing for future use, in case it is necessary to transport the instrument to a different site or to return it to the supplier for repair/testing.
  • Page 17: Cleaning

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Instruments may be mounted side-by-side in a multiple installation, but instrument to panel moisture and dust sealing will be compromised. Allow a 20mm gap above, below and behind the instrument for ventilation. The cut-out width (for n instruments) is: (96n - 4) mm or (3.78n - 0.16) inches...
  • Page 18: Field Upgrade Options

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 3 Field Upgrade Options Options Modules and Functions The available plug-in modules, options and accessories are shown in below: Table 1. Options & Accessories BOARD PART DESCRIPTION IDENTIFICATION NUMBER NUMBER OPTION SLOT 1...
  • Page 19: Preparing To Install Or Remove Options Modules

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Board Positions Board Mounting Struts Option 4 Module Option A Module Option 3 Module Universal Input Board Power Supply Board Option B Module Option 1 Module (hidden below B) Option 2 Module Option C Module Figure 3.
  • Page 20: Removing/Replacing Option Modules

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Main Board Connectors POWER SUPPLY Option 3 Slot BOARD Connector PL4B Transformer Colour Code Option Slot A 100-240V (Yellow) Connectors PL5, & PL6 24-48V(Blue) Option 1 Slot Connectors PL7 & PL8 Display Board...
  • Page 21: Replacing The Instrument In Its Housing

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Replacing the Instrument in its Housing CAUTION: Before replacing the instrument in it’s housing, ensure that all power has been removed from the rear terminals. With the required option modules correctly located into their respective positions the instrument can be replaced into it’s housing as follows:...
  • Page 22: Data Recorder Board

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Data Recorder Board If installed, the Data Recorder memory and Real Time Clock (RTC) components are located on a plug-in daughter board attached to the front Display/CPU board. CAUTION: Servicing of the Data Recorder/RTC circuit and replacement of the lithium battery should only be carried out by a trained technician.
  • Page 23: Electrical Installation

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 4 Electrical Installation CAUTION: Installation should be only performed by technically competent personnel. It is the responsibility of the installing engineer to ensure that the configuration is safe. Local Regulations regarding electrical installation & safety must be observed (e.g.
  • Page 24: Use Of Shielded Cable

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Use of Shielded Cable All analogue signals must use shielded cable. This will help eliminate electrical noise induction on the wires. Connection lead length must be kept as short as possible keeping the wires protected by the shielding.
  • Page 25: Sensor Placement (Thermocouple Or Rtd)

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Sensor Placement (Thermocouple or RTD) If the temperature probe is to be subjected to corrosive or abrasive conditions, it must be protected by an appropriate thermowell. The probe must be positioned to reflect true process temperature: 1.
  • Page 26: Connections And Wiring

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Connections and Wiring This symbol means the equipment is protected throughout by double insulation. CAUTION: All external circuits connected must provide double insulation. Failure to comply with the installation instructions may impact the protection provided by the unit.
  • Page 27: Power Connections

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual The wiring diagram below shows the additional connections (numbered 25 to 42) at the sides of the case rear. These are required for Options Slots 4 and C if fitted. Figure 8. Additional Option terminals Note: Use single strand (1.2mm / AWG18 max size) copper wire throughout, except for the...
  • Page 28: Universal Input Connections

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Power Connections - 24/48V AC/DC Powered Instruments 24/48V AD/DC powered instruments will operate from a 20 to 48V AC or 22 to 55V DC supply. AC power consumption is 15VA max, DC power consumption is 12 watts max.
  • Page 29 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Universal Input Connections – PT100 / NI120 (RTD) input For three wire RTDs, connect the resistive leg and the common legs of the RTD as illustrated. For a two wire RTD a wire link should be used in place of the third wire (shown by dotted line).
  • Page 30: Option Slot 1 Connections

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Option Slot 1 Connections Option Slot 1 – Single Relay Output Module If option slot 1 is fitted with a single relay output module, make connections as illustrated. The relay contacts are SPDT and rated at 2 amps resistive, 240 VAC.
  • Page 31: Option Slot 2 Connections

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Option Slot 1 - Linear Voltage or mADC Output module If option slot 1 is fitted with a DC linear output module, make connections as illustrated. Figure 17. Option Slot 1 - Linear Voltage & mADC Module Option Slot 2 Connections Option Slot 2 –...
  • Page 32 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Option Slot 2 – Single SSR Driver Output Module If option slot 2 is fitted with a single SSR driver output module, make connections as illustrated. The solid-state relay driver is a 0-10V DC signal, load impedance must be no less than 500 ohms.
  • Page 33: Option Slot 3 Connections

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Option Slot 2 - Linear Voltage or mADC Output module If option slot 2 is fitted with a DC linear output module, make connections as illustrated. Figure 23. Option Slot 2 - Linear Voltage & mADC module...
  • Page 34 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Option Slot 3 - Dual Relay Output Module If option slot 3 is fitted with a dual relay output module, make connections as illustrated. This module has two independent SPST relays, which share a common connection terminal. The contacts are rated at 2 amp resistive 240 VAC.
  • Page 35 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Option Slot 3 – Dual SSR Driver Output Module If option slot 3 is fitted with a dual SSR driver output module, make connections as illustrated. The solid-state relay drivers are a 0-10V DC signal, load impedance must be no less than 500 ohms.
  • Page 36: Option Slot 4 Connections

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Option Slot 3 - Transmitter Power Supply Module If option slot 3 is fitted with a transmitter power supply module, make connections as illustrated. The output is an unregulated 24V DC, 22mA supply.
  • Page 37: Option Slot A Connections

