Meriam MFC 4101 HART Operator's Instruction Manual

Mfc 4100 series

Advertisement

Quick Links

File No. 4100:440-4
December 2003
®
MFC 4100 HART
Communicator
MFC 4101 HART Communicator with Documentation
MFC 4102 HART Communicator with Intrinsic Safety (I.S.)
MFC 4103 HART Communicator with Documentation and I.S.
OPERATOR
INSTRUCTION MANUAL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MFC 4101 HART and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Meriam MFC 4101 HART

  • Page 1 File No. 4100:440-4 December 2003 ® MFC 4100 HART Communicator MFC 4101 HART Communicator with Documentation MFC 4102 HART Communicator with Intrinsic Safety (I.S.) MFC 4103 HART Communicator with Documentation and I.S. OPERATOR INSTRUCTION MANUAL...
  • Page 2 For a geographic listing of Representatives and contact information, visit our web site at www.meriam.com and click on the “Representatives” button. Contact Meriam Process Technologies directly by phone at (216) 281-1100 or by e-mail at meriam@meriam.com. Direct all assistance inquiries to Technical Services. ®...
  • Page 3 MFC 4100 HART Communicator OPERATING INSTRUCTIONS MFC 4100, MFC 4101, MFC 4102, MFT 4103 TABLE OF CONTENTS Subject Page MFC 4100 Communicator Overview ......................1 Display Overview ............................1 Header Line Symbols ........................... 2 Keypad Overview ............................2 Alphanumeric Keys ..........................3 Left / Right Arrow Keys ........................
  • Page 4 Save / Send Configuration Functions...................16 Documenting HART Configurations with Meriam DMS software ............17 MFC 4100 Device Specific & Generic HART Communication ..............17 Using Generic Communications ......................17 DOF / Firmware Download Site .......................18 Who may use............................18 PC Requirements ..........................18 Preparing the MFC for updating ......................18 Preparing to Download .........................18...
  • Page 5: Display Overview

    MFC 4100 HART COMMUNICATOR The MFC 4100 HART Communicator is the latest handheld communicator in the Meriam family of HART devices. All HART field devices can be configured, polled, and trimmed using the MFC with HART communications. The MFC is a full function HART Communicator supporting Universal, Common Practice and Device Specific commands for commissioning, configuration and maintenance operations.
  • Page 6: Header Line Symbols

    HEADER LINE SYMBOLS KEY heart symbol indicates active HART communication up arrow indicates SHIFT key is on # number sign indicates numeric / symbol entry is the present entry mode for all dual functions keys A letter indicates alpha entry is the present entry mode for all dual function keys battery symbol indicates MFC under battery power;...
  • Page 7: Quick Menu

    Configs, and Create Configs functions for all MFC models. For Documenting models MFC 4101 and MFC 4103, this key also provides documenting functions used with the Meriam Device Management System software. Access to this key is disabled while critical HART communications are in process.
  • Page 8: Left / Right Arrow Keys

    Alpha Lock This key changes the keypads dual function keys from numeric/symbol entry mode to alpha ALPHA character entry mode and back. The present entry mode is indicated in the display header line next to LOCK the power supply indicator on the upper right of the screen. The letter “A” in the display header line indicates that alpha entry is active while a # sign in the display header indicates that numeric / symbol entry is active.
  • Page 9: General Operation

    The MFC 4100 can be powered for portable operation by two each 9-volt alkaline, Lithium or NiMH batteries. Alkaline batteries are standard with the MFC shipment. Meriam offers NiMH batteries and charger cradles (external charge only) as an option. For bench top operations and download operations, an AC adapter (P/N A36742) is recommended.
  • Page 10: Mfc Main Display

    Turning on the MFC Use the dedicated ON/OFF key to power up the MFC. A brief diagnostic runs while the Meriam Process Technologies logo, MFC model number, and MFC firmware version is displayed. A message is displayed indicating the MFC is scanning for a HART device at address zero. The following scenarios are possible.
  • Page 11: Mfc Configurations Settings

    MFC Configurations Settings Lockout Feature The MFC HART Communicator can be programmed to lock out certain standard functions that a supervisor may wish to control. The functions included are used to set up the MFC for normal use, change online HART device configurations, create offline HART device configurations, update the installed DOFs list (HART device profiles), or to update the MFC’s operating firmware.
  • Page 12: Disable Lockout

    BE SURE TO SAVE THIS CODE IN A SAFE PLACE IN THE EVENT YOU FORGET THE NUMBER. ACCESS TO LOCKED-OUT FEATURES WILL BE DENIED WITHOUT THE PROPER CODE. To Disable Lockout When you wish to use a function or edit a value that is protected by the lockout code, enter the three digit Lockout code when prompted and press Save.
  • Page 13: External Connections

    Device Object Files (DOFs) and documenting operations (Documenting options pending). All MFC upgrades are available via the Meriam Process Technologies Download Site accessible from www.meriam.com. The MFC will not need to be returned to Meriam for firmware updates or for the addition of DOF files.
  • Page 14: Hazardous Area Use

    Note: Restrictions apply to the use of Intrinsically Safe MFC units in hazardous areas. Refer to the Intrinsically Safe Control Document in the Appendix for exact details. Meriam Process Technologies reserves the right to revise the Control Document without notice. Contact Meriam Process Technologies (phone (216) 281-1100) for the current Intrinsically Safe Control Document.
  • Page 15: Hart Commands

    For low load loops (less than 250 Ω), a 250 Ω resistor will need to be added to the loop to insure reliable HART communications. Meriam supplies a 250 Ω load resistor in the form of a standard adaptor (P/N...
  • Page 16: Hart Communications

