Johnson Controls Unitary Products YH-10 Technical Manual

Split-system air-cooled condensing units and air handlers
Hide thumbs Also See for YH-10:

Advertisement

TECHNICAL
TECHNICAL
GUIDE
GUIDE
R-410A
SPLIT-SYSTEM
AIR-COOLED CONDENSING UNITS
AND AIR HANDLERS
YH-07 thru -25 and YJ-10 thru -20
CONDENSING UNIT MODELS
PH-07 thru -15 and PJ-15 thru -20
HEAT PUMP UNIT MODELS
NH-07 thru -25 and NJ-10 thru -20
AIR HANDLING UNIT MODELS
7.5 - 25 Ton
60 Hertz
NH/NJ Indoor Units
Description
UP condensing units and heat pumps are completely assembled,
piped and wired at the factory to provide a single-piece unit for
shipment and rigging. Each unit is pressurized with a holding charge of
refrigerant R-410A for storage and/or shipping.
The compact design, clean styling, small footprint, and quiet operation
make these condensing units and heat pumps suitable for almost any
outdoor location. On rooftops... because they weigh much less than a
single package unit of similar capacity and are much easier to rig and
support. On the ground... because the footprint is compact allowing a
variety of applications.
Both the UP condensing units and heat pumps are equipped with
reliable Simplicity® SE microprocessor controls to assure proper
operation and unit protection for long product life. Products from 10 to
20 tons are available in single or dual (2 or 4 pipe) refrigerant circuits
for redundancy in operation and various application choices such as
one outdoor unit matched with two indoor units.
The UP air handling units are completely assembled units, including a
well-insulated cabinet, a DX cooling coil with copper tubing, aluminum
fins, expansion valve(s), distributor(s), 2" throwaway filters, a
centrifugal blower, a blower motor, an adjustable belt drive, a blower
YH/YJ/PH Outdoor Units
motor contactor and a small
holding charge of nitrogen.
YH/YJ/PH/PJ Outdoor Units
505430-BTG-P-0316
(Except YH-25)
ISO 9001
Certified Quality
Management System

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls Unitary Products YH-10

  • Page 1 505430-BTG-P-0316 TECHNICAL TECHNICAL GUIDE GUIDE Description UP condensing units and heat pumps are completely assembled, R-410A piped and wired at the factory to provide a single-piece unit for SPLIT-SYSTEM shipment and rigging. Each unit is pressurized with a holding charge of AIR-COOLED CONDENSING UNITS refrigerant R-410A for storage and/or shipping.
  • Page 2 An added benefit of the UP air handling units is they are heat pump applications. Johnson Controls Unitary Products...
  • Page 3 Weights And Dimensions ................101 Johnson Controls Unitary Products...
  • Page 4: Nomenclature

    2. NH/NJ-20 Airflow Option D = 3 HP Motor “F” Only. E = 5 HP Motor F = 7.5 HP Motor N = None (Motor Drive Kit Req) 1. Motors are not shipped with 25 ton Air Handler Units. Johnson Controls Unitary Products...
  • Page 5: Condensing Unit Features And Benefits

    These air handlers can be arranged for a variety of air maintenance or for service. discharge patterns in either the horizontal or vertical position. • Factory installed powered or non-powered 115 volt GFI Refer to the unit installation instructions for other application outlet. possibilities. Johnson Controls Unitary Products...
  • Page 6 The coil is Relay Kit. See details in Overload Relay Kit and Overload leak-tested at 325 psig and dried before the connections are Relay Setting Tables on Page 70. capped for storage and shipping. Johnson Controls Unitary Products...
  • Page 7: Guide Specifications

    _____ cfm entering-air temperature at the evaporator at bonded to seamless internally enhanced copper tubes _____ F wet bulb and _____ F dry bulb, and air with all joints brazed. entering the condensing unit at _____F. Johnson Controls Unitary Products...
  • Page 8 Condenser Fans • Aluminum blades riveted to corrosion resistant steel spider brackets. • Direct driven propeller-type fans • Arranged for vertical air discharge. • Statically and dynamically balanced • Equipped with PVC coated steel wire safety guards. Johnson Controls Unitary Products...
  • Page 9: Cooling