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Option Slot A Connections Option Slot A Connections – Basic Auxiliary Input Module If option slot A is fitted with a basic auxiliary input module, connect as shown. Consider using the full auxiliary input (Option Slot B) instead, as this has additional features and leaves option slot A free for other modules.
  • Page 38: Option Slot B Connections

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual External computing devices connected to the communications port should comply with the standard, UL 60950. Option Slot B Connections Option Slot B Connections – Digital Input B (Full Auxiliary Module) If option slot B is fitted with the Full Auxiliary input module (see below), a secondary digital input is also provided.
  • Page 39: Powering Up

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 5 Powering Up CAUTION: Ensure safe wiring practices have been followed. When powering up for the first time, disconnect the output connections. The instrument must be powered from a supply according to the wiring label on the side of the unit.
  • Page 40: Led Functions

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual LED Functions There are four red LEDs that by default, indicate the status of the primary and secondary control outputs, automatic tuning and alarm status. The top line of the graphical display has four labels for LED indicators.
  • Page 41: Messages And Error Indications

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 6 Messages and Error Indications Start-up Errors The following displays are shown when an error detected during the power-up self-test. Option Module Problems The “Option Slot n Error” display is shown when an error detected with the installed option modules - where “n”...
  • Page 42: Usb Data Transfer Problems

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual PV Over-range or Under-range Indication If the measured process variable value is more than 5% above than the Scale Range Upper Limit, its value is replace by the word “HIGH”. If the measured process variable value is more than 5% below than the Scale Range Lower Limit, its value is replace by the word “LOW”.
  • Page 43: Configuration And Use

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 7 Configuration and Use Operation Mode This is the mode used during normal operation of the instrument. It can be accessed from the Main Menu, and is the usual mode entered at power-up. The available displays are dependent upon the features and options fitted and the way in which it has been configured.
  • Page 44 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Example Profile Operating Screen LED Indicators LED Function Labels Process Value & Setpoint Engineering Units Profile Name & Progress Segment No. & Progress Profile Status ■ ► Run, Held, Stopped ▌▌ Table 4. Operation Mode Screens Operation Mode: After 2 minutes without key activity, the most screens revert to the Base Operating Screen.
  • Page 45: Adjusting The Local Setpoint(S)

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Operator Profile Control Allows the operator to control the defined profiles. If a profile is running, the choices are: Do Nothing; Abort Profile (end immediately); Jump to Next Segment; Hold Profile or Release Hold.
  • Page 46: Adjusting The Setpoint Ramp Rate

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual  Press to select the Setpoint Value Display and Adjustment screen   Press to adjust each Local Setpoint to the required value. A Remote Setpoint value cannot be altered from the key pad.
  • Page 47: Main Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Main Menu This menu is used to access the various features and configuration menus available in the instrument. The available menus are dependent upon the features and options fitted and the way in which it has been configured Entry into the Main Menu ...
  • Page 48: Setup Wizard

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Setup Wizard An easy Setup Wizard runs automatically at first ever power-up or if whenever a Reset To Defaults is carried out. Users can follow the Wizard screens to setup parameters required for typical applications (screens marked w in the following Screen Sequence lists are also included in the Setup Wizard).
  • Page 49: Supervisor Mode

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Supervisor Mode This mode is only available if it has been configured from the PC software. The software is used to copy up to 50 screens from the Configuration Menus to include in Supervisor Mode.
  • Page 50: Configuration Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Configuration Menu This menu can be used as an alternative to the more limited Setup Wizard when the instrument is configured for the first time, or when further changes are required to the instruments characteristics.
  • Page 51: Input Configuration Sub-Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Input Configuration Sub-Menu Table 9. Input Configuration Sub-Menu Screens Input Configuration: Process Variable Input w From various Thermocouple, RTD and Linear inputs. - see Type specifications section for full details of input types available.
  • Page 52: Control Configuration Sub-Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Control Configuration Sub-Menu Table 10. Control Configuration Sub-Menu Screens Control Configuration: Control Enable/Disable Sets the method used to enable/disable the control output(s). From: Enabled (always); Disabled (always); Enable/Disable via Digital Input A or B, or Operator Selectable (allows control output(s) to be turned Caution: off from Operation Mode).
  • Page 53 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Secondary On-Off Sets the Secondary On-Off control hysteresis (deadband) from 0.1 to Differential 10.0% of Span (centred about setpoint), when Primary PID with Secondary On-Off control is used. Primary & Secondary Sets the combined Primary & Secondary On-Off Control hysteresis On-Off Differential (deadband) from 0.1 to 10.0% of Span.
  • Page 54: Output Configuration Sub-Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Setpoint Ramp Rate The Setpoint Ramp Rate value (1 to 9999 display units per hour or OFF). This ramp is applied at power-up and any setpoint changes. Local Setpoint 1 Value w Sets the value of Local Setpoint 1 between the Setpoint Upper and Lower Limits.
  • Page 55: Alarm Configuration Sub-Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Alarm Configuration Sub-Menu Table 12. Alarm Configuration Sub-Menu Screens Alarm Configuration: Alarm n Type w Sets the type for each of the 5 alarms From: Unused; Process High; Process Low; PV-SP Deviation; Band; Control Loop; Rate Of Signal Change;...
  • Page 56: Recorder Configuration Sub-Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Recorder Configuration Sub-Menu Table 14. Data Recorder Configuration Sub-Menu Screens Recorder Configuration: No Recorder Warning If the Recorder Configuration menu is entered on an instrument without this option fitted. Recording In Progress If recording in progress when Recorder Configuration entered.
  • Page 57: Clock Configuration Sub-Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Clock Configuration Sub-Menu Table 15. Internal Clock Configuration Sub-Menu Screens Clock Configuration: Date Format w Sets the format used for all displayed dates: dd/mm/yyyy (Day / Month / Year) or mm/dd/yyyy (Month / Day / Year). – Recorder versions only.
  • Page 58: Lock Code View

