Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the Ameri-
can Society for Testing and Materials (ANSI/ASTM) stan-
dards.The solvent shall be free flowing and contain no
lumps, undissolved particles or any foreign matter that ad
versely affects the joint strength or chemical resistance of
the cement.
TABLE 2
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe)
Schedule 40 PVC (Cellular Core Pipe)
Schedule 40 PVC (Fittings)
Schedule 40 CPVC (Pipe)
Schedule 40 CPVC (Fittings)
SDR-21 PVC or SDR-26 PVC (Pipe)
SDR-21 CPVC or SDR-26 CPVC (Pipe)
Schedule 40 ABS Cellular Core DWV
(Pipe)
Schedule 40 ABS (Pipe)
Schedule 40 ABS (Fittings)
ABS-DWV (Drain Waste & Vent) (Pipe &
Fittings)
PVC-DWV (Drain Waste & Vent) Pipe &
Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer
PVC Solvent Cement
CPVC Solvent Cement
ABS Solvent Cement
PVC/CPVC/ABS All Purpose Cement
For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent
Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition
Cement
POLYPROPYLENE VENTING SYSTEM
PolyPro® by Duravent
InnoFlue® by Centrotherm
Solvent cements for plastic pipe are flammable liquids
and should be kept away from all sources of ignition.
Do not use excessive amounts of solvent cement when
making joints. Good ventilation should be maintained to
reduce fire hazard and to minimize breathing of solvent
vapors. Avoid contact of cement with skin and eyes.
The cement shall show no gelation, stratification, or sep-
aration that cannot be removed by stirring. Refer to the
table 2 below for approved piping and fitting materials.
D1785
F891
D2466
EL195UHE exhaust and intake connections are made
F441
of PVC. Use PVC primer and solvent cement when
F438
using PVC vent pipe. When using ABS vent pipe, use
transitional solvent cement to make connections to the
D2241
PVC fittings in the unit.
F442
Use PVC primer and solvent cement or ABS solvent ce-
F628
ment meeting ASTM specifications, refer to Table 2. As an
alternate, use all purpose cement, to bond ABS, PVC, or
D1527
CPVC pipe when using fittings and pipe made of the same
D2468
materials. Use transition solvent cement when bonding
ABS to either PVC or CPVC.
D2661
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used for
D2665
vent pipe hangers. Uniformly apply a liberal coat of PVC
ASTM
primer for PVC or use a clean dry cloth for ABS to clean
SPECIFICATION
inside socket surface of fitting and male end of pipe to
depth of fitting socket.
F656
Canadian Applications Only - Pipe, fittings, primer and
D2564
solvent cement used to vent (exhaust) this appliance must
F493
be certified to ULC S636 and supplied by a single manu-
D2235
facturer as part of an approved vent (exhaust system. In
addition, the first three feet of vent pipe from the furnace
D2564, D2235,
flue collar must be accessible for inspection.
F493
D3188
MARKING
ULCS636
Page 14