    RPM to be adjusted to meet extracted via USB device, displayed real-time via the the CFM requirements of the air delivery system. (Refer MAP Gateway as well as be broad-casted through a to Technical Guide for Airflow Capabilities.) Johnson Controls Unitary Products...
  • Page 10 The Blower Wheels Shall: Be dynamically balanced to minimize the levels of sound and vibration generated by the unit. Johnson Controls Unitary Products...
  • Page 11 Holding Charge is the amount in the unit as shipped from the factory. Includes matched indoor blower unit with 25 ft of piping. All compressors include crankcase heaters. When viewing the shaft end of the motor. Johnson Controls Unitary Products...
  • Page 12 9800 Holding Charge is the amount in the unit as shipped from the factory. Includes matched evaporator unit with 25 ft of piping. All compressors include crankcase heaters. When viewing the shaft end of the motor. Johnson Controls Unitary Products...
  • Page 13 FACE AREA (SQ. FT.) 11.1 11.1 11.1 20.0 20.0 22.2 22.2 16 x 25 x 4 Size and Quantity Per Model (In.) 20 x 24 x 4 FACE AREA (SQ. FT.) 11.1 11.1 11.1 18.0 18.0 22.2 22.2 Johnson Controls Unitary Products...
  • Page 14 Fins per inch Tube diameter (Copper) (In.) Connection, (NPTE) (In.) Inlet Outlet 1-1/2 Weight (lb) Motors, Drive and Overload Kits must be ordered separately for the NH-25. The Motor Drive and Overload Kits are to be field installed. Johnson Controls Unitary Products...
  • Page 15: Unit Limitations

    460-3-60 (20) 575-3-60 208/230-3-60 460-3-60 (25) 575-3-60 1. Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage. †. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F. Johnson Controls Unitary Products...
  • Page 16 90/77 208/230-3-60 8,000 12,000 65/57 90/77 NH-25 460-3-60 8,000 12,000 65/57 90/77 575-3-60 8,000 12,000 65/57 90/77 Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils. Johnson Controls Unitary Products...
  • Page 17: Cooling And Heating Ratings

    Gross capacity does not include heat added by blower motor. Refer to appropriate table for blower horsepower. Heat Pumps designed for matched systems only. LEGEND EER = Energy Efficiency Ratio AHRI = Air Conditioning and Refrigeration Institute IPLV = Integration Part-Load Value IEER = Integrated Energy Efficiency Ratio Johnson Controls Unitary Products...
  • Page 18: Capacity Performance

    49.1 89.7 89.7 87.9 75.3 61.4 47.4 3750 86.1 86.1 86.1 86.1 72.3 58.4 44.5 82.1 82.1 82.1 82.1 68.2 54.3 40.4 87.1 87.1 87.1 87.1 73.2 59.4 45.5 83.0 83.0 83.0 83.0 69.1 55.2 41.2 Johnson Controls Unitary Products...
  • Page 19: Btg-P

    Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 20: Johnson Controls Unitary Products

    44.6 100.0 96.3 83.0 69.8 56.6 43.4 3750 95.9 95.9 95.9 87.1 73.9 60.7 47.5 92.4 92.4 92.4 85.8 72.5 59.3 46.1 93.5 93.5 93.5 93.5 80.3 67.1 53.9 90.5 90.5 90.5 90.5 77.3 64.1 50.9 Johnson Controls Unitary Products...
  • Page 21: Btg-P

    Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 22: Btg-P

    126.1 120.4 102.1 82.5 62.9 5000 127.0 127.0 127.0 127.0 107.9 88.8 69.7 118.5 10.5 118.5 118.5 118.5 99.0 79.4 59.8 125.6 125.6 125.6 125.6 106.5 87.4 68.3 117.8 10.6 117.8 117.8 117.8 98.2 78.7 59.1 Johnson Controls Unitary Products...
  • Page 23: Btg-P

    Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 24 125.0 118.9 99.9 81.0 62.0 5000 122.2 122.2 122.2 122.2 103.5 84.9 66.2 115.0 10.5 115.0 115.0 115.0 96.1 77.1 58.1 125.7 125.7 125.7 125.7 107.0 88.4 69.7 118.7 10.5 118.7 118.7 118.7 99.8 80.8 61.8 Johnson Controls Unitary Products...
  • Page 25 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 26 125.2 100.4 75.6 6250 146.0 11.9 146.0 146.0 146.0 121.3 96.5 71.8 142.2 13.6 142.2 142.2 142.2 117.5 92.7 67.9 151.8 12.0 151.8 151.8 151.8 127.0 102.3 77.6 146.8 13.7 146.8 146.8 146.8 122.0 97.2 72.5 Johnson Controls Unitary Products...
  • Page 27 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 28 131.2 106.1 81.0 6250 152.7 11.7 152.7 152.7 152.7 127.7 102.8 77.8 144.3 13.2 144.3 144.3 144.3 119.2 94.1 69.0 155.6 11.7 155.6 155.6 155.6 130.6 105.6 80.6 147.8 13.3 147.8 147.8 147.8 122.7 97.6 72.5 Johnson Controls Unitary Products...
  • Page 29 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 30 154.3 126.5 98.6 7500 181.9 17.0 181.9 181.9 181.9 154.1 126.4 98.6 167.9 17.0 167.9 167.9 167.9 140.1 112.2 84.4 182.2 17.0 182.2 182.2 182.2 154.4 126.7 99.0 169.0 17.0 169.0 169.0 169.0 141.2 113.4 85.6 Johnson Controls Unitary Products...
  • Page 31 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 32 150.7 121.5 92.3 7500 176.0 13.9 176.0 176.0 176.0 146.8 117.6 88.4 171.5 15.7 171.5 171.5 171.5 142.3 113.1 84.0 177.0 13.9 177.0 177.0 177.0 147.8 118.6 89.5 174.2 15.6 174.2 174.2 174.2 145.0 115.9 86.7 Johnson Controls Unitary Products...
  • Page 33 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 34 140.4 115.9 91.4 7500 171.7 13.8 171.7 171.7 171.7 147.1 122.6 98.1 169.5 15.5 169.5 169.5 169.5 145.0 120.5 96.1 173.0 13.8 173.0 173.0 173.0 148.4 123.9 99.4 168.6 15.4 168.6 168.6 168.6 144.1 119.7 95.2 Johnson Controls Unitary Products...
  • Page 35 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 36 208.3 205.8 172.6 138.3 104.0 10000 198.3 13.7 198.3 198.3 198.3 163.9 129.5 95.1 195.3 15.5 195.3 195.3 195.3 161.0 126.7 92.4 203.2 13.8 203.2 203.2 203.2 168.8 134.4 100.0 197.7 15.5 197.7 197.7 197.7 163.4 129.1 94.8 Johnson Controls Unitary Products...
  • Page 37 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 38 146.5 118.7 90.9 7500 172.9 13.7 172.9 172.9 172.9 145.4 118.0 90.6 162.9 15.5 162.9 162.9 162.9 135.1 107.3 79.5 178.0 13.8 178.0 178.0 178.0 150.5 123.1 95.6 166.7 15.4 166.7 166.7 166.7 138.8 111.0 83.2 Johnson Controls Unitary Products...
  • Page 39 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. 2. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 40 190.5 180.6 151.0 121.5 91.9 7500 175.9 13.9 175.9 175.9 175.9 146.3 116.8 87.2 171.2 15.5 171.2 171.2 171.2 141.6 112.0 82.4 176.8 13.9 176.8 176.8 176.8 147.2 117.6 88.0 173.5 15.5 173.5 173.5 173.5 143.9 114.3 84.7 Johnson Controls Unitary Products...
  • Page 41 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 42 184.0 148.9 113.9 10000 235.6 17.5 235.6 235.6 230.6 196.2 161.7 127.3 222.8 19.8 222.8 222.8 220.3 185.3 150.3 115.2 231.4 17.5 231.4 231.4 231.4 196.9 162.5 128.1 221.9 19.9 221.9 221.9 221.9 186.9 151.8 116.8 Johnson Controls Unitary Products...
  • Page 43 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 44 187.5 153.7 119.9 10000 235.3 17.3 235.3 235.3 232.8 199.0 165.2 131.4 242.2 19.8 242.2 242.2 237.0 203.2 169.4 135.6 235.1 17.3 235.1 235.1 235.1 201.3 167.5 133.7 231.8 19.7 231.8 231.8 231.8 198.0 164.3 130.5 Johnson Controls Unitary Products...
