WARNING! This installation guide provide the basic wiring, programming and troubleshooting informa- tion required to install the Lun Security System. Use this guide in conjunction with the Lun-25. Reference Manual and Configurator Operatinig Manual available online from ORTUS Group website at www.ortus.io.
Radio Receiver MCR-300 Visonic Wire Complete all wiring including modules, L25-R433 ORTUS Group (for Visonic) keypads/readers, zones, siren and ground L25-Crow ORTUS Group (for Crow) connection. Save module serial numbers L25-R433M ORTUS Group (for Jablotron) on page 11 uartBridge Ajax ...
This alarm system must be installed and used within an fed in this document and/or on the equipment. environment that provides the pollution degree max 2 and Lun-25 Control Panel. • over-voltages category 11 NON-HAZARDOUS LOCATIONS, Additional Control Panel’s spare parts and in- •...
• Terminal Descriptions interface bus. Separate wire runs for keypads/read- ers and zone expanders are not necessary. The following terminals are available on the Lun-25 Con- No module can be more than 150m/15m (in wire • trol Panel: length) from the panel as noted in terminal de- Table 1 scription table above.
Page 6
Control Panel detects if the circuit is secure, open, NOTE: Wire and installa- or shorted. tion hardware not included. Battery A sealed, rechargeable, lead acid or gel type 12V 2.3Ah battery is required for power standby. Lun-25. Installer Guide Revision...
TAN 2. Install the cable driver if required. You can down- bus. load it online at www.ortus.io. The Control Panel provided up to 2 additional ICD (key- 3. Connect the “Lun-GPRSg cable to the “Confg-AM11g pad or readers) and up to 4 zone expanders.
Configuration – Create main menu item or press a wireless zones table. button. 5. Select wireless zone number (at frst column) by 5. Select a Lun-25 Control Panel type and confrm it touching it: by Ready button. To enrolling – select zone with free SensorID •...
Page 9
8. To delete the existing enrolled wireless detector (without any ICD), their signal strength can not be checked. press , then the appropriate ZONE LED will fashing as free. 9. To exit press . The MODE 0 LED will turn off. Lun-25. Installer Guide Revision...
13.70-13.80VDC. Replace fuse battery voltage FU2 (1.5A) if required 12.5VDC under load Manufacturer: ORTUS Group 5624 California st, San Francisco, CA 94121, USA Tel.:+1 650 240 27 62 mail: info@ortus.io http://www. ortus.io Lun-25. Installer Guide Revision...
Wireless Devices Zone # Device type Serial Number Receiver Installer – Defined Access Codes Installer Code Group #1 Administrator Code Fire Subsystem Code Group #2 Administrator Code Fire Subsystem Code ICD Information ICD Type Serial Number Lun-25. Installer Guide Revision...