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Lock Code View Unlock Codes To prevent unauthorised entry, some menus are protected by a lock code. These screens are indicated by the symbol before their names in the screen list tables. To enter these screens, the correct code must first be entered.
  • Page 59: Resetting To Defaults

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Resetting To Defaults Table 18. Reset To Defaults Sub-Menu Screen Reset To Defaults: Reset To Defaults Sets all parameters to their factory default values. If the instrument is to be used in a new or changed application, it is possible to reset all of the instruments parameters back to their factory default settings.
  • Page 60: Profiler Setup Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Table 19. Automatic Tuning Menus Screens Automatic Tuning Menu: Automatic Tuning Mode Enter correct code number to access the Automatic Tuning Menu. Unlocking Pre-Tune w Turns Pre-Tune on/off. Pre-Tune is disabled in On-Off Control Mode;...
  • Page 61 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Profile Header: Settings that apply to the chosen profile as a whole Enter Profile Name Up to 16 characters can be used to name each profile Profile Starting The setpoint value to be used at the beginning of the first segment.
  • Page 62 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Segment Loop Enter the segment to loop back to, and the number of times to loop back, before continuing forward to the next segment, if the segment type is Loop. Note: Two Loops cannot be set to cross each other.
  • Page 63: Profiler Control Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Profiler Control Menu Table 21. Profiler Control Menu Screens Profiler Menu: Profile Control If a profile is running, choose from: Do Nothing, Abort Profile (end immediately); or Jump to Next Profile Segment, Hold Profile or Release Hold.
  • Page 64: Usb Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual USB Menu A Notification is shown if a USB Memory Stick is inserted or removed from the USB Port. The USB Menu will automatically be offered after insertion. The USB menu can also be accessed from the Main Menu.
  • Page 65: Recorder Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Recorder Menu This menu controls the starting and stopping of the Data Recorder and the deletion of previous recordings. Refer to the Recorder Configuration sub-menu in Configuration Mode for information about how to setup the data to be recorded and the recording interval.
  • Page 66: Service Information Mode

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Table 24. Product Information Screens Product Information Mode: Input Calibration Status Calibration status of the mVDC, VDC, mADC, RTD and Caution: Thermocouple CJC inputs. Re-calibrate the unit if any inputs are not shown as “Calibrated”.
  • Page 67: The Usb Interface

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 8 The USB Interface The features covered in this section of the manual are available on models fitted with the optional USB Interface or the Data Recorder (which includes the USB Interface).
  • Page 68: The Data Recorder Option

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 9 The Data Recorder Option The features covered in this section are available on models fitted with the Data Recorder option. This option includes a USB Interface (refer to section 8) and a Real Time Clock (RTC) with battery backup..
  • Page 69: 10 The Profiler Option

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 10 The Profiler Option The features covered in this section are only available on models fitted with the Profiler (Setpoint Programmer) option. If the instrument also has the Data Recorder option fitted, it’s Real Time Clock is used to expand the profiling capabilities by adding Day &...
  • Page 70: Profile Starting & Standard Segments

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Profile Starting & Standard Segments The example profiles below contain examples of the standard segment types required to make simple profiles or profile sequences. A Start Trigger is the instruction to begin the selected profile.
  • Page 71: Loops Segments

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Loops Segments A Loop Segment goes back to a specified segment in the current profile. This action is repeated for the required number of times (1 to 9999) before the profile continues onwards.
  • Page 72: The Auto-Hold Feature

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual The Auto-Hold Feature Each profile segment has individual Auto-Hold settings. If utilised, these ensure that the profile and the actual process remain synchronised. If the process does not closely match the required setpoint by remaining within the defined Hold Band, the profile can be held until it returns within bounds.
  • Page 73: Profile Cycles & Repeat Sequences

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Profile Cycles & Repeat Sequences A profile can be configured to run itself 1 to 9999 times or continuously using the Profile Cycles setting. A profile ending with Repeat Then End will run the entire sequence of profiles again from 1 to 9999 times before ending.
  • Page 74: Profile End Actions

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Power On Power Off (Start-on SP) Power Off Time Planned Profile = Control Off Controller SP Possible Recovery Methods: A Abort the profile and maintain the profile value from the time the power failed.
  • Page 75: Profile Abort Actions

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Profile Abort Actions If a running profile is forced to end early, the Profile Abort Action defines action taken by the instrument. This is set in the General Profile Configuration section of the Profile Setup Menu, and is common to all profiles.
  • Page 76: 11 Manually Tuning Controllers

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 11 Manually Tuning Controllers Single Control Tuning (PID with Primary Output only) This technique balances the need to reach setpoint quickly, with the wish to limit setpoint overshoot at start-up or during process changes. It determines values for the Primary Proportional Band and the Integral and Derivative time constants that allow the PID control algorithm to give acceptable results in most applications that use a single control device.
  • Page 77: Dual Control Tuning (Pid With Primary And Secondary Outputs)

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Dual Control Tuning (PID with Primary and Secondary Outputs) This tuning technique balances the need to reach setpoint quickly, with the wish to limit setpoint overshoot at start-up and during process changes. It determines values for the...
  • Page 78 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 5. Follow the instructions in the diagram below. At each stage, allow sufficient settling time before moving on to the next stage. P.Pb is the Primary Proportional Band, Int.T is the Integral Time Constant.
  • Page 79: Fine Tuning

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Fine Tuning. A separate cycle time adjustment parameter is provided for the Primary and Secondary control when using time proportioning control outputs. Note: Adjusting the cycle time affects the controllers operation; a shorter cycle time gives control that is more accurate, but mechanical components such as relays will have a reduced life span.
  • Page 80: 12 Serial Communications

