Eurapo Sigma SV Technical Manual

Eurapo Sigma SV Technical Manual

Fancoil units
Table of Contents

Advertisement

EN
TECHNICAL MANUAL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Sigma SV and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eurapo Sigma SV

  • Page 1 TECHNICAL MANUAL...
  • Page 3: Table Of Contents

    INDEX 1. GENERAL INFORMATION 5.15.1 AFT – Anti-frost function ..........26 5.15.2 AFT – In combination with electric heater ..26 1.1 Applications ................4 5.16 PC – Condensate pump ..........26 1.2 Operation ...................4 1.3 Performances ................4 6. REGULATING VALVES 1.4 Operating limits .................4 1.5 Product range ................5 6.1 H3A2 –...
  • Page 4: General Information

    1. GENERAL INFORMATION 1.1 APPLICATIONS Fan coils are used to directly treat the air in the room where they are installed. They can be used both for heating and cooling applications; in the latter case, the air is also dehumidified. 1.2 OPERATION The effectiveness of a fan coil is due to the large surface area of the finned heat exchanger (coil) where the air drawn from the room by the fan passes through.
  • Page 5: Product Range

    To facilitate choosing the correct size of a fan coil for any operating condition (including those differing from the standard ones), EURAPO offers a dedicated computer program which can be downloaded from the ftp address http://ftp.eurapo.it/ and can be updated with automatic upload through internet.
  • Page 6: Exploded View Sv And Sh/Af

    SV MODEL LEGEND Internal structure Fan deck Electric motor Scroll and impeller Autotransformer Capacitor Electric panel Standard coil (2, 3 or 4 rows) Additional coil 10. Condensate tray 11. Auxiliary drain pan (vertical) 12. Water discharge plastic pipe 13. Grilles 14.
  • Page 7: Exploded View Pv And Ch

    PV MODEL LEGEND Internal structure Fan deck Electric motor Scroll and impeller Autotransformer Capacitor Electric panel Standard coil (2 or 3 rows) Additional coil 10. Condensate tray 11. Auxiliary drain pan (vertical) 12. Water discharge plastic pipe 13. Grilles 14. Housing 15.
  • Page 8: Models With Cabinet

    2. MODELS WITH CABINET 2.1 SIGMA SERIE: SV – SV/AF MODELS SV MODEL Vertical units with upper air outlet and bottom (SV) or frontal (SV/AF) air intake, to be installed on the wall (SV) or on the floor (both models, but with a set of feet in white RAL 9003 for SV model).
  • Page 9 SV - SH Dimensions and weights SH/AF MODEL Size 218 220 222 224 226 328 898 1023 1148 1273 1273 1523 1523 1773 999 1249 1249 1499 409 409 409 409 409 Ø SV/AF - SH/AF Dimensions and weights Size 218 220 222 224 226 328 898 1023 1148 1273 1273 1523 1523 1773 999 1249 1249 1499...
  • Page 10: Prisma Serie: Pv-Pv/Af Models

    2.3 PRISMA SERIE: PV – PV/AF MODELS PV/AF MODEL Vertical units with upper air outlet and bottom (PV) or frontal (PV/AF) air intake, to be installed on the wall (PV) or on the floor (both models, but with a set of feet in white RAL 9003 for PV model).
  • Page 11 PV - PH Dimensions and weights PH/AF MODEL Size 1023 1148 Ø PV /AF - PH/AF Dimensions and weights Size 1023 1148 Ø...
  • Page 12: Low Body Serie: Svr Model

    2.5 LOW BODY SERIE: SVR MODEL Vertical unit in a reduced height (430 mm) with upper air outlet and frontal air intake, to be installed on the floor. • grilles can be adjusted in all four directions and are made of heat-resistant ABS •...
  • Page 13: Suggested Installation

    2.6 SUGGESTED INSTALLATION SH/AF PAE/HAF PAE/HAF SV/AF SV/AF...
  • Page 14: Models Without Cabinet

    3. MODELS WITHOUT CABINET 3.1 CONCEALED SERIE: CV – CV/AF MODELS CV MODEL Vertical units for concealed installation with upper air outlet and bottom (CV) or frontal (CV/AF) air intake. • models equipped with auxiliary drain pan • 2 pipe systems: 2, 3 or 4 row coils; in all units an electric heater can also be mounted •...
  • Page 15 CH - CH/AF Dimensions and weights CH MODEL Size 949 1074 1199 1199 1449 1449 1699 999 1249 1249 1499 974 1224 1224 1474 409 409 409 409 409 Ø ø CV - CV/AF Dimensions and weights Size 930 1055 1180 1180 1430 1430 1680 999 1249 1249 1499 974 1224 1224 1474 409 409 409 409 409...
  • Page 16: Low Body Serie: Cvr Model

