SR700 SRHRV Fan TP600 Single Room Heat Recovery Ventilation Fan Unit SRC1 Controller TP590 Single Room Heat Recovery Ventilation Controller Unit Product Installation Manual ventilation systems...
Controller Unit is suitable for 220-240V ~ 50-60Hz single phase with a fuse rating of 3A. 7. Control & communication cable - Titon recommends the use of unshielded CAT5e cable to comply with EMC directives. 8. Control & communication cables should not be placed within 50mm or on the same metal cable tray as any mains lighting or power cables.
The system provides an easily installed and maintainable solution for removing internal condensation and eliminating mould growth within the home. Unlike regular extractor fans that waste 100% of heat that passes through them from the home, the SR700 system will recover up to 94%, based on in house testing, of wasted heat.
Inspect the units when taking delivery. Check the units for damage and that all accessories have been supplied. SR700 Fan Unit Package supplied with: SR700 Fan unit x 1; Product Installation Manual x 1. Any shortages or damage must be immediately reported to the supplier.
Installation Component Diffuser Bezel Wiring Aperture Cover Spring Steel Clip Air Filter Component Heat Cell Fan with Connectors Vent Tube Foam Strip Seal positions (not supplied) Foam Fly Screen External Louvre SRHRV Fan Unit ‑Components...
SRHRV Fan Unit Read and observe the guidance & safety notices listed in Warnings, Safety Information and Guidance . The Titon SRHRV Fan unit is designed to be mounted through a wall with a thickness between 305mm & 700mm. ...
Vent Tube fig 1 Outside Area that can be removed. Min Cut Line Inside Inside Outside fig 2 Installation, Cutting & Orientation Prepare Vent Tube. Cut out one of the Wiring Pockets Using a sharp blade, cut out the material highlighted to create an aperture to accommodate the 12v fan connection, fig 1.
External Louvre External Louvre, Screw Ports and Sealant Groove Fit three of the Spring Steel Clips to the positions on the External Louvre. Fit External Louvre. Louvre is a push fit. If screw fixing is desired drill out the three screw ports from the inside to the outside of the External Louvre using a Ø4mm drill.
Internal Bezel Note: Position of serial label to be visible when installed. Internal Bezel Fit the remaining three Spring Steel Clips to the positions on the Internal Bezel. Fit Internal Bezel. Internal Bezel is a push fit into the Vent Tube, when fitting ensure Wiring Aperture is aligned with the Wiring Pocket in the Vent Tube.
Internal Components Fit Internal Components Fit the first Ceramic Heat Cell. Slide a Ceramic Heat Cell into the Vent Tube. Ensure the Wire Handle is facing the inside and that the Ceramic Heat Cell is pushed up against the stop in the Vent Tube. Fit the Fan.
Diffuser Fit Wiring Cover and Diffuser Connect the Fan Cable. Using the push connector connect the Fan Cable to the Communication Cable, see wiring section for details. Fit the Air Filter, which is held in place by the Wiring Aperture Cover. Fit the Wiring Aperture Cover.
Wiring Fans Connection Connection of Fan Unit(s) to Controller is to be made with specified communication cable. Up to 3 pairs (six fans) can be connected to the controller by connecting multiple cables to each terminal or by using a separate larger capacity connector. Extract Supply Controller SRC1 FAN 1...
SRC1 Controller Unit All necessary control components are integrated in this device. The SRC1 Controller is designed to fit into a single flush mounting wall box. Mains External Digital Input Switch (optional) see note Fuse All Pole Isolator L1 N L1 N FAN 1 FAN 2...
Sensors Extract Supply Controller SRC1 FAN 1 FAN 2 B + - - + S 4 3 2 1 Surface Mount Sensors A B + - Flush Mount Sensors Sensor to controller connection Sensor Options Sensor type Surface mount Flush mount Relative humidity (RH) sensor TP610 TP614...
Sensor PCB, Encoder Highlighted The type of sensor will be detected automatically. For every type of sensor there are 3 threshold levels. The parameters are Humidity, CO2 and VOC threshold. For humidity only, one of three different sets of thresholds can be selected in the service menu. See below table of thresholds. Function threshold Fan speed Threshold value...
Service Menu The Service Menu can be used to configure external sensors and adjust other controller parameters and is based on the buttons and the LEDs. In order to enter the service menu, the two left buttons have to be held for at least five seconds. When in service mode, all three LEDs on the left side (cross ventilation, heat recovery and error) will be activated, either flashing or permanently lighting up.
Number Display Menu FLASH Function of digital input 1=sleep timer (Default) FLASH Fan level off allowed 1=not allowed (Default) 2=allowed FLASH Sensor sensitivity 1=low 2=medium (Default) FLASH 3=high FLASH LED brightness Increase and decrease using UP and DOWN arrows. Fan selection FLASH 1=Fan settings 1 (Default) 2=Fan settings 2...