10-6. TEST POINT DIAGRAM
10-6-1. Power board
PLA-RP1.6AA.UK
PLA-RP2AA.UK
PLA-RP2.5AA.UK
PLA-RP3AA.UK PLA-RP3AA
PLA-RP4AA.UK PLA-RP4AA
PLA-RP5AA.UK PLA-RP5AA
PLA-RP6AA.UK PLA-RP6AA
CN02
Connect to the indoor
controller board (CN03)
Between 1 and 2 0~24V DC
(Indoor/Outdoor transmission)
Between 2 and 3 220~240V AC
.UK
1
.UK
1
.UK
1
.UK
1
+
71
CN2S
Connect to the indoor controller
}
board (CN2D)
+
(12~16V DC)
+ –
Fuse 4A/250V
CN01
Connect to the Terminal Block (TB4)
(Indoor/outdoor connecting line)
Between 1 and 2 220~240V AC
Between 2 and 3 0~24V DC
(Indoor/outdoor transmission)