    3.3 LOW BODY SERIE: CVR MODEL Vertical unit in a reduced height (395 mm) for concealed installation, with upper air outlet and frontal air intake. • model equipped with auxiliary drain pan • 2 pipe systems: 2 or 3 row coils; on 2 row coil units an electric heater can also be mounted •...
  • Page 17: Suggested Installation

    3.4 SUGGESTED INSTALLATION PAE/HM CH/AF CH/AF PM 90° PAE/V...
  • Page 18: Components

    4. COMPONENTS 4.1 INNER FRAME The inner frame consists of 2 sides and a back panel assembled together, and of a movable element (condensate tray). It is made of galvanised steel: 8/10 mm thick for models up to size 218, 10/10 mm thick starting from size 220. The sides have a special structure near the coil connections in order to avoid the headers’...
  • Page 19: Electrical Components And Controls

    removed, independently of the inner frame, by taking off two fixing screws. It consists of a centrifugal fan, one (110÷114 sizes), two (216÷226 sizes) or three (328) aluminium impellers, directly splined to the motor shaft, and of galvanized steel scrolls. All motors operate at 50/60Hz. 4.4 ELECTRICAL COMPONENTS AND CONTROLS The electric panel (CBL00) consists of a self-extinguishing plastic box (class V0), which contains a 12 pole terminal board.
  • Page 20: Electrical Accessories

    5. ELECTRICAL ACCESORIES 5.1 ELECTRIC BOX CBL10 Self-extinguishing plastic box (class V0), which contains a 12 pole terminal board and a voltage transformer (230/24 V~ 10 VA), for the electrical connection of the modulating valves. It is supplied as standard when the regulators CER10/B e CER30/B are requested.
  • Page 21: Fan Speed Selectors Csl - Csr

    CSL00 CSR00 Manual fan speed selector + OFF position • • Manual speed selector • • BUILT-IN REMOTE Compatibility Ref. EURAPO CSL00 CSR00 2 pipe system only • • Minimum water temp. thermostat • • Remote room thermostat TAD10 •...
  • Page 22: Electronic Regulators Cel - Cer

    NTC sensor for automatic S/W changeover • • • • • • • • (2 pipe system only) Electric heater (in alternative to the heating valve) • • • • KREL For more information please refer to the TECHNICAL MANUAL FOR EURAPO CONTROLLERS.
  • Page 23: Omnibus Digital Control

    5.9 OMNIBUS DIGITAL CONTROL The OMNIBUS digital control system permits a complete and integrated management of several fancoil units installed in the same building. It is designed either for a stand-alone operating mode, or to be integrated, at different levels, to a centralized Building Automation System, with a serial communication protocol RS-485 (Modbus RTU).
  • Page 24: Analogue Plus Console - Oc736

    5.9.3 ANALOGUE PLUS CONSOLE – OC736 The Console is connected to the Power Omnibus card by a phone cable (4 wires), from which it is energized (15 Vcc) and it receives information from the Local-bus network. The Analogue Plus Console is composed by: •...
  • Page 25: Onet - Ocb50 Webserver

    5.10.3 ONET – OCB50 WEBSERVER (up to 480 units) • Modbus/RTU protocol • Different access levels (user/supervisor/service) • Centralized operation • Set-up parameters configuration • INPUT/OUTPUT status monitoring • Daily, weekly and special events program • Alarms management • Suitable for connecting up to 2 lines of 240 units each •...
  • Page 26: As - Air Sensor

    5.13 AS – AIR SENSOR 1m long NTC sensor (10K, 25°C), to be installed on the fancoil unit’s air intake. It is supplied as standard with the following regulators: CML00, CEL00, CEL10/B, CEL20, CEL30/B and CEL31. It is optional, on request, with the following regulators: CMR00, CER00, CER10/B, CER20, CER30/B and CER31. 5.14 CS –...
  • Page 27: Regulating Valves

    6. REGULATING VALVES 6.1 ON/OFF VALVES: 3-WAY WITH 4 WATER CONNECTIONS (H3A2-H3B2) OR 2-WAY (H2A2- H2B2), 1/2”-3/4”, 230V, FOR 2 OR 4 PIPE SYSTEMS The ON/OFF 3-way regulating valves with bypass and 2-way regulating valves are provided with thermoelectric actuator and connection tubes.
  • Page 28: Dt - Shut-Off Valves

