Input Specifications And External Wiring - Mitsubishi Electric FX3G-14M series Hardware Manual

Melsec-f fx3g series
Hide thumbs Also See for FX3G-14M series:
Table of Contents

Advertisement

3.2
Power supply specifications and example of
external wiring
As for the details of the power supply specifications and example of
external wiring, refer to the following manual.
→ Refer to FX
Series User's Manual - Hardware Edition.
3G
3.2.1
Power supply specifications
[Main unit, Input/output extension units]
Specification
Item
AC power type
DC power type
Supply voltage
100 to 240V AC
24V DC
Voltage fluctuation range
-15%, +10%
-15%, +20%
Rated frequency
50/60Hz
Operation can
Operation can be
be continued
continued upon
Allowable instantaneous
upon occurrence
occurrence of
power failure time
of instantaneous
instantaneous
power failure for
power failure for
10 ms or less.
5 ms or less.
FX
-14M,
3G
250V 1A
125V 2.5A
FX
-24M
3G
FX
3G
-40M,
250V 3.15A
125V 3.15A
Power fuse
FX
-60M
3G
FX
-32E
250V 3.15A
2N
FX
-48E
250V 5A
250V 5A
2N
30A max. 5ms or
less/100 V AC
30A max. 1ms or
Main unit
50A max. 5ms or
less/24 V DC
less/200 V AC
Rush current
40A max. 5ms or
FX
-32E,
2N
less/100 V AC
FX
-48E
60A max. 5ms or
2N
less/200 V AC
FX
-14M
31W
19W
3G
FX
-24M
32W
21W
3G
Power
FX
-40M
37W
25W
3G
consumption
*
FX
-60M
40W
29W
3G
(
1)
FX
-32E
30W
2N
FX
-48E
35W
30W
2N
Main unit
400mA
24V DC
service
FX
-32E
250mA
2N
power supply
FX
-48E
460mA
2N
5V DC built-
FX
-32E
2N
in power
690mA or less
690mA or less
FX
2N
-48E
supply
*
(
1) This item shows values when all 24V DC service power
supplies are used in the maximum configuration connectable
to the main unit or input/output extension units,
For the power (current) consumed by the input/output
extension units/blocks, refer to FX
Series User's Manual -
3G
Hardware Edition. (The DC power type main unit does not
have a 24V DC service power supply.)
→ For the power consumed by the special extension blocks,
refer to the respective manual.
→ Refer to FX
Series User's Manual - Hardware Edition.
3G
3.2.2
Example of external wiring (AC power type)
100 to 240V AC power is supplied to the main unit and input/output
extension unit.
→ For the details of wiring work, refer to section 3.1.
PLC
Main unit
L
*
(
)
N
-
Input/output
extension
Fuse
unit
L
N
MC
-
*
(
) Class D grounding
See section 3.3 for
Power supply for loads connected
details.
to PLC output terminals
3.2.3
Example of external wiring (DC power type)
-
24V DC power is supplied to the main unit and input/output
extension unit.
→ For the details of wiring work, refer to section 3.1.
PLC
Main unit
-
*
(
)
-
-
-
Input/output
extension
Fuse
unit
MC
*
(
) Class D grounding
See section 3.3 for
Power supply for loads connected
details.
to PLC output terminals
3.3
Grounding
Ground the PLC as stated below.
• Perform class D grounding. (Grounding resistance: 100 Ω or less)
• Ground the PLC independently if possible.
100 to 240V AC
If it cannot be grounded independently, ground it jointly as shown
below.
Other
PLC
Breaker
equipment
Power on
Independent grounding
Emer-
(Best condition)
gency
PL
MC
• Use ground wires thicker than AWG14 (2 mm
• Position the grounding point as close to the PLC as possible to
MC
decrease the length of the ground wire.
3.4

Input specifications and external wiring

As for the details of the Input specifications and external wiring, refer
to the following manual.
MC
→ Refer to FX
3.4.1
Input specifications (24V DC input type)
Item
DC
power
FX
2N
-8ER
supply
FX
-14M,
3G
FX
2N
-8EX
DC
AC
FX
-24M
3G
Number of
input
FX
-16EX,
2N
points
FX
-32E
2N
FX
-40M,
3G
FX
-48E
2N
FX
-60M
3G
Input connecting type
24V DC
Input form
Circuit protector
Main unit
Input
Power on
signal
Input/
Emer-
voltage
output
gency
PL
extension
MC
unit
MC
Main unit
Input
impedance
Input/output
extension unit/block
MC
Main unit
Input
signal
current
Input/output
extension unit/block
Main unit
ON input
sensitivity
current
Input/output
extension unit/block
OFF input sensitivity current
Input response time
Input signal form
(Input sensor form)
Other
Other
PLC
PLC
equipment
equipment
Shared grounding
Common grounding
(Good condition)
(Not allowed)
Input circuit insulation
2
).
Input operation display
*
(
3.4.2
Series User's Manual - Hardware Edition.
3G
Specification
*
4 points (8 points)(
1)
8 points
*
14 points(16 points)(
1)
16 points
24 points
*
36 points(40 points)(
1)
Refer to FX
Series
3G
User's Manual -
Hardware Edition
AC power type 24V DC +10%, -10%
DC power type 20.4-28.8V DC
AC power type 24V DC +10%, -10%
DC power type 24V DC +20%, -30%
X000 to X007
3.3kΩ
X010 or more
4.3kΩ
4.3kΩ
X000 to X007
7mA/24V DC
X010 or more
5mA/24V DC
5mA/24V DC
X000 to X007
4.5mA or more
X010 or more
3.5mA or more
3.5mA/24V DC
1.5mA or less
Approx. 10ms
Item
Specification
• Sink input:
No-voltage contact
input
NPN open collector
transistor
• Source input:
No-voltage contact
input
PNP open collector
transistor
Photocoupler insulation
LED on panel lights
when photocoupler is
driven.
1) Each value inside ( ) indicates the number of occupied points.
Examples of input wiring [AC power type]
1. Sink input type
2. Source input type
[1]
[1]
Fuse
Fuse
L
L
*
*
(
)
(
)
N
N
100 to 240V AC
100 to 240V AC
S/S
S/S
0V
0V
24V
24V
X000
X000
X001
X001
3-wire type
3-wire type
X002
X002
sensor
sensor
X003
X003
[2]
[2]
S/S
S/S
X000
X000
*
(
) Class D grounding
See section 3.3 for details.
[1]:Main unit, Input/output extension unit
(Common to both sink and source inputs)
[2]:Input/output extension block
(Common to both sink and source inputs)

Advertisement