Diagnostics

All messages are sent to the armature converter and displayed in Signals 04.26, 04.27, 04.36 and
04.37. If the communication is broken or node numbers are mixed up the simple fault display on the
SDCS-FEX-81 / 82 can be used.
Therefore the unit is equipped with two small LEDs.
V730 = Green
V731 = Yellow
Following messages are displayed:
Both OFF
Green and yellow continuous
Green blinking
Green continuous
Green and yellow toggling:
X times yellow
Y times green
X = 1
Y = 1
Y = 2
Y = 6
Y = 7
Y = 8
Y = 9
X = 2
Y = 1
Y = 2
Y = 3
Y = 4
Y = 5
Y = 6
Y = 9
Y = 10
Y = 11
Y = 12
Y = 14
Y = 15
Autotransformer (T3)
Fuses
(F3.x).
No 24 V supply
No firmware or S2:1-2
50 A / 60 A output active, waiting for
DCSLink communication
50 A / 60 A output active, DCSLink communication OK
Warning or Fault
Warning
Phase missing, see parameter 28.63 and 42.68
Warning
Temperature heatsink
Warning
Parameters added
Warning
Parameter up- or download failed
Warning
Compatibility
Warning
Parameters restored
Fault
DCSLink communication
Fault
Supply voltage synchronization
Fault
Overcurrent
Fault
Fast voltage rise, see parameter 28.62 and 42.67
Fault
AC supply voltage < 30 V
Fault
AC supply voltage > 650 V
Fault
Temperature heatsink
Fault
Parameter flash read
Fault
Compatibility
Fault
Auxiliary voltage
Fault
General hardware (no reset possible)
Fault
General firmware (no reset possible)
3ADW000462R0301 DCS880 Hardware Manual e c
AC
AC
129