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 12 Serial Communications Supported Protocols Communication with a Modbus RTU or Modbus TCP master device is possible if the appropriate communications module is fitted into Option Slot A. An RS485 Module is required for Modbus RTU.
  • Page 81 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Link Layer A Query (or command) is transmitted from the Modbus Master to the Modbus Slave. The slave instrument assembles the reply to the master. All of the instruments covered by this manual are slave devices, and cannot act as a Modbus Master.
  • Page 82: Supported Modbus Functions

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Supported Modbus Functions Modbus defines several function types. The following types are supported by this instrument: Function Code Modbus Meaning Description (decimal) 03 / 04 Read Holding/Input registers Read current binary value of specified number of parameters at given address.
  • Page 83 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Function 06 - Write Single Register Writes two bytes to a specified word address. QUERY Function Address of Word Value to write RESPONSE Function Address of Word Value written Note: The Response normally returns the same data as the Query.
  • Page 84: Exception Responses

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Function 23 Hex - Read / Write Multiple Registers (0x17 hex) Reads and writes the requested number of consecutive words (two-bytes) starting at the specified addresses. QUERY Function Read Number of Write...
  • Page 85: 13 Modbus Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 13 Modbus Parameters The Modbus parameter register addresses are detailed in the tables below. The Access column indicates if a parameter is read only (RO) or if it can also be written to (R/W).
  • Page 86: Universal Process Input Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Universal Process Input Parameters Parameter Name Modbus Address Access Values (Dec) (Hex) Value Process Input Type Universal Process 1024 0x0400 Input Type B Type Thermocouple C Type Thermocouple D Type Thermocouple E Type Thermocouple...
  • Page 87 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Process Input Under Range Status Input Signal Under 1033 0x0409 Range Flag Inactive Active Input Signal Over 1034 0x040A Value Process Input Over Range Status...
  • Page 88: Option Slot A Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Scale Point 13 1078 0x0436 >Scale point 12 to 100.0% Display Point 13 1079 0x0437 Valid between scale range maximum and minimum Scale Point 14...
  • Page 89: Option Slot B Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Data Format Master Transmit 2123 0x084B Format Integer Integer with 1 decimal place Floating point number Value Communications Status Comms Write 2124 0x084C...
  • Page 90: Option Slot 1 Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Digital Input B Status Digital Input B Status 2085 0x0825 Inactive Active Calibration Status 2086 0x0826 Value Calibration Status Calibration OK Calibration Required...
  • Page 91 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Alarm 1. Reverse Acting Alarm 2, Direct Acting Alarm 2. Reverse Acting Alarm 3. Direct Acting Alarm 3. Reverse Acting Alarm 4. Direct Acting Alarm 4.
  • Page 92: Option Slot 2 Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Option Slot 2 Parameters Parameter Name Modbus Address Access Values (Dec) (Hex) Option Slot 2 2160 0x0870 Value Module Fitted In Slot 2 Module Type None Fitted Single Relay Single SSR Driver...
  • Page 93 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Digital Output 2B Function Digital Output 2B 2177 0x0881 Function Disabled Primary Output Power Secondary Output Power Alarm Alarm and Event Value Output 2 or 2A Alarm Selection...
  • Page 94 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Output 2 or 2A Event/Alarm Selection Output 2 or 2A 2180 0x0884 Event And Alarm Event 1. Direct Acting Selection Event 1. Reverse Acting Event 2.
  • Page 95: Option Slot 3 Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Event 4 AND Alarm 4. Direct Acting Event 4 AND Alarm 4. Reverse Acting Event 5 AND Alarm 5. Direct Acting Event 5 AND Alarm 5. Reverse Acting...
  • Page 96 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Digital Output 3 or 3A Function Digital Output 3 or 2205 0x089D 3A Function Disabled Primary Output Power Secondary Output Power Alarm Alarm and Event...
  • Page 97 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) OR of Alarm 1, 2, or 3. Reverse OR of Alarm 1, 2, 3, or 4. Direct OR of Alarm 1, 2, 3, or 4. Reverse OR of Alarm 1, 2, 3, 4 or 5.
  • Page 98: Option Slot 4 Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Event 1 AND Alarm 1. Direct Acting Event 1 AND Alarm 1. Reverse Acting Event 2 AND Alarm 2. Direct Acting Event 2 AND Alarm 2. Reverse Acting Event 3 AND Alarm 3.
  • Page 99 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Digital Output 4C Function Digital Output 4C 2232 0x08B8 Function Disabled Primary Output Power Secondary Output Power Alarm Alarm and Event Value Digital Output 4D Function...
  • Page 100 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) OR of Alarm 1, 2, or 3. Reverse OR of Alarm 1, 2, 3, or 4. Direct OR of Alarm 1, 2, 3, or 4. Reverse OR of Alarm 1, 2, 3, 4 or 5.
  • Page 101 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Output 4A Event/Alarm Selection Output 4A Event 2238 0x08BE And Alarm Selection Event 1. Direct Acting Event 1. Reverse Acting Event 2. Direct Acting Event 2.
  • Page 102 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Event 3 AND Alarm 3. Reverse Acting Event 4 AND Alarm 4. Direct Acting Event 4 AND Alarm 4. Reverse Acting Event 5 AND Alarm 5. Direct Acting Event 5 AND Alarm 5.
  • Page 103: Setpoint Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Event 1 AND Alarm 1. Direct Acting Event 1 AND Alarm 1. Reverse Acting Event 2 AND Alarm 2. Direct Acting Event 2 AND Alarm 2. Reverse Acting Event 3 AND Alarm 3.
  • Page 104: Control Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Auxiliary Input B 4080 0x0FF0 Setpoint is always limited within Setpoint Maximum Offset and Minimum Auxiliary Input B 4081 0x0FF1 The value of analogue Auxiliary Input B...
  • Page 105 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Proportional Band Integral Time 4314 0x10DA 0.0 to 5999 Seconds Constant Derivative Time 4315 0x10DB 0.0 to 5999 Seconds Constant Bias 4316 0x10DC For single control 0 to 100.
  • Page 106: Alarm Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Alarm parameters Parameter Name Modbus Address Access Values (Dec) (Hex) Value Alarm 1 Type Alarm 1 Type 6144 0x1800 Not Used Process High Alarm Process Low Alarm Deviation Alarm (SP-PV) Band Alarm...
  • Page 107 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Alarm 2 Inhibit Status Alarm 2 Inhibit 6165 0x1815 Status Not Inhibited Inhibited Alarm 3 Type 6176 0x1820 Value Alarm 1 Type Not Used...
  • Page 108: Recorder & Clock Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Alarm 4 Inhibit Status Alarm 4 Inhibit 6197 0x1835 Status Not Inhibited Inhibited Value Alarm 1 Type Alarm 5 Type 6208 0x1840 Not Used...
  • Page 109 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Recording Mode Recording Mode 7551 0x1D7F Record until memory used Continuous FIFO buffer Start Stop 7552 0x1D80 Value Operator Start/Stop Recording Recording Stop Recording...
  • Page 110 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Record Change Of State For Alarm 3 Record Alarm 3 7580 0x1D9C Status Do Not Record Alarm 3 Record Alarm 3 Value Record Change Of State For Alarm 4...
  • Page 111: Display Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Memory Used 7605 0x1DB5 Recorder Memory Used. 0 (Empty) to 100% (Full) Value Display Date Format Date format 7868 0x1EBC dd/mm/yyyy (European Default) mm/dd/yyyy (USA Default)
  • Page 112 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Event 3 Event 4 Event 5 Any Event Manual Control Profile Running Profile Ended Value LED 2 Usage LED 2 Usage 7665 0x1DF1 Primary Control Secondary Control Tuning Any Alarm Alarm 1...
  • Page 113 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual LED 4 Usage 7667 0x1DF3 Value LED 4 Usage Primary Control Secondary Control Tuning Any Alarm Alarm 1 Alarm 2 Alarm 3 Alarm 4 Alarm 5 Event 1 Event 2 Event 3...
  • Page 114: Profiler Control & Status Parameters

