Advertisement

Figure 5: CA-A470-A indicators
Green "STATUS" LED:
Flash = Module OK
Slow flash = Communication failure
(see also "COMM" LED)
Green "LOCK#1" and "LOCK #2" LEDs:
ON = Relay activated.
D1NC
LOCK#1
COM
STATUS
D1NO
D2NC
LOCK#2
COM
D2NO
Z1
COM
Z2
Z3
COM
Z4
READER#2
DATA
Green "READER#2 DATA" and "READER#1 DATA" LED:
Long flash = Receiving card read
Short flash = Receiving card read, but the system
does not recognize the card's format
OFF = Not receiving card read
The reader LEDs can be used to verify the reader's connections and programming. If no flashing occurs when a card
is presented to the reader, the reader may be installed incorrectly. A short flash indicates that the reader is correctly
installed, but the card is the wrong type or that the reader was incorrectly programmed.
Warranty
Paradox Security Systems Ltd. ("Seller") warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as spe-
cifically stated herein, all express or implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for
a particular purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be used in conjunction with products not
manufactured by Seller, Seller cannot guarantee the performance of the security system and shall not be responsible for circumstances resulting from the product's inability to
operate. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting the specifications. Returns
must include proof of purchase and be within the warranty period. In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct
or indirect or consequential or incidental, including without limitation, any damages for lost profits stolen goods, or claims by any other party, caused by defective goods or
otherwise arising from the improper, incorrect or otherwise faulty installation or use of the merchandise sold. Notwithstanding the preceding paragraph, the Seller's maximum
liability will be strictly limited to the purchase price of the defective product. Your use of this product signifies your acceptance of this warranty.
BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make additional warranties that are binding on the Seller.
© 2006 CDVI. All rights reserved.
Centaur is a trademark or registered trademark of CDVI or its affiliates in Canada, the United States and/or other countries.
Green "AC" LED:
ON = AC power
OFF = Power failure
Green "AUX" LED:
ON = Auxiliary power
OFF = Auxiliary power failure
Red "COMM" LED:
ON = Communication failure
OFF = OK
Green "CHECK BATT" LED:
ON = Battery verification in
progress (every minute)
Red "BATT TRBL" LED:
ON = Battery low or disconnected
CA-A470-A
AC
AC
BAT+
+
BAT-
AC OK
V+
AUX OK
V+
JP120
COMM
V-
350mA/700mA
CHECK BATT
V-
BATT TRBL
OUT5
SWITCH
BACKUP
OUT6
SW1
ADD 1
2
1
ADD 2
SW2
0
0
NO CARD
SW3
L1Energize
0
1
2 CARDS
SW4
L2Energize
1
0
ALL CARDS
SW5
BACKUP1
1
1
UNLOCK DOOR
BACKUP2
SW6
LOW HIGH
A+
SW7
PULSE 5&6
B-
B-
SW8
N/D
A+
GND
T A MP E R
READER#1
DATA
T A MP E R
EOL
TX RX
E-BUS
Red "TX" LED and green "RX" LED:
ON = Communication OK (may flicker)
OFF = Communication failure
Figure 6: Connection drawing of the CA-A470-A
LOCK 2
(Optional connection method)
24VDC
LOCK 1
V-
12VDC
V+
LOCK#1
D1NC
COM
STATUS
D1NO
D2NC
LOCK#2
COM
D2NO
Z1
COM
Z2
Z3
COM
Z4
READER#2
DATA
KEYPAD 2
(BCD)
Input 1
1KΩ
See inputs in Centaur Software
manual: setting ATZ 2R Connection
OR
1KΩ
EOL
See inputs in Centaur Software
1KΩ
manual: setting ATZ 3R Connection
Z
COM
OR
See inputs in Centaur Software
manual: setting NC Input Connection
Z
COM
24VDC Power Supply
V-
16V Transformer
40VA
Gell Cell BAttery
12V, 7 Ah
CA-A470-A
AC
AC
BAT+
+
BAT-
AC OK
V+
AUX OK
V+
JP120
COMM
V-
350mA/700mA
CHECK BATT
V-
BATT TRBL
OUT6
SWITCH
BACKUP
OUT6
ADD 1
SW1
2
1
SW2
ADD 2
0
0
NO CARD
SW3
L1Energize
0
1
2 CARDS
L2Energize
SW4
1
0
ALL CARDS
BACKUP1
1
1
SW5
UNLOCK DOOR
SW6
BACKUP2
LOW HIGH
A+
SW7
PULSE 5&6
B-
B-
N/D
SW8
A+
GND
T A M P E R
READER#1
DATA
T A M P E R
EOL
TX RX
E-BUS
Connect to tamper
switch (N.C.)
Terminals for
KEYPAD 2
Terminals for KEYPAD 1
BROWN
READER 1
Reader and keypad wiring may differ
from the diagram. Please consult
your dealer for details.
Warning
2-Door Expansion Module (CA-A470-A)
16Vac Transformer Only
The use of a transformer with a rating other 16Vac
can severaly damage the module.
Firmware Requirements
The 2-Door Expansion Module can only be used
with CT-V900-A firmware version R2-C3-05 or higher.
Software Requirementrs
The 2 -Door Expansion Module can only be used
with Centaur version 3.0 build 400 or higher.
E-BUS :
To CT-V900 or to
other CA-A470-A
E-BUS