ACH550-PCR/PDR Packaged Drive with Disconnect
Fuses, 500...600 Volt, Fuses
HP
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
1. "PxR" represents both PCR and PDR.
2. UL Type 3R/NEMA 3R enclosed units are provided with fuses as shown in the ACH550-UH User's
Manual. Fuse ratings shown relate to the latest production. Where installed product includes fuses of a
lower rating, either rating may be used.
500...600 Volt
1
Type Code
ACH550-PDR-02A7-6
ACH550-PDR-03A9-6
ACH550-PDR-06A1-6
ACH550-PDR-09A0-6
ACH550-PDR-011A-6
ACH550-PDR-017A-6
ACH550-PDR-022A-6
ACH550-PDR-027A-6
ACH550-PDR-032A-6
ACH550-PDR-041A-6
ACH550-PDR-052A-6
ACH550-PDR-062A-6
ACH550-PxR-077A-6
ACH550-PxR-099A-6
ACH550-PxR-125A-6
ACH550-PxR-144A-6
Drive Input Fuse Ratings
Frame
Amps
Size
(600V)
R2
15
R2
15
R2
15
R2
15
R2
30
R2
30
R3
50
R3
50
R4
100
R4
100
R4
100
R4
100
R6
200
R6
200
R6
200
R6
200
17
Bussmann
Type
KTK-R-15
KTK-R-15
KTK-R-15
KTK-R-15
KTK-R-30
KTK-R-30
JJS-50
JJS-50
JJS-100
JJS-100
JJS-100
JJS-100
2
170M1370
or 170M2617
2
170M1370
or 170M2617
2
170M1370
or 170M2617
2
170M1370
or 170M2617
Technical Data