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Trend View Sample 9000 0x2328 Value Trend Sample Interval Every Second Interval Every 2 Seconds Every 5 Seconds Every 10 Seconds Every 15 Seconds Every 30 Seconds Every Minute Every 2 Minutes...
  • Page 115 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Value Editing Current Running Profile Enable Edit While 8262 0x2046 Running Editing current running profile forbidden Editing current running profile allowed Profile Control In...
  • Page 116: Profile Setup Via Modbus

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Parameter Name Modbus Address Access Values (Dec) (Hex) Current Profile 8235 0x202B The elapsed time of the current running profile Running Time Current Profile 8236 0x202C The remaining time for the current running profile...
  • Page 117 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 5. The very last segment of the profile must be one of the end type segments. Thereafter, no more segments can be added to the specified profile. To add a segment to an existing profile the insert segment command must be used.
  • Page 118 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Instruction Sequence to read a profile 1. Use the command RP to read the profile header data 2. Use the command RS to read the 1 segment’s data 3. Use the command RS to read the 2 segment’s data.
  • Page 119 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Creating Or Editing A Profile Header - Request (to instrument) Field Name Data Comments (Dec) (Hex) Profile Name Character 8 Profile Name Character 9 The space character (32dec / 0x20hex) is used to fill any unused characters at the Profile Name Character 10 end of the name.
  • Page 120 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual position 3 of profile 1 the segment number will be 3, and to edit or insert a segment at position 3 of profile 6 the segment number will also be 3. Creating, Editing or Inserting Segments - Request (to instrument)
  • Page 121 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Creating, Editing or Inserting Segments - Request (to instrument) Field Name Data Comments (Dec) (Hex) Events High Byte The status of the five events are defined by the lowest 5 bits of the low byte. A bit value Events Low Byte of 1 signifies the event is on.
  • Page 122 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Delete Profiles - Request (to instrument) Field Name Data Comments (Dec) (Hex) Unit Address The ID address of the instrument. Function Code Requires the multi read/write function Read Start Address High Byte...
  • Page 123 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Delete A Segment - Request (to instrument) Field Name Data Comments (Dec) (Hex) Profile Number Low Byte Segment Number High Byte Segment Number Low Byte CRC High Byte CRC Low Byte The instrument replies to this message with an Edit Response Message.
  • Page 124 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Edit Response Message - Response (from instrument) Field Name Data Comments (Dec) (Hex) Unit Address The ID address of the instrument Function Code The multi read/write function Byte Count Command Response High Byte...
  • Page 125 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Read A Profile Header Read A Profile Header - Request (to instrument) Field Name Data Comments (Dec) (Hex) Unit Address The ID address of the instrument Function Code Requires the multi read/write function...
  • Page 126 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Read Profile Header - Response (from instrument) Field Name Data Comments (Dec) (Hex) Profile Start Time (Byte 4 - High) Profile Start Time (Byte 3) Floating point number Profile Start Time (Byte 2)
  • Page 127 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Read A Segment - Request (to instrument) Field Name Data Comments (Dec) (Hex) Profile Number High Byte Profile Number Low Byte Segment Number High Byte Segment Number Low Byte CRC High Byte...
  • Page 128 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Segment Data The Segment Data is included in the response to a Read Segment request. It is provided in two parts (Segment Info A and B). The meaning of the data contained in Segment Info A and B depends on the type of segment it relates to.
  • Page 129 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Read Profile Name - Request (to instrument) Field Name Data Comments (Dec) (Hex) Write Quantity Of Registers High Byte Write Quantity Of Registers Low Byte Byte Count Command Code High Byte Command Code Low Byte...
  • Page 130 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Read Profile Memory Status This command returns the status of the profile memory used. The response to this command is to return a table of all the profile numbers that are in use. A value of 0x00 indicates that the profile position is free and value of 0x01 indicates that the position is used by a profile.
  • Page 131: Instrument Data

