6 | INSTALLING THE CONNECTIVE PIPEWORK
4.5 Confirmation for the diameters of outdoor unit
connecting pipes
Table 4-4 R410A outdoor unit connecting pipes diameters
Total capactiy
Main pipe size when the total
of the
equivalent pipework length of liquid
outdoor units
+ gas side is <90 m
gas
liquid
The first Line
side
side
Branch Pipe
(inches)
(inches)
A<160
Ø15.9
Ø9.5
IDU - 01
Ø19.1
Ø9.5
160≤A<230
IDU - 01
NOTE
When installing branch joints ensure there is at least 0.5 m of straight
pipe before and after the branch joint;
The straight distance between branchpipes must be at least 0.5 m;
The straight distance where the branch pipes connect to the indoor
unit must be at least 0.5 m;
Branch header must be connected with the indoor units directly,
further branch connections are not allowed.
Select branch joint
Select the branch joint required by the total designed capacity of the
indoor units which it connects to. If this capacity is more than that of
the outdoor unit, then select the connection according to the outdoor
unit.
The selection of branch header depends on the quantity of branches
it connects to.
Connection method
Table 4-5
Gas side
8kW
Flaring
10.5kW
Flaring
12kW
Flaring
14kW
Flaring
16kW
Flaring
18kW
Flaring
Indoor unit
Flaring
Branch pipe
Brazing or Flaring
Pipework sizes at the branch pipe
Table 4-6
Refrigerant
Indoor Unit
Capacity
A(x100W)
R410A
A≤45
12.7(Flaring nut)
A≥56
15.9(Flaring nut)
6 720 874 421 (2017/04) ZA
Main pipe size when the total
equivalent pipework length of liquid
+ gas side is ≥90 m
gas
liquid
The first Line
side
side
Branch Pipe
(inches)
(inches)
Ø19.1
Ø9.5
IDU - 01
Ø22.2
Ø9.5
IDU - 02
Liquid side
Flaring
Flaring
Flaring
Flaring
Flaring
Flaring
Flaring
Brazing or Flaring
Gas Side (Ø)
Liquid Side (Ø)
6.4(Flaring nut)
9.5(Flaring nut)
Pipe diameter of the connections onto the outdoor unit.
Table 4-7
Pipework
Pipe diameter of outdoor
side
unit's connections (inches)
Gas Side
MODEL
(kW)
8
10.5
12
14
16
18
Table 4-8
Outdoor Unit
Capacity of
(kW)
Outdoor unit
(horse power)
8
2.5
10.5
3
12
4
14
5
16
6
18
6.5
When connecting more than one indoor unit, the largest capacity connected
should be less than 8KW.
When the total capacity of the indoor units is greater than 100% of the
outdoor units capacity, ensure you turn the indoor units on one by one one.
Too many at once will cause damage to the compressor.
When the total capacity of the indoor units is greater than or equal to
16.8 kW, the size of primary gas pipe should be enlarged from Ø16 to Ø19.
Table 4-9
Capacity
Capacity
ranking
(horsepower)
18
0.6
22
0.8
28
1
36
1.25
45
1.7
56
2
When the outdoor unit connects to one indoor unit
Table 4-10
MODEL
The max height drop (m)
(kW)
When out-
When
door
outdoor unit is
unit is top
bottom
8
25
20
10.5
25
20
12
25
20
14
25
20
16
25
20
18
25
20
Liquid Side
Ø15.9
Ø9.5
Ø15.9
Ø9.5
Ø15.9
Ø9.5
Ø15.9
Ø9.5
Ø19.1
Ø9.5
Ø19.1
Ø9.5
Maximum
Sum Capacity of
Quantity of
Indoor unit (horse-
Indoor units
power)
4
45%~130%
5
45%~130%
6
45%~130%
6
45%~130%
7
45%~130%
9
45%~130%
Capacity
Capacity
ranking
(horsepower)
80
2.5
10.5
3
120
4
140
5
160
6
The length of
The number
refrigerant pipe
of bends
(m)
50
50
50
less than 10
50
50
50