  • Page 45 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 46 184.0 148.2 112.3 10000 237.6 18.0 237.6 237.6 234.9 199.1 163.3 127.5 227.5 20.3 227.5 227.5 226.1 190.3 154.5 118.6 232.1 18.0 232.1 232.1 232.1 196.3 160.5 124.7 223.6 20.3 223.6 223.6 223.6 187.7 151.9 116.1 Johnson Controls Unitary Products...
  • Page 47 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 48 260.5 211.3 162.2 12500 311.8 24.7 311.8 311.8 311.8 263.3 214.7 166.2 289.5 27.4 289.5 289.5 289.5 240.4 191.2 142.1 314.6 24.5 314.6 314.6 314.6 266.1 217.6 169.0 297.6 27.2 297.6 297.6 297.6 248.5 199.3 150.2 Johnson Controls Unitary Products...
  • Page 49 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 50 23.1 10.2 25.6 27.9 YH-25 18.4 19.0 20.0 16.0 21.4 13.6 23.7 11.4 26.3 28.8 18.9 20.4 20.6 17.3 22.2 14.8 24.2 12.6 27.1 10.4 29.7 19.5 21.8 21.3 18.5 22.9 16.0 24.8 13.7 27.8 11.2 30.7 Johnson Controls Unitary Products...
  • Page 51 54.4 90.1 90.1 89.4 79.9 65.9 52.0 3750 89.8 89.8 89.8 89.8 75.9 62.0 48.1 84.4 84.4 84.4 84.4 70.4 56.4 42.4 90.4 90.4 90.4 90.4 76.5 62.6 48.7 84.4 84.4 84.4 84.4 70.5 56.5 42.5 Johnson Controls Unitary Products...
  • Page 52 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 53 118.0 115.5 101.5 82.6 63.8 5000 119.0 119.0 119.0 119.0 100.5 82.0 63.5 112.9 10.7 112.9 112.9 112.9 94.1 75.2 56.4 125.8 125.8 125.8 125.8 107.3 88.8 70.3 117.0 10.7 117.0 117.0 117.0 98.2 79.4 60.5 Johnson Controls Unitary Products...
  • Page 54 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 55 150.7 121.9 93.1 7500 174.3 14.4 174.3 174.3 174.3 145.5 116.7 87.9 161.5 16.2 161.5 161.5 161.5 132.7 103.9 75.1 179.2 14.5 179.2 179.2 179.2 150.4 121.6 92.8 166.8 16.2 166.8 166.8 166.8 138.1 109.3 80.5 Johnson Controls Unitary Products...
  • Page 56 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor Johnson Controls Unitary Products...
  • Page 57 147.1 118.3 89.6 7500 172.4 14.4 172.4 172.4 172.4 144.1 115.7 87.4 160.1 16.3 160.1 160.1 160.1 131.4 102.6 73.9 173.7 14.5 173.7 173.7 173.7 145.3 117.0 88.7 162.3 16.4 162.3 162.3 162.3 133.5 104.8 76.0 Johnson Controls Unitary Products...
  • Page 58 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 59 177.9 141.2 104.6 10000 231.2 18.6 231.2 231.2 227.3 190.8 154.2 117.6 216.8 20.8 216.8 216.8 214.9 178.2 141.5 104.8 236.4 18.7 236.4 236.4 232.5 195.9 159.3 122.7 223.9 21.0 223.9 223.9 220.6 183.9 147.2 110.5 Johnson Controls Unitary Products...
  • Page 60 Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products...
  • Page 61 These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh.  Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. Johnson Controls Unitary Products...
  • Page 62 These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh.  Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. Johnson Controls Unitary Products...
  • Page 63 These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh.  Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency. Johnson Controls Unitary Products...
  • Page 64 These capacities do not include any blower motor heat. Steam Coil Capacity Correction Factors For High Steam Pressure STEAM PRESSURE (PSIG) CAPACITY CORRECTION FACTOR 1.05 1.12 1.19 1.25 1.30 NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH Johnson Controls Unitary Products...
  • Page 65 1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications. 2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency. Johnson Controls Unitary Products...