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Instrument Data Parameter Name Modbus Address Access Values (Dec) (Hex) Serial Number 1 0x00D2 The first 4 digits of the instrument’s Serial number. Serial Number 2 0x00D3 The digits 5 to 8 of the instrument’s Serial number.
  • Page 132: 14 Calibration

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 14 Calibration WARNING: CALIBRATION IS ONLY REQUIRED FOR INSTRUMENTS IN WHICH CALIBRATION ERRORS HAVE BEEN ENCOUNTERED. REFER TO CALIBRATION CHECK BELOW. CAUTION: Calibration must be performed by personnel who are technically competent and authorised to do so.
  • Page 133: Recalibration Procedure

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Recalibration Procedure Recalibration is carried out in five phases as shown in the table below; each phase corresponds to a basic input type. CAUTION: The 50mV phase MUST be calibrated before the thermocouple range.
  • Page 134: 15 Appendix 1 - Glossary Of Terms Used

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 15 Appendix 1 – Glossary of Terms Used Active Setpoint The term Active Setpoint is used to describe the currently selected setpoint when the instrument is in Controller Mode. Controllers can use Local Setpoint 1 and/or the Alternative Setpoint.
  • Page 135 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Inactive Inactive Active Figure 50. Alarm Hysteresis Operation PROCESS HIGH Alarm Value ALARM Alarm Hysteresis Value Process Variable Process Variable Alarm Hysteresis Value PROCESS LOW Alarm Value ALARM Inactive Inactive Active Alarm Value...
  • Page 136: Alarm Operation

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Alarm Operation The Process and Deviation Alarm types are illustrated, together with the action of any associated outputs. Also refer to: Alarm Hysteresis, Alarm Inhibit, Alarm Types, Band Alarm Value, Deviation Alarm, Latching Relay, Logical Alarm Combinations, Loop Alarm, Process High Alarm and Process Low Alarm.
  • Page 137: Alarm Inhibit

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Alarm Inhibit Alarm Inhibit prevents unwanted process or deviation alarm activation at power-up or when the controller setpoint is changed. The alarm activation is inhibited until a ‘Safe’ condition is present. The alarm operates normally from that point onwards. E.g. if inhibited, a low alarm will not activate at power-up, until the process has first risen above the alarm point and then falls back below.
  • Page 138: Auxiliary Input

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Auxiliary Input Up to two secondary linear input modules can be installed in Option Slot A and B. These can be used as Remote Setpoint inputs. Signals can be mA, mV, VDC or Potentiometer. Auxiliary Input B also has a Digital Input onboard.
  • Page 139: Bar Graphs

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Bar Graphs The instrument displays a bar-graph in the base operation mode screen. These can show PID Power Output (single control = uni-directional, dual control = bi-directional), Control Deviation (bi-directional) or for Data Recorder version %Memory Used (uni-directional). Bar- graphs are uni-directional or bi-directional depending on the information to be displayed.
  • Page 140: Clock Configuration

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual As the jacket temperature rises, the slave’s heater output falls. The product temperature also rises at a rate dependant on the transfer lag between the jacket and product. This causes the master’s PID output to decrease, reducing the ‘jacket’ setpoint on the slave, effectively reducing the output to the heater.
  • Page 141: Control Deviation

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Control Deviation Control Deviation is the difference between the Process Variable value and the Actual Setpoint. The Control deviation error is equal to PV – SP. This value can be monitored using the bar-graph, and an excessive deviation warning can be given by using a deviation alarm.
  • Page 142: Cpu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual This stands for Central Processing Unit and refers to the onboard microprocessor that controls the measurement, control, alarm and display functions of the instrument. Current Proportioning Control Current proportioning control is used to produce the correcting variable on units with linear output(s).
  • Page 143: Deviation Alarm Value

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Deviation Alarm Value Defines the amount of control deviation considered acceptable before a deviation alarm is activated. A positive value (deviation high) sets the alarm point above the current actual setpoint, a negative value (deviation low) sets the alarm point below actual setpoint. If the process variable deviates from the actual setpoint by a margin greater than this value, the deviation alarm becomes active.
  • Page 144: Display Resolution

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Display Resolution The maximum number of digits that can be displayed and/or the maximum number of decimal places. Numeric values (e.g. process variable, setpoints etc) are limited to no more than 5 digits.
  • Page 145: Input Range

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Input Range This is the overall process variable input range and type as selected by the Process Input Type parameter. This range can be scaled by the Scale Range Upper & Lower Limits.
  • Page 146: Linear Output

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Linear Output A mVDC, mADC or voltage signal used to provide a proportional control or retransmit output. Also refer to: Linear Input mVDC, mADC, Proportional Control, Retransmit Output and VDC Limit Controller A safety protection device that will shut down a process at a preset “exceed condition”.
  • Page 147: Loop Alarm

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Table 28. Examples Of Logical Alarm Outputs Logical OR: Alarm 1 OR Alarm 2 Direct Acting Reverse-Acting Logical AND: Alarm 1 AND Alarm 2 Direct Acting Reverse-Acting Loop Alarm A loop alarm detects faults in the control feedback loop, by continuously monitoring process variable response to the control output(s).
  • Page 148: Main Menu

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Main Menu The top-level menu that allows access to operation mode as well as all other menus. These are: configuration mode, profiler setup and recorder menus, the setup wizard, supervisor mode and the tuning and USB menus. Most menus require an unlock code to gain access.
  • Page 149: Minimum Duration Of Change

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Cascade Control is another type of Master & Slave application where the slaves setpoint is set using the master controllers PID power output. The terms Master and Slave are also used in a different context in relation to serial communications.
  • Page 150: Modulating Valve

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Modulating Valve A valve that can be positioned anywhere between fully closed and fully open by means of an incorporated motor. A typical application would be controlling temperature in a furnace heated by gas burners. This instrument can control modulating valves that have a positioning circuit.
  • Page 151: Operation Mode

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Operation Mode The mode used during normal operation of the instrument. It can be accessed from the Main Menu, and is the usual mode entered at power-up. The screens shown include a main screen with bar-graph, a trend view, information about the process, alarms plus optionally, selection of auto/manual control, control output disabling.
  • Page 152 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual OVERLAP Proportional Band 1 WITH PID Proportional Band 2 Output 2 Output 1 Output 2 Output 1 Process Variable Overlap (positive value) DEADBAND Proportional Proportional WITH PID Band 2 Band 1 Output 1...
  • Page 153: Pd Control

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual PD Control Proportional and Derivative (PD) control combines proportional control with derivative action. It is similar to PID control, but without Integral action. Also refer to: Derivative, Integral, PID Control, Proportional Control and Tuning.
  • Page 154: Power Output Limits

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Setpoint Process Variable SP – Initial PV Initial PV Pre-Tune +100% Power (HEAT output) engaged here Control Power -100% Power (Cool output) Figure 53. Pre-Tune Operation When Pre-Tune is completed, the PID control output power is applied using the calculated values.
  • Page 155: Primary Proportional Band

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Primary Proportional Band The portion of the input span over which the Primary Output power level is proportional to the process variable value. Applicable if Control Type is single or dual. For dual control a Secondary Proportional band is used for the second output.
  • Page 156: Process Variable Offset

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Process Variable Offset The Process variable offset is used to modify the measured process variable value. Use this parameter to compensate for errors in the displayed process variable. Positive values are added to the process variable reading, negative values are subtracted.
  • Page 157: Profiler

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Profiler A profiler controls the value of the actual setpoint over time; increasing, decreasing or holding its value as required. This is used in applications where the rate of rise or fall of the process variable must be closely controlled, or where a value must be maintained for a period before moving to the next value.
  • Page 158: Recorder Option

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Recorder Option - Refer to Data Recorder. Recorder Menu If the Data Recorder is fitted, a Recorder Menu is added to the Main Menu. This is used to control the recording (start, stop, delete recordings etc) and to show the recorder status. This menu is protected by a lock code.
  • Page 159: Retransmit Output N Scale Minimum

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Retransmit Output n Scale Minimum Scales a linear output module in slot n if it has been selected to retransmit the PV or SP. Retransmit Scale Minimum defines the value of the process variable, or setpoint, at which the output will be at its minimum value.
  • Page 160: Rtd

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Resistance Temperature Detector. A temperature sensor that changes resistance with a change in the measured temperature. This instruments process input supports PT100 (platinum, 100 at 0° C) and NI120 (nickel, 120 at 0° C) sensors. These have positive temperature coefficients (PTC) which means their resistance increases with higher temperatures.
  • Page 161: Self-Tune

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Self-Tune Self-Tune continuously optimises tuning while a controller is operating. It uses a pattern recognition algorithm, which monitors the control deviation. The diagram shows a typical application involving a process start up, setpoint change and load disturbance.
  • Page 162: Serial Communications Configuration

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Serial Communications Configuration A sub-menu of Configuration Mode used to adjust the serial communications parameters. (Addressing, data rate, parity, master/slave settings and write enabling). Also refer to: Configuration Mode, Serial Communications Serial Communications Option A feature that allows other devices such as PC’s, PLC’s or a master controller to read, or...
  • Page 163: Setpoint Ramp Rate

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Setpoint Ramp Rate The rate at which the actual setpoint value will move towards its target value, when the setpoint value is adjusted or the active setpoint is changed. With ramping in use, the initial value of the actual setpoint at power up, or when switching back to automatic mode from manual control, will be equal to the current process variable value.
  • Page 164: Solenoid Valve

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Solenoid Valve An electromechanical device, use to control the flow of gases or liquids. It has just two states, open or closed. Usually, a spring holds the valve closed until a current is passed through the solenoid coil forces it open.
  • Page 165: Time Proportioning Control

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Time Proportioning Control Time proportioning control is accomplished by cycling the output on and off during the prescribed cycle time, whenever the process variable is within the proportional band(s). The PID control algorithm determines the ratio of time (on vs. off) to achieve the level of the correcting variable required to remove the control deviation error.
  • Page 166: Triac

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Triac A small internal solid state relay, which can be used in place of a mechanical relay in applications switching low power AC, up to 1 amp. Like a relay, the output is time proportioned, but much faster switching cycle times are also possible, leading to superior control.
  • Page 167: 16 Pc Software

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 16 PC SOFTWARE The primary function of the software is to create, download and store instrument configurations and profiles. Additionally, changes can be made to the operation of the instrument; adding extra screens into Operation Mode, enabling and configuring Supervisor Mode, changing the contact details or the function of the front LED’s.
  • Page 168: Instrument Configuration

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Instrument Configuration When creating a new configuration with the software, the basic instrument type and the options to be fitted to it must be defined in the Device Selection screen. You can select these from the drop down lists or by typing the full model number in the Order number field.
  • Page 169: Profile Creation And Editing

