Download Print this page

VAC V100 Troubleshooting Manual

Positioner

Advertisement

Quick Links

Trouble Shooting Guide for V100 Positioner
1) 1.V100 not responding to input signal
a) The tubing to the actuator may be
incorrect
i)
Plant Air Supply should be ported to
the Sport on the side of the
positioner. Supply must be
greater than 30 PSI.
ii) The pneumatic control signal
(3 to 15 psi) should be ported to
the Ip port on the side of the
positioner.
If the positioner is a V100E, using
an I/P on the positioner, the Ip
port should be plugged tightly!! Double check once plug is in place to make sure
there is no air leakage from Ip plug.
iii) The driving port of this positioner is the C+ port. In other words, on an
increasing control signal the supply is directed through the positioner to the
C+ port. This is very important – not only for single acting
or spring assist valve packages, but also to insure proper
air to open (or close) operation (rotation).
b) I/P wiring
i)
Make sure the unit is properly wired.
(1) The positive terminal (+) MUST have a positive
voltage to it.
(2)The negative terminal (-) MUST have a negative voltage to it.
c) I/P operation
i)
If the I/P has been in use the potential for contaminated air
supply exist – check the I/P by either of the following steps.
(1) Install a gauge on the I/P gauge port (1/8 inch NPT) to make
sure that the I/P is generating a 3 to 15 psi pneumatic output in correlation to
the 4 to 20 mA input signal.
(2) Using an ohm meter check to make sure that there is resistance still in the
loop. A good unit will put out 240 Ω or more.

Advertisement

loading

Summary of Contents for VAC V100

  • Page 1 Trouble Shooting Guide for V100 Positioner 1) 1.V100 not responding to input signal a) The tubing to the actuator may be incorrect Plant Air Supply should be ported to the Sport on the side of the positioner. Supply must be greater than 30 PSI.
  • Page 2 d) Cam If cam nut and locking screw are not correctly inserted the positioner will not work correctly, generally resulting in the cam slipping and a small input change will equal a full stroking of the actuator. Make sure that the locking screw is all the way out before you tighten the cam nut;...
  • Page 3 (a) If there are doubts on which spool valve to order call our service center at 205.678.0507 (b) Replace standard spool valve with the Low Gain spool valve. VAC will do an exchange at no cost.
  • Page 4 Reversing a positioners action A common question that Valve Accessories & Controls often gets from the field is that a customer has a valve package with our positioner however they wish to reverse the input signal and action of the valve. For example a customer has a valve that is closed at 4mA and open at 20mA. The below diagrams are 4mA closed and 20mA open.
  • Page 5 1. The tubing must be reversed. C+ tube must now go to C- and C- must go to C+. So for double acting actuators you do exactly that, just reverse the tubing, for single acting, C+ would now be plugged and C- would now be piped to the actuator. 2.