  • Page 66 1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications. 2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency. Johnson Controls Unitary Products...
  • Page 67 1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications. 2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency. Johnson Controls Unitary Products...
  • Page 68 1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications. 2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency. Johnson Controls Unitary Products...
  • Page 69 4.2 - 5.2 0.875 AK84 1.000 48.3 Std. 56HZ 1VP50 565 - 721 3.6 - 4.6 0.875 AK114 11.0 1.000 45.3 NH/NJ-15 1725 1.15 184T 2VP50 707 - 894 3.7 - 4.7 1.125 2B5V94 1.000 41.8 Johnson Controls Unitary Products...
  • Page 70 Motors with Service Factor of 1.15 or Greater: Adjust overload relay dial to the motor nameplate Full Load Amps (FLA). Motors with Service Factor Less Than 1.15: Adjust overload relay dial based on the formula: Motor nameplate FLA x 0.90 = relay setting Johnson Controls Unitary Products...
  • Page 71 0.01 0.22 0.13 0.04 0.08 0.12 9500 0.00 0.23 0.00 0.04 0.08 0.13 9750 0.00 0.24 0.00 0.04 0.09 0.13 10000 0.00 0.25 0.00 0.04 0.09 0.14 Pressure drop added by condensate over a dry coil. Johnson Controls Unitary Products...
  • Page 72 As the altitude application at sea level. Air density correction factors are or temperature increases, the density of air decreases. In shown in Altitude Factors Table and Temperature Correction Figure. Johnson Controls Unitary Products...
  • Page 73 Corrected BHP = 4.0 x 0.832 = 3.328 Example 2: A system, located at 5,000 feet of elevation, is to BHP at 5,000 ft. = 3.2 x .832 = 2.66 deliver 6,000 CFM at a static pressure of 1.5". Use the unit Johnson Controls Unitary Products...
  • Page 74 Motor Blower 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully Unit Model Sheave Sheave Open Open Open Open Open Open Closed Std. 1.73 1VL40 AK69 2.30 1VL40 AK56 1062 1128 1194 Johnson Controls Unitary Products...
  • Page 75 Model (Tons) Rating 1000 2000 4000 8000 PH-07 (7.5) YH-07 PH-10 YH-10 (10.0) YJ-10 YH-12 (12.5) YJ-12 PH-15 PJ-15 (15.0) YH-15 YJ-15 PH-20 PJ-20 (20.0) YH-20 YJ-20 YH-25 (25.0) Rated in accordance with AHRI 270 Standard. Johnson Controls Unitary Products...
  • Page 76 Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C. Maximum fuse or maximum circuit breaker (HACR type per NEC). Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing. Johnson Controls Unitary Products...
  • Page 77 Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C. Maximum fuse or maximum circuit breaker (HACR type per NEC). Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing. Johnson Controls Unitary Products...
  • Page 78 Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C. Maximum fuse or maximum circuit breaker (HACR type per NEC). Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing. Johnson Controls Unitary Products...
  • Page 79 116.8 None 10 KW 12.0 19.3 460-3-60 16 KW 19.2 28.3 26 KW 31.3 43.3 36 KW 43.3 58.4 None 10 KW 15.0 575-3-60 16 KW 15.4 22.2 26 KW 25.0 34.3 36 KW 34.6 46.3 Johnson Controls Unitary Products...
  • Page 80 19.2 32.8 460-3-60 26 KW 31.3 47.8 36 KW 43.3 62.9 50 KW 60.1 68.9 None 10 KW 18.5 16 KW 15.4 25.7 575-3-60 26 KW 25.0 37.8 36 KW 34.6 49.8 50 KW 48.1 54.6 Johnson Controls Unitary Products...