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Functional Groups Mode Drop Down Parameter List Selected Parameters Add Entry Remove Entry Move Up Move Down Figure 57. Supervisor/Enhanced Operation Mode Configuration Profile Creation And Editing Select the Profile Editor from the button bar or view menu. An existing profile file can be opened from the file open menu or button, or uploaded from an instrument connected to the PC via the configuration socket or serial communications module.
  • Page 170 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual If the option to uploaded a profile is chosen, a list of profiles in the connected instrument is shown. The user can select the required profile from the list. A directory of existing profiles in the instrument can also be requested.
  • Page 171: Changing The Start-Up Splash Screen

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Changing the Start-up Splash Screen The graphic shown during the instrument start-up sequence can be changed from the main parameter screen. Select Download Splash Screen option from the Device menu. Choose your new graphic file (most common file types are supported). The chosen image will converted to monochrome and be rescaled to 160 pixels wide by 80 pixels high.
  • Page 172 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual A communications settings screen is shown whenever the user attempts to connect to the instrument from the software. The settings must be correct in order for communications to work successfully. First correctly select Configuration Socket or Bus as the Device connector, and select the PC Serial Com port that you have connected to For Modbus TCP, select Ethernet (bus coupler).
  • Page 173: Network Configuration For Modbus Tcp Options

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Network Configuration For Modbus TCP Options If the instrument has the Modbus TCP communications option fitted, an IP address must be assigned to it in order for it to communicate with the Modbus TCP master device over your Ethernet network.
  • Page 174 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Edit Modbus Settings The Edit Modbus Settings tab configures the connection between the Ethernet module and the instrument’s microprocessor. These settings MUST match with the settings in the instruments Communications Configuration menu. A faster...
  • Page 175: 17 Appendix 2 - Specifications

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 17 Appendix 2 - Specifications Universal Process Input General Input Specifications Input Sample Rate: Ten samples per second. Digital Input Filter 0.0 (OFF), 0.5 to 100.0 seconds in 0.5 second increments. time constant Input Resolution: Always four times better than display resolution.
  • Page 176: Resistance Temperature Detector (Rtd) Input

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Thermocouple Performance Calibration: Complies with BS4937, NBS125 and IEC584. Measurement ±0.1% of full range span ±1LSD. Accuracy: NOTE: Reduced performance for B Thermocouple from 100 to 600° C. NOTE: PtRh 20% vs PtRh 40% Thermocouple accuracy is 0.25% and has reduced performance below 800°...
  • Page 177: Dc Linear Input

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual DC Linear Input DC Linear Types & Ranges Input Ranges Input Ranges Type Type mA DC V DC 0 to 20mA 4 to 20mA 0 to 5V 1 to 5V mV DC...
  • Page 178: Digital Inputs

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Input resistance: mV ranges : >10M . Voltage ranges: 47K . Curent ranges: 5 . Input protection: Voltage input: will withstand up to 5x input voltage overload without damage or degradation of performance in either polarity.
  • Page 179: Output Specifications

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Output Specifications Output Module Types Single Relay, Single SSR Driver, Triac or DC linear. Option Slot 1 Options: Single Relay, Dual Relay, Single SSR Driver, Dual SSR Driver, Triac, Option Slot 2 Options: DC Linear or 24VDC Transmitter Power Supply.
  • Page 180 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Triac Output Performance Operating Voltage: 20 to 280Vrms @47 to 63Hz. Current Rating: 0.01 to 1A (full cycle rms on-state @ 25°C); derates linearly above 40°C to 0.5A @ 80°C. Non-repetitive Surge 25A peak maximum, for <16.6ms.
  • Page 181: Communications

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Communications Supported Communication Methods Function Type Direct configuration using the PC Configuration Software PC Configuration Socket Configuration and general communications using Modbus RTU. RS485 Configuration and general serial communications using the Modbus Ethernet TCP protocol.
  • Page 182: Display

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Display Display Type: 160 x 80 pixel, monochrome graphic LCD with a dual colour (red/green) backlight. Display Area: 66.54mm (W) x 37.42mm (H). Display Characters: 0 to 9, a to z, A to Z, plus ( ) - and _ Trend View: 120 of 240 data points shown in a scrollable window.
  • Page 183: Profiler Option

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Profiler Option Profile Limits: Number of profiles = 64 maximum. Total number of segments (all programs) = 255 maximum. Loop Back Segments: 1 to 9999 loops back to specified segment. Profile Cycling: 1 to 9999 or Infinite repeats per profile.
  • Page 184: Conditions For Use

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual Conditions For Use Reference Test Conditions Ambient Temperature: 20°C ±2°C. 60 to 70%. Relative Humidity: 100 to 240V AC 50Hz ±1%. Supply Voltage: <10 for thermocouple input. Source Resistance: RTD Lead Resistance: <0.1 /lead balanced (Pt100).
  • Page 185: 18 Appendix 3 - Product Coding

    ProVU4 Controller, Profiler & Recorder/Controller - Product Manual 18 Appendix 3 - Product Coding V4-x Model Code Regional Defaults Non-US defaults USA defaults Graphical Controller/Recorder Graphical Controller Graphical Controller with USB Port Controller/Recorder with USB Port Profiler Not fitted Profiler...
  • Page 186 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual V4-x Model Code HMI & Manual Language English French German Italian Spanish Czech Russian Packing And Manual Options Single Packed with Concise Manual Bulk Pack with 1 Concise Manual per unit – (Min 20 pieces.) Bulk Pack without Manual –...
  • Page 187 ProVU4 Controller, Profiler & Recorder/Controller - Product Manual BRITAIN FRANCE GERMANY WEST INSTRUMENTS HENGSTLER SA DANAHER CONTROLS West Instruments Hengstler SA PMA Prozeß- und Danaher Controls The Hyde Business Park, 69 Rue de la Belle Etoile - Maschinen- Automation 1675 Delany Road...

Table of Contents