    MAXIMUM OPERATING PRESSURE WITH VALVES: 10 BAR. PRESSURE DROP DIAGRAM FOR VALVES Kvs=1,6 Kvs=1,7 Kvs=2,5 Kvs=2,6 Water flow [l/h] Pressure drop diagram referred to the body valve only. In order to choose the correct type of valve it is necessary to know the system’s technical specifications. For this reason the consultant has full responsibility for the correct choice of the valve.
  • Page 29: Four-Pipe Compact Kit

    6.4 FOUR-PIPE COMPACT KIT Four-pipe Compact Kit is made by two 3-way valves and two actuators On/Off 230V or 24V (IP43) or 2 modulating actuators 24V (IP43). The kit enables, in a four pipe system, to use the main coil (3 or 4 row coil) both for cooling and for heating operation. It is suitable for fan coil size 110÷328.
  • Page 30: Other Accessories

    7. OTHER ACCESSORIES 7.1 CP – SET OF FEET Set of painted steel feet, each of them composed by two elements: a bearing element fixed to the inner frame, on which the unit leans, and a visible element fixed to the previous one. They are designed to cover the water connections and the electric cables.
  • Page 31: Pae/H - Horizontal External Air Intake With Manual Damper

    7.7 PAE/H – HORIZONTAL EXTERNAL AIR INTAKE WITH MANUAL DAMPER Air suction plenum made of galvanized steel sheet, provided with a rectangular collar for the connection to the external air intake. It is mounted on the air intake of the unit, between the external air intake and the filter, which remains accessible for maintenance.
  • Page 32: Pm - Air Delivery Plenum

    7.10 PM – AIR DELIVERY PLENUM The air delivery plenum is made of galvanized steel sheet, insulated inside, provided with spigots for the connection to the air ducts. It is mounted on the air outlet of the unit. SIZE No. of spigots Spigots’...
  • Page 33: Pas - Air Suction Plenum With Spigots

    7.13 PAS – AIR SUCTION PLENUM WITH SPIGOTS Air suction plenum made of galvanized steel sheet, provided with collars (spigots) for the connection to the external air intake. It is mounted on the air intake of the unit, between the external air intake and the filter, which remains accessible for maintenance.
  • Page 34: Rccmf - Telescopic Air Outlet Connection

    7.16 RCCMF – TELESCOPIC AIR OUTLET CONNECTION The telescopic connection is made of galvanized steel sheet. It is mounted on the air outlet of the unit. See drawing and tables. 7.17 RCCAF – 90° TELESCOPIC AIR INTAKE CONNECTION The 90° telescopic air intake connection is made of galvanized steel sheet, it is complete with G3 filter. It is mounted on the air intake of the unit.
  • Page 35: Technical Data

    8. TECHNICAL DATA 8.1 AIR VOLUMES 8.1.1 SIGMA, PRISMA, CONCEALED SERIE Nominal values (m SIZE Fan speed 1 1038 1308 1579 1771 2351 Fan speed 2 MAX 1081 1254 1481 2068 Fan speed 3 MED 1116 1352 1725 Fan speed Fan speed 4 1152 1340...
  • Page 36 Values with external static pressure (m Pressure drop (Pa) Fan speed 1 Fan speed 2 MAX Fan speed 3 MED Size 110 Fan speed 4 Fan speed 5 MIN Fan speed 6 Fan speed 1 Fan speed 2 MAX Fan speed 3 MED Size 112 Fan speed 4 Fan speed 5 MIN...
  • Page 37: Low Body Serie

    8.1.2 LOW BODY SERIE Nominal values (m SIZE Fan speed 1 Fan speed 2 MAX Fan speed 3 MED Fan speed Fan speed 4 Fan speed 5 MIN Fan speed 6 Nominal air volumes refer to standard fan coils with clean air filter, 20 °C room temperature, at sea level, without external static pressure.
  • Page 38: Cooling Capacities

    8.2 COOLING CAPACITIES 8.2.1 SIGMA, PRISMA, CONCEALED SERIE Room temperature: 27 °C D.B. - 48% Humid. IN Water temperature: 7/12 °C SIZE 2 ROWS Total cooling capacities 1,17 1,27 2,17 3,07 3,15 3,79 4,41 6,03 6,57 8,23 Sensible cooling capacities 0,87 1,26 1,76...
  • Page 39: Total Cooling Capacities Kw

