Contents Installation. Description Introduction Operation The Home Screen The Output Screen The System Screen The SNMP Screen 4.4.1 SNMP Alarms 4.4.2 Email Alerts Initial Configuration Pin-outs Response Times Temperature Indications Specifications. Appendix 1 MIB File information MDU12-PMi Manual Issue 4...
Page 4
This Page is Blank MDU12-PMi Manual Issue 4...
SAFETY Installation. Unless otherwise stated TSL equipment may be installed at any angle or position within an operating temperature range of 5° ~ 30° C . The RJ45 connector is for use only with an Ethernet 10/100 system. All TSL equipment conforms to the EC Low Voltage Directive: EC Low Voltage Directive (73/23/EEC)(OJ L76 26.3.73)(LVD).
Page 6
WARRANTY, MAINTENANCE AND REPAIR All TSL equipment is guaranteed for one year from the date of delivery to the customer’s premises. If the equipment is to be stored for a significant period, please contact TSL concerning a possible extended warranty period.
Page 7
• Symptoms of the fault (to include switch setting positions, input signals etc): Packing Please ensure that the unit is well packed as all mechanical damage is chargeable. TSL recommends that you insure your equipment for transit damage. The original packaging, when available, should always be used when returning equipment..
Page 8
United Kingdom Type of Equipment: Mains Distribution Unit Model No: MDU12-PMi Part Number: TSLP- MDU12-PMi Date CE Mark Affixed: I, the undersigned, declare that the equipment specified above conforms to the quoted Directives and Standards. Place: Maidenhead, England Signature: Date:...
Power Manager Mains Distribution Unit MDU12-PMi FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE Description Features: • 19" 1RU. • 16 Amp Double Pole Breaker / Switch. • 12 Fused IEC outlets. • LED Indication Power - Blue - Power applied to the unit.
Upon connecting the unit to power it will go through a quick boot up procedure with normally the LEDs going from Red to Amber to Green. The following login screen will be seen. The unit is now on-line. The default IP address is 192.168.100.235 The Username is <<root>> The Password is <<telsys>> MDU12-PMi Manual Issue 4...
Page 11
This shows the total power consumed by the MDU in Watts, VA, and current in amps with the power factor. To navigate back to this page from any other, click on the TSL Logo at the top LHS of screen.
Page 12
The input circuit polarity may be set at either Normally Open, or Normally Closed as indicated. Press << Update >> when done. NB Allow the page to refresh before cycling the power to check the settings. MDU12-PMi Manual Issue 4...
LAN - Flashing Amber LAN connected & active Output LEDs 1-12 Green - Circuit on and fuse OK Amber – Circuit off and fuse OK. Red – Circuit off and fuse failed. Off – Circuit on but fuse has failed MDU12-PMi Manual Issue 4...
Lower and upper voltage alarm thresholds can be set from this page. If the input voltage breaks either threshold then an SNMP alarm, and email alert is generated. Press <<Update>> when done. NB Allow the page to refresh before cycling the power to check the settings. MDU12-PMi Manual Issue 4...
Page 15
The Status Screen This page shows the overall alarm status for the unit and refreshes every 10 seconds. MDU12-PMi Manual Issue 4...
Then put in the IP address of the email server, and the email address to where the alert should be sent. Your IT manager will be able to help in setting this up. Press << Update >> when done. NB Allow the page to refresh before cycling the power to check the settings. MDU12-PMi Manual Issue 4...
IP Address; Subnet Mask; Gateway; & Mac Address will be shown on the screen. Web interface (http) Using any browser (e.g. Microsoft Internet Explorer) you can browse to the IP address previously set. Use the username and password you have previously set to access the configuration pages. MDU12-PMi Manual Issue 4...
Going over or under the preset threshold generates an SNMP trap alarm, as detailed in the MIB. Specifications Input 110-240V AC 50/60Hz Max load 16A Power consumption 8W No load. Connector Powercon Power Consumption Output 110-240V AC Max load 10A per outlet, fused on front panel. Connectors 12 x IEC 3 pin MDU12-PMi Manual Issue 4...
Page 20
Ethernet Standard: IEEE 802.3 Physical layer 10/100 Base-T Data Rate: 10/100 Mbps (auto-sensing) Mode Full or half duplex (auto-sensing) Connector RJ45 MDU12-PMi Manual Issue 4...
Page 23
::= { alarmEntry 7 } ------- end of table alarmTotal OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The total number of alarms in the table" ::= { alarm 3 } alarmLocation OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION MDU12-PMi Manual Issue 4...
Page 24
"The equipment temperature has exceeded the maximum allowed" ::= 5 alarmEqptTempOkTrap TRAP-TYPE ENTERPRISE tslMIB VARIABLES alarmEqptTemp DESCRIPTION "The equipment temperature is now within limits" ::= 6 --------------------------------------------------- -------------- MDU12 specific MIB mdu12 OBJECT IDENTIFIER ::= { tslMIB 3 } MDU12-PMi Manual Issue 4...
Page 28
ENTERPRISE tslMIB VARIABLES mduVoltage DESCRIPTION "The voltage to the MDU has traversed a limit" ::= 8 mduTotalCurrentStatusTrap TRAP-TYPE ENTERPRISE tslMIB VARIABLES mduTotalCurrent DESCRIPTION "The total current through the MDU has traversed a limit" ::= 9 ------------ MDU12-PMi Manual Issue 4...