Pos: 14.6 /Überschriften/1.1/1-spaltig/A - C/Bedienelemente des Servicefelds (ISF) @ 7\mod_1167724580593_3101.doc @ 53637
6.2

Operating elements of the service field (ISF)

Pos: 14.7 /Konfiguration, Parametrierung/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Bedienelemente des Servicefelds (ISF) EX @ 13\mod_1191933980187_3101.doc @ 129109
Fig. 18: Commissioning and service field (ISF)
1 Power LED: Displays supply by line
voltage.
2 Accept button (100%): Press to set the
current position as 100 %; press in
combination with the 4 button to end the
adjustment process.
3 Reset button: Press to restart the
processor and delete any values
assigned positions 0% and 100%.
4 Accept button (0 %): Press to set the
current position as 0%; press in
combination with the 2 button to end the
adjustment process.
5 LED for 0% position: Depending on the
flash rate, this LED indicates either
adjustment, position saved or error.
Pos: 15.1 /Überschriften/1/G - I/Inbetriebnahme und Servicefeld (ISF) @ 5\mod_1167725076390_3101.doc @ 53680
42/68-830-EN
1
2
3
4
5
6
EBN853, EBN861 (Contrac)
6 Write-protection switch (default: ON).
7 RS232 connector: Connection for a PC.
8 Potential switch: Connection of reference
potential either to system or protective
ground (default setting: to system).
9 Travel button: Press to initiate actuator
movement.
10 LED for 100 \% position: Depending on
the flash rate, this LED indicates either
adjustment, position saved or error.
Local operation
10
9
8
7
M00203