Whirlpool 4KWFC120MAW0 Installation Instructions Manual page 9

30", 76 cm freestanding electric ranges
Table of Contents

Advertisement

Style 2: Direct wire strain relief
Remove the knockout as needed for the flexible conduit
connection.
Assemble a UL listed conduit connector in the opening.
A. Removable retaining nut
B. Conduit
Tighten strain relief screw against the flexible conduit.
5. Complete installation following instructions for your type of
electrical connection:
3-wire
Electrical Connection Options
If your home has:
And you will be
connecting to:
3-wire receptacle
An IEC 60309
(NEMA type 10-50R)
listed, 250-volt
minimum, 40-
amp minimum,
range power
supply cord
3-wire direct
A circuit breaker
box or fused
³⁄₈"
disconnect
(1.0 cm)
3"
(7.6 cm)
3-wire connection: Power Supply Cord
Use this method only if local codes permit connecting chassis
ground conductor to neutral wire of power supply cord.
1. Use a Phillips screwdriver to remove the ground-link screw
from the back of the range. Save the ground-link screw.
A
B
Go to Section:
3-wire connection:
Power supply cord
3-wire connection:
Direct wire
2. Feed the power supply cord through the strain relief on the
cord/conduit plate on bottom of range. Allow enough slack to
easily attach the wiring to the terminal block.
A
C
A. Terminal block
B. Location of ground-link screw
C. UL listed strain relief
D. Power supply cord wires - large opening
3. Use a Phillips screwdriver to connect the ground (green) wire
from the power supply cord to the range with the ground-link
screw and ground-link section. The ground wire must be
attached first.
4. Use ³⁄₈" nut driver to connect the neutral (red) wire to the left
terminal block post with one of the 10-32 hex nuts.
A
B
C
A. 10-32 hex nut
B. Neutral (red) wire
C. Ground-link screw
5. Connect the line 1 (black) wire to the right terminal block post
with one of the 10-32 hex nuts.
6. Securely tighten hex nuts.
NOTE: For power supply cord replacement, use only a power
cord rated at 250 volts minimum, 40 amps or 50 amps that is
marked for use with nominal 1³⁄₈" (3.5 cm) diameter
connection opening, with ring terminals and marked for use
with ranges.
7. Tighten strain relief screws.
8. Replace terminal block access cover.
B
D
E
D
D. Ground (green) wire
E. Line 1 (black) wire
9