Carrier 070-08/024070 Installation, Start-Up, Operating And Service And Maintenance Instructions page 37

120/c series single-stage deluxe induced-combustion 4-way multipoise furnace
Table of Contents

Advertisement

TERMINALS
WITH
THERMOSTAT
REMOVED
(ANITICIPATOR,
CLOCK,
ETC.,
MUST
BE OUT
OF CIRCUIT.)
FROM
UNIT
24-V
CONTROL
TERMINALS
EXAMPLE:
5.0 AMPS
ON AMMETER
= 0.5 AMPS
FOR THERMOSTAT
10 TURNS
AROUND
JAWS
ANTICIPATOR
SETTING
A96316
Fig. 54--Amp
Draw Check With Ammeter
c. Unblock return air to permit normal circulation.
d. Burners will re-light when lurnace cools down.
2. Check draft salk:guard switch.
The purpose of this control is to cause the sale shutdown of the
l?lrnace during certain blocked vent conditions.
a. Verify vent pipe is cool to the touch.
b. Disconnect power to furnace and remove vent connector
l?'om lilrnace vent elbow.
c. Restore power to lurnace and set room thermostat above
room temperature.
d. After normal start-up,
allow furnace to operate
liar 2
minutes, then block vent elbow in furnace 80 percent of
vent area with a piece of fiat sheet metah
e. Furnace should cycle olT within 2 minutes. If gas does not
shut off within 2 minutes, determine reason draft salcgnard
switch did not function properly and correct condition.
f. Remove blockage 15"orelurnace vent elbow.
g. Switch will auto-reset when it cools.
h. Re-install vent connector.
NOTE:
Should switch
remain open
longer
than 3 minutes,
furnace control board will lockout the furnace liar 3 hours. To reset
furnace control board, turn thermostat below room temperature or
from HEAT to OFF and turn 115v power OFF, then back ON.
3. Check Pressure Switch
This control proves operation of the draft inducer blower.
a. Turn o11 l lS-v power to lurnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115-v power to li_rnace.
d. Set thermostat to "call Ik_rheal" and wait 1 minute. When
pressure switch is functioning properly, hot surface igniter
should NOT glow and control diagnostic light flashes a
status code 32. If hot surface igniter glows when inducer
motor is disconnected, shut down l_lrnace immediately.
e. Determine reason pressure switch did not lunction properly
and correct condition.
f. Turn off 115-v power to furnace.
g. Reconnect
inducer motor wires, replace outer door, and
turn on 115-v power.
37
Table
10-GAS
RATE
(CU FT/HR)
SECONDS
SIZE OF TEST DiAL
SECONDS
SIZE OF TEST DiAL
FOR 1
1
2
5
FOR 1
1
2
5
REVOLUTION
Cu Ft
Cu Ft
Cu Ft
REVOLUTION
iCu Ft
Cu Ft
Cu Ft
10
360
720
1800
50
72
144
360
11
327
655
1638
51
71
141
355
12
300
600
1500
52
68
138
348
18
277
555
1385
53
68
136
340
14
257
514
1286
54
67
133
333
15
240
480
1200
55
65
131
327
16
225
450
1125
56
64
129
321
17
212
424
1059
57
63
126
316
18
200
400
1000
58
82
124
310
19
189
379
947
59
81
122
305
20
180
360
900
60
80
120
300
21
171
343
857
62
58
118
290
22
184
327
818
64
56
112
281
23
157
313
783
68
54
109
273
24
150
300
750
68
53
108
265
25
144
288
720
70
51
103
257
26
138
277
892
72
50
100
250
27
133
267
867
74
48
97
243
28
129
257
843
78
47
95
237
29
124
248
821
78
46
92
231
30
120
240
8OO
80
45
90
225
31
116
232
581
82
44
88
220
32
113
225
563
84
43
88
214
33
109
218
545
88
42
84
209
34
106
212
529
88
41
82
205
35
103
208
514
90
40
80
200
38
100
200
500
92
39
78
196
37
97
195
488
94
38
78
192
38
95
189
474
98
38
75
188
39
92
185
462
98
37
74
184
40
90
180
450
100
36
72
180
41
88
178
439
102
35
71
178
42
86
172
429
104
35
89
173
48
84
167
419
106
34
88
170
44
82
164
409
108
33
87
187
45
80
160
400
110
33
85
184
46
78
157
391
112
32
84
181
47
76
153
383
116
31
82
155
48
75
150
375
120
30
80
150
49
73
147
367
h. Blower will run lot 90 sec belol'C beginning the call R_r
heat again.
i. Furnace should ignite normally.
Step 5--Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that blower OFF-DELAY time is selected as desired.
3. Verify that blower and burner access doors are properly
installed.
4. Cycle test lurnace with room thermostat.
5. Check operation of accessories
per manufacturer's
instruc-
tions.
6. Review User's Guide with owner.
7. Attach literature packet to l_lrnace.