  • Page 81 None 28.0 460-3-60 11.0 None 14.0 575-3-60 None Minimum Circuit Ampacity. Dual Element, Time Delay Type. HACR type per NEC. (NC/ND)180C00D Models Only Motors are not shipped with these models. Motor and Drive Kits are required. Johnson Controls Unitary Products...
  • Page 82 505430-BTG-P-0316 Typical Wiring Diagrams Air Conditioning Condensing Units Typical YH-07 Wiring Diagram Johnson Controls Unitary Products...
  • Page 83 505430-BTG-P-0316 Typical YH-10 thru -12 Wiring Diagram Johnson Controls Unitary Products...
  • Page 84 505430-BTG-P-0316 Typical YJ-10 thru -12 Wiring Diagram Johnson Controls Unitary Products...
  • Page 85 505430-BTG-P-0316 Typical YH-15 Wiring Diagram Johnson Controls Unitary Products...
  • Page 86 505430-BTG-P-0316 Typical YH-20 Wiring Diagram Johnson Controls Unitary Products...
  • Page 87 505430-BTG-P-0316 Typical YH-25 Wiring Diagram Johnson Controls Unitary Products...
  • Page 88 505430-BTG-P-0316 Typical YJ-25 Wiring Diagram Johnson Controls Unitary Products...
  • Page 89 505430-BTG-P-0316 Typical YJ-15 thru -20 Wiring Diagram Johnson Controls Unitary Products...
  • Page 90 505430-BTG-P-0316 Heat Pump Units Typical PH-07 Wiring Diagram Johnson Controls Unitary Products...
  • Page 91 505430-BTG-P-0316 Typical PH-10 Wiring Diagram Johnson Controls Unitary Products...
  • Page 92 505430-BTG-P-0316 Typical PH-15 thru -20 Wiring Diagram Johnson Controls Unitary Products...
  • Page 93 505430-BTG-P-0316 Typical PH-20 Wiring Diagram Johnson Controls Unitary Products...
  • Page 94 505430-BTG-P-0316 Typical PJ-15 thru -20 Wiring Diagram Johnson Controls Unitary Products...
  • Page 95 505430-BTG-P-0316 Air Handling Units Typical NH-07 Wiring Diagram Johnson Controls Unitary Products...
  • Page 96 505430-BTG-P-0316 Typical NH-10 thru -20, 1.5 thru 5 HP Blower Motor Only Wiring Diagram Johnson Controls Unitary Products...
  • Page 97 505430-BTG-P-0316 Typical NH-20, 7.5 HP Blower Motor 208/230 V Only Wiring Diagram Johnson Controls Unitary Products...
  • Page 98 505430-BTG-P-0316 Typical NH-20, 7.5 HP Blower Motor 460/575 V Only Wiring Diagram Johnson Controls Unitary Products...
  • Page 99 505430-BTG-P-0316 Typical NH-25 Wiring Diagram Johnson Controls Unitary Products...
  • Page 100 505430-BTG-P-0316 Typical NJ-20, 1.5 Thru 5 HP Blower Motor Only Wiring Diagram Johnson Controls Unitary Products...
  • Page 101 505430-BTG-P-0316 Typical NJ-20, 7.5 HP Blower Motor 208/230 V Only Wiring Diagram Johnson Controls Unitary Products...
  • Page 102 505430-BTG-P-0316 Typical NJ-20, 7.5 HP Blower Motor 460/575 V Only Wiring Diagram Johnson Controls Unitary Products...
  • Page 103 DIM Y LENGTH RIGHT PC090, PC120, DIM Y YC090, YC120, YD120, YC150, YD150 LENGTH RIGHT PC180, PD180, PC240, PD240, YC180, YD180, YC240, YD240, YC300 NOTE: Front of unit is considered the side having the unit control box. Johnson Controls Unitary Products...
  • Page 104 10.000 4.875 6.26 4.132 7.52 2.382 8.98 REAR LEFT 1.882 10.60 Unit Dimensions PH-07, PH-10, YH-07, YH/YJ-10, YH/YJ-12 Unit Height Dimensions MODEL PH-07 44.5 PH-10 50.0 YH-07 44.5 YH-10 50.0 YJ-10 50.0 YH-12 50.0 YJ-12 50.0 Johnson Controls Unitary Products...
  • Page 105 7.000 23.000 7.000 23.000 7.000 7.000 3.913 37.000 2.923 37.000 3.181 64.000 1.913 59.000 3.563 FRONT RIGHT SYSTEM 2 SYSTEM 1 16.133 13.133 17.367 18.867 20.617 22.617 FRONT (PIPING DETAIL) Unit Dimensions PH/PJ-15, PH/PJ-20, YH/YJ-15, YH/YJ-20 Johnson Controls Unitary Products...
