Q6SE SEriES 14 SEEr uSEr’S manual & inStallation inStructionS SinglE PackagE HEat PumP - 3 PHaSE - r-410a imPortant attEntion inStallErS: it is your responsibility to know this product better than your customer. this includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product.
Page 3
uSEr inFormation imPortant SaFEtY inFormation ....4 Operating the Heat Pump for Automatic Cooling & Heating ..............5 about tHE HEat PumP ........4 Operating the Indoor Blower Continuously ..... 5 oPErating inStructionS ........4 Shutting the Heat Pump Off ........5 Cooling Operation ...........
uSEr inFormation imPortant SaFEtY inFormation oPErating inStructionS Please read all instructions before servicing this equipment. Please refer to the thermostat manufacturer’s User manual Pay attention to all safety warnings and any other special for detailed programming instructions. notes highlighted in the manual. Safety markings are cooling operation used frequently throughout this manual to designate a 1.
uSEr inFormation operating the Heat Pump for automatic HEat PumP maintEnancE cooling & Heating caution: 1. Set the thermostat system mode to AUTO and the thermostat fan mode to AUTO. See Figure Shut off all electrical power to the unit before notE: Thermostat styles vary.
inStallEr inFormation imPortant SaFEtY inFormation Warning: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special unless noted otherwise in these instructions, notes highlighted in the manual. Safety markings are only factory authorized parts or accessory used frequently throughout this manual to designate a kits may be used with this product.
gEnEral inFormation The Q6SE series heat pump is designed only for outdoor 0" 36” For Coil Only rooftop or ground level installations. This unit has been tested for capacity and efficiency in accordance with A.H.R.I. Standards and will provide many years of safe and dependable comfort, providing it is properly installed and maintained.
air Filter requirements HEat PumP inStallation Packaging removal Warning: Remove the shipping carton and User’s Manual from the equipment. Take care not to damage the tubing never operate the unit without a filter in place. connections when removing the carton. For rooftop Dust and lint could accumulate on internal parts, installations, remove and discard the two supports attached beneath the unit.
• Units require horizontal roof curb and return air kit for horizontal installations. • Ductwork should be attached directly to flanges on panels supplied in horizontal duct conversion kits. rooftop Rooftop installations must be located according to local Roof building codes or ordinances and these requirements: Curb •...
condensate Drain line Voltage Condensate is removed from the unit through the 3/4” • A wiring diagram is located on the inside cover of the female pipe fitting located on the front side of the unit. units electrical box. The installer should become familiar with the wiring diagram before making any electrical Figure 6.
unbalanced 3-Phase Supply Voltage grounding Voltage unbalance occurs when the voltages of all phases Warning: of a 3-phase power supply are no longer equal. This unbalance reduces motor efficiency and performance. the unit cabinet must have an uninterrupted or Some underlying causes of voltage unbalance may include: Lack of symmetry in transmission lines, large unbroken electrical ground to minimize personal single-phase loads, and unbalanced or overloaded...
rEcommEnDED maximum minimum timE tErminatE 30 SEconD WirE jumPEr WirE lEngtH (Ft) From unit bEtWEEn tEmPEraturE comPrESSor gaugE PoSition to tHErmoStat DEFroStS (min) (° F) DElaY Function table 3. thermostat Wire gauge table 4. Demand Defrost curve Profiles Demand Defrost control •...
Start uP & aDjuStmEntS 3. Allow the cooling system to operate for several minutes and then set the temperature selector above room Pre-Start check list temperature. Verify the fan and compressor cycle off √ Verify the unit is level and allows condensate to drain. with the thermostat.
charging an r-410a unit in ac mode caution: (With Outdoor Temperatures Above 65° F) 1. With the system operating at steady-state, measure the the unit should never be operated without a liquid refrigerant pressure in psig at the service valve. filter in the return air system.
Electrical information ECONOMIZER PLUG (IF APPLICABLE. SEE ECONOMIZER INSTALLATION INSTRUCTIONS) 1 2 3 4 5 6 7 8 9 See Note Blower Relay Brown W2 IN W2 OUT INDOOR DEFROST HEAT PUMP BOARD UNIT LOW THERMOSTAT VOLTAGE ACCESSORY TERMINAL HEAT PLUG BOARD Typical Wiring for Single Stage Heat Pump Operation with Single Stage Auxillary Electric Heat FACTORY WIRING...
ECONOMIZER PLUG (IF APPLICABLE. SEE ECONOMIZER INSTALLATION INSTRUCTIONS) 1 2 3 4 5 6 7 8 9 See Note Blower Relay W2 IN INDOOR W2 OUT HEAT PUMP UNIT LOW THERMOSTAT ACCESSORY DEFROST VOLTAGE HEAT PLUG BOARD TERMINAL BOARD Typical Wiring for Single Stage Cool, Single Stage Electric Heat (Field Supplied) FACTORY WIRING FIELD WIRING NOTE: If installing an economizer using the new Honeywell W7220A JADE control module, the following change MUST be made to...
cooling charging charts Q6SE-X36 Charging Chart-Cooling Remove refrigerant when above curve Add refrigerant when below curve Liquid Temperature ( ° F ) Figure 12. charging chart for 3 ton units Q6SE-X48 Charging Chart-Cooling Remove refrigerant when above curve Add refrigerant when below curve Liquid Temperature ( °...
Q6SE-X60 Charging Chart-Cooling Remove refrigerant when above curve Add refrigerant when below curve Liquid Temperature ( ° F ) Figure 14. charging chart for 5 ton units airflow Data ExtErnal Static PrESSurE DroP moDEl motor (incHES WatEr column) numbEr SPEED Q6SE Tap T1 1137...
inStallation cHEck liSt ElEctrical SYStEm inStallation aDDrESS: Electrical connections tight? CITY: STATE: Line voltage polarity correct? UNIT MODEL # Has the thermostat been calibrated? Is the thermostat level? UNIT SERIAL # Is the heat anticipator setting correct? Unit Installed Minimum clearances SinglE PHaSE unitS as snhown in Figure 2 (page...