Applications Manual
System #4
Low Voltage Wiring
out sen
TT
BUS
1
2
3
Bosch
CRC100 or CRC200
Wiring:
Low Voltage
Wire Comfort Room Controller (CRC100 or
CRC200) to Terminal # 1 on back of Greenstar FS
Boiler
See Appendix A for Room Controller Settings
Heatronic Settings:
Boiler
Typical supply
Heating
temperatures
Dial
1
approx. 95 °F (35 °C)
2
approx. 109 °F (43 °C)
3
approx. 122 °F (50 °C)
4
approx. 140 °F (60 °C)
5
approx. 153 °F (67 °C)
6
approx. 167 °F (75 °C)
max
Approx. 194 °F (90°C)
DHW thermostat
min
e
max
Bosch Thermotechnology Corp.
DHW sen
LWCO
4
5
6
120 V Line
Ground
Neutral
Application
Frost protection
Radiant floor heating
Panel radiator system
Cast Iron radiator system
Baseboard & convector system
Typical DHW temperatures
approx. 104 °F (40 °C)
approx. 122 °F (50 °C)
approx. 140 °F (60 °C)
Line Voltage Wiring
L
L
N
black
white
ch pump
mains
for unmixed heating
120v/60 hz
(Not Used)
Note: For Low Water Cutoff Wiring see
Appendix E of this manual
Line Voltage
Wire Main power supply (120 v) to White molex
3
4
5
2
1
6
max
Bosch Greenstar | 13
N
reset
eco
3
4
e
2
6
1
max
Data subject to change