  • Page 106 Electrical connections for power and control wiring are made from the front of the units, right or left of 7.5 thru 12.5 Ton electrical control box access or left of the electrical control box access on 15 thru 20 Ton units. See Unit Dimensions and Piping and Electrical Connection Sizes tables for piping sizes and electrical knockout details. Johnson Controls Unitary Products...
  • Page 107 1 1/8 1 5/8 1 3/8 2 1/8 Liquid Line OD (in.) Power Wiring Knockout 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 Control Wiring Knockout Johnson Controls Unitary Products...
  • Page 108 High Static Mtr. and Drv. 30.6 42.4 126 130 133 176 171 167 LEFT LEFT WIDTH WIDTH FRONT REAR FRONT REAR DIM Y DIM Y DIM X DIM X LENGTH RIGHT LENGTH HORIZONTAL POSITION RIGHT VERTICAL POSITION Johnson Controls Unitary Products...
  • Page 109 220 204 180 160 172 194 NH-25 137.8 1067 1157 35.4 45.1 225 210 185 164 176 198 D (E) (D) C D (E) (D) C A (A) (B) B A (A) (B) B Horizontal Vertical Johnson Controls Unitary Products...
  • Page 110 SYSTEM 1 13.13 10.73 2.000 DRAIN 3/4” ABS 1.88 PIPE CONNECTION 52.000 2.000 7.12 56.000 30.00 FRONT VIEW - RETURN AIR RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS NH-07/-10 & NJ-10 INDOOR Unit Dimensions NH-07/-10 and NJ-10 Johnson Controls Unitary Products...
  • Page 111 505430-BTG-P-0316 BOTTOM VIEW 2.72 50.75 2.72 2.66 AIR IN 11.43 30.00 HORIZONTAL CONFIGURATION 30.00 35.00 30.00 60.00 Unit Dimensions NH-07/-10 and NJ-10 (Continued) Johnson Controls Unitary Products...
  • Page 112 SYSTEM 2 17.85 15.50 SYSTEM 1 13.13 10.73 2.00 DRAIN 3/4” ABS 1.88 70.50 2.00 PIPE CONNECTION 7.12 74.50 33.00 FRONT VIEW - RETURN AIR RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS NH/NJ-15 INDOOR Unit Dimensions NH/NJ-15 Johnson Controls Unitary Products...
  • Page 113 505430-BTG-P-0316 BOTTOM VIEW 74.50 2.72 69.25 2.72 2.66 AIR IN 14.43 33.00 HORIZONTAL CONFIGURATION 33.000 42.000 33.000 66.000 Unit Dimensions NH/NJ-15 (Continued) Johnson Controls Unitary Products...
  • Page 114 19.19 15.50 SYSTEM 1 13.13 10.73 2.56 1.88 7.12 3.56 44.91 DRAIN 3/4” ABS PIPE CONNECTION 2.56 93.37 98.50 30.00 FRONT VIEW - RETURN AIR RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS NH/NJ-20 INDOOR Unit Dimensions NH/NJ-20 Johnson Controls Unitary Products...
  • Page 115 505430-BTG-P-0316 BOTTOM VIEW 98.50 2.72 45.38 50.59 45.38 2.72 2.66 AIR IN AIR IN 11.43 30.00 HORIZONTAL CONFIGURATION 30.00 35.00 30.00 60.00 Unit Dimensions NH/NJ-20 (Continued) Johnson Controls Unitary Products...
  • Page 116 505430-BTG-P-0316 BLOWER EVAPORATOR POSITION POSITION POSITION POSITION COIL POSITION POSITION POSITION POSITION Vertical Airflow Arrangements NH-07 thru -20 and NJ-10 thru -20 Johnson Controls Unitary Products...
  • Page 117 505430-BTG-P-0316 POSITION POSITION POSITION POSITION POSITION POSITION POSITION POSITION Horizontal Airflow Arrangements NH-07 thru -20 and NJ-10 thru -20 Johnson Controls Unitary Products...
  • Page 118 33.22 Ø 2.13 SUCTION CONNECTION Ø 1.38 KO 24.98 Ø 0.88 DRAIN CONNECTION 7.64 3.53 2.36 3.37 46.97 0.63 4.08 95.59 4.22 100.13 38.06 FRONT (RETURN AIR) VIEW RIGHT SIDE (SERVICE CONNECTION) VIEW Unit Dimensions NH-25 Johnson Controls Unitary Products...
  • Page 119 505430-BTG-P-0316 HORIZONTAL CONFIGURATION RETURN SUPPLY 73.3 74.0 Unit Dimensions NH-25 (Continued) BLOWER EVAPORATOR COIL Vertical Airflow Arrangements NH-25 NOTE: *If required, some air can be returned through the bottom of the evaporator section Johnson Controls Unitary Products...
