7. Putting Relay into Service

The following procedure must be adhered to when putting the relay into service after finishing
commissioning or maintenance tests.
 Check that all external connections are correct.
 Check the setting of all measuring elements, timers, scheme switches, recordings and clock
are correct.
In particular, when settings are changed temporarily for testing, be sure to restore them.
 Clear any unnecessary records on faults, events and disturbances which are recorded during
the tests.
 Press the VIEW key and check that no failure message is displayed on the
"Auto-supervision" screen.
 Check that the green "IN SERVICE" LED is lit and no other LEDs are lit on the front panel.
 140 
6 F 2 S 0 7 8 9