Some other notes of interest include:
Implements Application Class 1 (standard drive)
Supports only Standard Telegram 1 (ST1, PZD-2/2) on slot 1 (similar to PROFIBUS PPO type 3)
Supports only Speed Control Mode
9.5.5.1

PROFIdrive standard telegram 1

The standard telegram 1 mapping is described in Table 35.
IO Data
Word
Significance
Offset
0
STW1
1
NSOLL_A
9.5.5.2

PROFIdrive control and status words

The control word, STW1, is the principal means for controlling the drive. It is sent by the controller (PLC)
to the device (inverter). The bitmapping for the control word is described in Table 36. The status word,
ZSW1, returns status information from the inverter to the controller. The bitmapping for the status word
is described in Table 37.
Bit
Value
1
0
0
1
1
0
1
2
0
1
3
0
1
4
0
1
5
0
1
6
0
1
7
0
8 - 9
Not used
1
10
0
1
11
0
12 - 15
Not used
Bit
Value
1
0
0
1
1
0
2
1
Table 35: Standard Telegram 1
Setpoint (PLC to Inverter)
Description
Control word 1
Reference speed setpoint
Table 36: STW1 Control Word Mapping
Significance
ON
OFF
ON2
OFF2
ON3
OFF3
Enable Operation
Disable Operation
Enable Ramp Generator
Disable Ramp Generator
Unfreeze Ramp
Generator
Freeze Ramp Generator
Enable Setpoint
Disable Setpoint
Fault Acknowledge
No significance
---
Control By PLC
No Control By PLC
Reverse Direction
Forward Direction
---
Table 37: ZSW1 Status Word Mapping
Significance
Ready To Switch ON
Not Ready To Switch ON
Ready to Operate
Not Ready To Operate
Operation Enabled
Actual Value (Inverter to PLC)
Significance
ZSW1
NIST_A
Description
Run command ON
Run command OFF
No coast stop
Coast to a stop
No quick stop
Quick stop
Enable inverter operation
Disable inverter operation
Enable the ramp frequency generator (RFG)
Hold the output frequency to 0 Hz
Unfreeze the RFG
Freeze the RFG with the current output frequency
Enable command
Disable command
Reset the alarm on a positive edge (0→1 transition)
Do not reset the alarm
---
Enable remote control. The IO process data is valid.
Disable remote control. The IO process data is not
valid.
Run in the reverse direction
Run in the forward direction
---
Description
Ready to run command ON
Not ready to run command ON
Ready to run
Not ready to run
Running
90
Description
Status word 1
Speed actual