    Room temperature: 27 °C D.B. - 48% Humid. IN Water temperature: 7/12 °C SIZE 4 ROWS Total cooling capacities 1,40 2,03 3,39 4,10 4,60 5,75 6,72 9,50 9,97 12,72 Sensible cooling capacities 1,21 1,67 2,22 3,17 3,65 4,61 5,60 7,30 7,85 10,32 Fan speed 1...
  • Page 40: Low Body Serie

    8.2.2 LOW BODY SERIE Room temperature: 27 °C D.B. - 48% Humid. IN Water temperature: 7/12 °C SIZE 2 ROWS Total cooling capacities 0,83 1,02 1,44 2,18 2,66 Sensible cooling capacities 0,76 0,94 1,35 2,00 2,30 Fan speed 1 Water flow Water pressure drop 14,1 Total cooling capacities...
  • Page 41: Heating Capacities

    8.3 HEATING CAPACITIES 8.3.1 SIGMA, PRISMA, CONCEALED SERIE Room temperature: 20 °C Water temperature: 70/60 °C SIZE 2 ROWS Heating capacities 2,49 3,27 5,11 6,43 7,41 10,18 11,92 14,62 16,01 18,87 Fan speed 1 Water flow 1199 1306 1615 Water pressure drop 21,3 10,2 27,2...
  • Page 42: Fan Speed 2 Max

    Room temperature: 20 °C Water temperature: 70/60 °C SIZE 4 ROWS Heating capacities 3,55 5,39 6,06 7,74 10,14 14,46 17,75 21,18 22,39 27,55 Fan speed 1 Water flow 1071 1261 1791 1886 2358 Water pressure drop 46,2 11,3 11,3 10,0 13,3 23,1 16,2...
  • Page 43: Low Body Serie

    8.3.2 LOW BODY SERIE Room temperature: 20 °C Water temperature: 70/60 °C SIZE 2 ROWS Heating capacities 2,31 2,83 3,84 5,18 6,19 Fan speed 1 Water flow Water pressure drop 12,0 16,0 Heating capacities 1,80 2,62 3,48 4,88 5,68 Fan speed 2 MAX Water flow Water pressure drop 13,3...
  • Page 44: Electrical Data

    Room temperature: 20 °C Water temperature: 70/60 °C SIZE 1 ROW Heating capacities 1,39 1,91 2,54 3,59 4,25 Fan speed 1 Water flow Water pressure drop 11,1 21,4 Heating capacities 1,26 1,83 2,39 3,42 3,96 Fan speed 2 MAX Water flow Water pressure drop 18,6 Heating capacities...
  • Page 45: Noise Levels

    The following values indicate the sound pressure emitted by the fan coils. By using the EURAPO software for selection it is possible to calculate the new sound pressure level obtained by changing the parameters: room volume, distance from the noise source and reverberation time.
  • Page 46 Sound power level Sound pressure in a closed environment dB (A) dB (A) Fan speed 1 Fan speed 1 Fan speed 2 MAX (Eurovent) Fan speed 2 MAX Fan speed 3 MED (Eurovent) Fan speed 3 MED Size 110 Size 110 Fan speed 4 Fan speed 4 Fan speed 5 MIN (Eurovent)
  • Page 47: Electrical Connections

    10. ELECTRICAL CONNECTIONS The following wiring diagrams are the most frequently used for fancoil applications: CBL00 CBL00 – EVC – EVH...
  • Page 48 CBL10 – EVCM – EVHM CBL20 – EVC – EVH – MASTER/SLAVE...
  • Page 49 CBL20 – RE CBL30 – EVCM – EVHM...
  • Page 50 CBL00 – EV – PC CBL00 – EVC – EVH – PC...
  • Page 51 Safety thermostat with automatic resetting Phase CBL00 terminal board Room thermostat Regulating valve: EVC for cooling; EVH for heating Summer/Winter switch NOTE. If other configurations are required, different from the standard ones, please refer to the instruction manual of every specific EURAPO regulator.
  • Page 52 Eurapo Srl Via A. Malignani, 12 33170 Pordenone - Italy T +39 0434 572552 F +39 0434 28667 info@eurapo.it www.eurapo.it As programs and technologies are always improving, description, data and drawings must be intended as merely indicative and can be modified www.eurovent-certification.com...