2.11.6 Thermal Overload Element THR
Thermal overload element THR has a characteristic based on thermal replica according to IEC
60255-8 standards (see Appendix N), which evaluates the phase current (A-phase) of CT
secondary circuits. Figure 2.11.4 shows the characteristic of THR element. The element has trip
and alarm stages.
Trip stage:
I
2
t = Ln
(k I
I
2
Alarm stage:
Ip
(I
2
t = Ln
where
t :
operating time
:
thermal time constant
I :
load current
kI B : allowable overload current as specified in IEC 60255-8 (refer to Appendix N)
I B : basic current of transformer (rated current)
k : constant (allowable overload current / I B )
Ip : prior load current before the overload occurs
T A : time for alarm
(Alarming time = t (operating time) T A (setting time))
Ln : natural logarithm
Figure 2.11.5 shows the thermal curve for a range of time constant settings under cold state when
the prior load current Ip is zero.
Figure 2.11.4 Characteristic of Thermal Overload Element
Ip
2
)
2
B
) (1 T A /)
2
(k I
I
2
)
2
B
t
K I B
0
42
T A
Trip
Alarm
T A
I