  • Page 120 This dimension is required for normal installation and service. Although no clearance is required for service and operation, some clearance may be required for routing the power and control wiring. Johnson Controls Unitary Products...
  • Page 121 Allow enough clearance to trap the condensate drain line. Note: If the coil has to be removed, the blower section can be unbolted and set aside and the coil can be lifted out the top of the evaporator section. Johnson Controls Unitary Products...
  • Page 122 All END VIEW MOUNTING DETAIL All Thread Steel Rod Mounting Bracket Flat Washer / Lock Washer and Nut Steel C- channel SIDE VIEW Typical Suspension of AHU’s From Ceiling Johnson Controls Unitary Products...
  • Page 123 After these bottom channels are cut per Note 1, a new hole will have to be drilled at the cut end if the unit is to be mounted on isolators. Typical Suspension of NH-25 Unit Mounting Dimensions- NH-25 DIMENSIONS, INCHES UNIT 69-1/4 49-1/16 26-5/8 NH-25 Johnson Controls Unitary Products...
  • Page 124 G W1 W2 THERMOSTAT SINGLE STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on 7.5 Ton Single Stage Units. Typical Field Wiring Diagram - NH-07 Evaporator Unit with PH-07 Heat Pump Johnson Controls Unitary Products...
  • Page 125 Typical Field Wiring Diagram - NH-10 thru NH-20 Evaporator Unit with PH-10 thru PH-20 Heat Pump VALVE SYS 2 218 / BR 1LLS 219 / Y NH-10 thru -20 Liquid Line Solenoid Wiring Johnson Controls Unitary Products...
  • Page 126 TWO STAGE COOLING TWO STAGE HEATING NOTE: Liquid line solenoid is not included or required on any 4 pipe units. Typical Field Wiring Diagram - NJ-15 thru NJ-20 Evaporator Unit with PJ-15 thru PJ-20 Heat Pump Johnson Controls Unitary Products...
  • Page 127 7.5 Ton Single Stage Units. Typical Field Wiring Diagram - NH-07 Evaporator Unit with YH-07 Condenser Unit NOTE: On non NH/NJ Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit. Johnson Controls Unitary Products...
  • Page 128 NOTE: Liquid line solenoid is only activated during second stage cooling operation. Typical Field Wiring Diagram - NH-10 thru NH-20 Evaporator Unit with YH-10 thru YH-20 Condenser Unit NOTE: On non NH/NJ Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
  • Page 129 Typical Field Wiring Diagram - NH-25 Evaporator Unit with YH-25 Condenser Unit NOTE: On non NH/NJ Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit. NH-25 Liquid Line Solenoid Wiring Subject to change without notice. Printed in U.S.A. 505430-BTG-P-0316 Copyright ©...
  • Page 130 Typical Field Wiring Diagram - NJ-10 thru NJ-20 Evaporator Unit with YJ-10 thru YJ-20 Condenser Unit NOTE: On non NH/NJ Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit. Johnson Controls Unitary Products...
  • Page 131 NOTE: On non NH/NJ Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit. VALVE SYS 2 218 / BR 1LLS 219 / Y NH-10 thru -20 Liquid Line Solenoid Wiring Johnson Controls Unitary Products...
  • Page 132 505430-BTG-P-0316 NOTE: Refer to Evaporator unit wiring diagram for control of liquid line solenoid valve. Johnson Controls Unitary Products...
  • Page 133 SINGLE STAGE HEATING Typical Field Wiring Diagram - Single 4-Pipe Evaporator Unit with Twin Condenser Units NOTE: On non NH/NJ Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit. Johnson Controls Unitary Products...
  • Page 134 TWO STAGE HEATING Typical Field Wiring Diagram - Twin NH-07 Evaporator Units with 4-Pipe Condenser Unit NOTE: On non NH/NJ Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit. Johnson Controls Unitary Products...