    When connecting the MFC 4100 to a loop with a resistive load greater than 250 Ωs, the HART jacks may be connected across the loop + and – or to the HART device communication terminals. Refer to the following diagram for connecting across the loop + and -. Connecting to the MFC communication terminals ®...
  • Page 17: Multi-Drop Poll

    When no device connection is detected or a device with non-zero (Multi-drop or Burst Mode) address is found, the message Device 0 Not Found is displayed and the MFC enters the MFC Main navigation screen. The MFC Main screen allows the user to launch a multi-drop poll to find all devices with non-zero addresses on the loop, to manually start an Online poll, or to enter Offline Mode.
  • Page 18: List / Show Dofs

    An MFC with Documenting option (MFC 4101, MFC 4103) will also list configurations downloaded from the separately available Device Management System software from Meriam (see www.meriam.com/dm_solns.htm for more information). Tag numbers, date / time of save, type of configuration stored, and other information are displayed under List/Edit Configs.
  • Page 19: Online Setup Mode

    Create Configs: The Create Configs function allows the user to configure a HART device file in Offline Mode for sending to the intended device later when connected in the Online Mode. Use the soft key controls to move through the list and select the device model number required. The menus prompt the user to make the necessary configuration selections, tag the file for later retrieval and use, and edit configuration lines as required.
  • Page 20: More Status Message

    If communication is still not established, check the List / Show DOFs menu under Offline Menu. Check the list for the presence of the “Generic” DOF under the manufacturer name “Meriam.” If “Generic” is found, then HART communication is possible when the device is properly wired and connected to the MFC (see connection troubleshooting details above).
  • Page 21: Documenting Hart Configurations With Meriam Dms Software

    Device Management System ® MFC 4100 Device Specific & Generic HART Communications Meriam supports a large and growing number of Device Specific DOFs (Device Object Files). For a current ® listing of HART devices with full Device Specific communication support, go to www.meriam.com...
  • Page 22: Dof / Firmware Download Site

    One of the unique features of the MFC 4100 Series is the built-in ability to have firmware upgrades installed by the user at his location. The Meriam Download Site is accessible over the Internet and provides for the convenient download of new or revised firmware and DOF’s (Device Object Files) for HART communication.
  • Page 23: Using The Download Site

    MFx Installer utility should be loaded onto the host PC from the instruction manual CD (included with MFC shipment) or from the Meriam Download Site where it can be found on the File Download Area page. MFx Installer coordinates the download operations from the host PC to the MFC. Periodic improvements may be incorporated into this Utility.
  • Page 24: Returning The Mfc For Repairs

    Meriam Process Technologies Representative (see list and contact information at www.meriam.com) or contact the factory direct at the numbers listed below. Please do not send any unit in for repair without first contacting Meriam Process Technologies or Representative for a Return Material Authorization (RMA) number. This number will be provided by the Meriam Repair Department when you call, fax or e-mail your information.
  • Page 25: Ordering Information

    BASE UNIT MODEL No & DESCRIPTION: MFC 4100 HART Communicator MFC 4101 HART Communicator with Documenting capability (via Meriam DMS software) MFC 4102 HART Communicator with Intrinsically Safe certification. I.S. certification by MET Laboratories per testing to UL3111-1 First Edition Rev. 6/30/94, CAN/CSA-22.2 No. 1010.1 &...
  • Page 26 ACCESSORIES A36885 Protective red boot provides degree of protection against drop related damage; slip on A900529-00014 HART Test Lead Kit (inc'd w/ MFC) - std banana plugs, mini-grabbers, 250 Ω resistor A36821 Std size 250 Ω shunt resistor (inc'd w/ MFC) - req'd for HART low resistance loops A900447-00052 DB-9 cable, Male x Female, 6 ft length A36875...
  • Page 27 Intrinsic Safety Control Document...
  • Page 28 1151 Rev. 5 Menu Tree Pressure Value Zero Trim Pressure Percent Range Lower Sensor Trim Process Vars Analog Output Upper Sensor Trim Lower Sensor Trim Point Upper Sensor Trim Point Pressure Trim Re Range Sensors Signal Cond Pressure Lower Range Value Pressure Upper Range Value Set 4mA Range Set 20mA Range...
  • Page 29 3051C Rev. 2 Menu Tree Pressure Value Zero Trim Pressure Percent Range Lower Sensor Trim Process Vars Analog Output Upper Sensor Trim Temperature Value Lower Sensor Trim Point Upper Sensor Trim Point Sensor Trim Re Range Sensors Signal Cond Pressure Lower Range Value Units Pressure Upper Range Value Set 4mA Range...
  • Page 30 EJA Rev. 2 Menu Tree Pressure Value Zero Trim Pressure Percent Range Lower Sensor Trim Analog Output Upper Sensor Trim Temperature Value Lower Sensor Trim Point Process Static Pressure Value Upper Sensor Trim Point Vars Engr Display Unit Engr Display Value Pressure Lower Range Value Pressure Upper Range Value Sensor Trim...
  • Page 31 EJA Rev. 1 Menu Tree Pressure Value Zero Trim Pressure Percent Range Lower Sensor Trim Analog Output Upper Sensor Trim Temperature Value Lower Sensor Trim Point Process Static Pressure Value Upper Sensor Trim Point Vars Engr Display Unit Engr Display Value Pressure Lower Range Value Pressure Upper Range Value Sensor Trim...

This manual is also suitable for: